home · Other · Security and fire control panel S2000M. Where to buy S2000 in Tyumen at the best price? Instructions for using the s2000m device

Security and fire control panel S2000M. Where to buy S2000 in Tyumen at the best price? Instructions for using the s2000m device

Fire extinguishing control device S2000-ASPT, water fire extinguishing station control device Potok-3N, relay modules S2000-KPB and S2000-SP1, voice fire alarm device Rupor, system status indicator units: S2000-BKI, S2000-BI, S2000-PT and S2000-BI isp.01, devices for transmitting notifications via the S2000-IT telephone line and the GSM channel of the Orion UO, the S2000-2 access controller, additional remote keyboards S2000K and S2000-KS, as well as in the ISO ARM system "ORION" and "Orion" Pro".

Addressable reception and control panels of the S2000 series (analog and addressable alarm loops) have stable characteristics and belong to the category of “Universal alarm systems”.

Control of up to 127 devices (Bolid address system) connected to the remote control via the RS-485 interface;

Display on the LCD (liquid crystal) indicator of events occurring in the system;

Storing events in a non-volatile buffer with the ability to view them on the display and print them on a printer with a serial RS-232 interface;

Signaling of alarms and events with a built-in sound signaling device;

Control of arming/disarming and monitoring the status of alarm loops from the remote control;

Programming configuration parameters of devices, printing the configuration on a printer, setting addresses of devices and addressable devices;

Restrict access to control and programming functions using passwords.


Technical characteristics of S2000M (Bolid)

PARAMETER NAME PARAMETER VALUE
Number of ISO “Orion” instruments and devices connected to the RS-485 line, no more
RS-485 interface 1
Length of RS-485 communication line, no more 3000 m
RS-232 interface 1
Number of devices connected to the RS-232 output

1
(computer with workstation, printer, radio transmitter ATS100 or TRX-150 (via converter) or radio transmitter RS-202TD)

Length of RS-232 communication line, no more 20 m
Number of alarm loops and addressable detectors grouped into sections, no more 2048
Number of automatically controlled relay outputs, no more 256
Number of sections, no more 511
Number of partition groups, no more 128
Number of user passwords, no more 2047
Output overvoltage protection 2 steps
Event log volume 8000
LCD indicator 2 lines x 16 characters, backlit
Nutrition from a redundant DC source
Supply voltage 10.2 to 28.4 V
Average current consumption in standby mode at supply voltage 12 V / 24 V 60 mA / 35 mA
Maximum current consumption in alarm mode at supply voltage 12 V / 24 V 120 mA / 65 mA
Operating temperature range from minus 10 to +55 °C
Shell protection degree IP30 (when mounted on a wall)
Weight, no more 0.3 kg
dimensions 140x114x25 mm
Type of connection to the device screw terminal block, wire from 0.2 to 1.5 sq. mm
Installation method wall-mounted

Full list of functions of the fire and security control panel Bolide S2000M:

The ability to combine individual fire alarm loops into sections, while supporting a larger number of loops than the previous S2000 analogue, which allows it to be used at particularly large facilities;

Display of text names on a large LCD display, sections and user names in the event log. The length of the display line is 32 characters. It is now possible to specify a text description of users, partition groups, partitions and fire alarm loops;

Increased maximum number of system users (PIN and TouchMemory);

Sections can be combined into section groups. This allows group control of arming and disarming. Any group can include any partition of the system;

Control of arming, disarming and monitoring the status of system sections, both from the remote control and from the S2000-K keyboard, S2000-KS remote control and S2000-4 device. At the same time, control powers are delimited by passwords (control rights for arming/unlocking partitions are set for users and separately for each connected device).

Possibility of software automatic control of relay outputs of relay blocks S2000-SP1, S2000-SP2 and S2000-KPB linked to the state of the sections. Ability to control the outputs of S2000-4, Signal-20P and Signal-20 series 02 devices and other ISO Orion devices. Ability to control relay outputs with a specified delay time;

Control of displaying the states of sections on the S2000-BI and S2000-BKI display units (and other display units);

The S2000M remote control transmits (duplicates) events occurring in the system to the S2000-K keyboards for their display on the indicator and the device for transmitting information via the telephone line (informant) S2000-IT;

For convenient logging of events and displaying the states of sections and loops of the fire alarm system, the monitoring and control panel can be connected to a personal computer with the Orion Pro automated workstation software;

Also in the “programming” mode, the remote control can perform the function of a converter of RS 232 - RS 485 interfaces. This function allows you to configure the remote control and the devices of the Bolid address system connected to it;

The remote control has the ability to connect several fire alarm subsystems based on the S2000M remote control to a personal computer with an Orion workstation;

When disconnected from the PC, the S2000M goes into offline mode and continues to work with the specified configurations;

Programming and configuration of the S2000M monitoring and control panel is carried out using the program (utility) "pprog.exe" or the "Database Administrator" program from the Orion Pro workstation, which can be downloaded on the official website of the Bolid company, or on the website of the ABars company in the "Documentation" section (there you will also find the connection diagram and passport of this network controller).

A wide range of devices for security alarm systems of the BOLID brand allows you to choose a model for any request and functionality. A large selection will please companies engaged in the installation of fire and security alarm systems and their Customers.

Although the S2000M belongs to the category " inexpensive OPS remotes", it is reliable, like all other elements of the Bolid brand.

Alarm system for office;
Security and fire alarms for cafes and clubs;
Alarm in the store;
Security systems for warehouses and office premises;
Autonomous alarm system for an apartment, house or cottage;
Fire alarm for covered parking lots, garages and parking lots;
Comprehensive protection for government institutions (kindergartens, schools, other educational institutions)

When choosing, pay special attention to carefully studying the technical characteristics, choosing suitable security detectors, fire detectors, and special cable products. Devices of the S2000 line are among the best in terms of price-quality ratio and are recommended for use in wide-spectrum security and fire alarm systems. All control panels (PKP) of this brand can be operated with most of the backup power supplies presented on this site.

Analogues of S2000M and other devices with similar characteristics: S2000

Buy and order delivery of fire alarm systems in Moscow:

You can order and buy the S2000M remote control, as well as other Bolid products (their analogues, detectors, relays) through the fire alarm online store on our website or order delivery and professional installation services in your premises in Moscow from the ABars company. (Attention, delivery is free for orders over 60 thousand rubles).

    The following features have been added:
  • Added a new "duress code" password attribute. When an object is controlled by a duress code, it is transferred to the “Derress” alarm state. Duress is displayed as an alarm condition when the ATTACK state's alarm setting is set to ALARM WITH SOUND or ALARM WITHOUT SOUND, and is hidden when the setting is set to NON ALARM. When a partition is disarmed using the duress code, the “DURES DISARMED” event is generated. The “Dussion code presented” event is supported, which sets the “Derress” alarm state for the “reader” object (intended to generate an alarm when accessing the ACS using a duress code). This alarm is reset by the manual command "Reset alarms". The Duress state controls outputs with programs 54 “Turn on during attack” and 55 “Turn off during attack” (“Attack” includes the states “Dress” and “Silent alarm”).
  • Added control function for one touch of the TM key/card to the reader. To do this, access levels now have the “Control Style” attribute, which takes two values: 1) “Display state, then manage”; 2) "Manage immediately." If the control style is set to “Manage immediately”, then when you bring a key with partition management rights to the reader, the partition is immediately managed. This management style is suitable for users with management rights to one partition.
  • Added alarm settings for events:
    • "Assault" (includes "Coercion" and "Silent Alarm");
    • "Entry alarm".
  • Added relay control programs:
    • 54 "Enable during attack";
    • 55 "Turn off when attacked";
    • 56 "Lamp 2";
    • 57 "Siren 2".
    The programs "Lamp 2", "Siren 2" are intended for radio annunciators with autonomous power supply. A setting has been added that allows you to control relays with programs 1 – 8 with a delay during “Fire 2” (as in “S2000M” version 2.07).
    Changes to existing features:
  • For ease of use of the S2000M, the user interface of the main operating mode has been redesigned:
    • The number of required actions to view alarms, fires, starts, and faults has been reduced. The display of the number of sections with alarms, fires, starts, and malfunctions has been changed;
    • the proposed control commands better correspond to the state of the partition and its type (for example, for a security partition in an alarm, a disarming command is proposed);
    • events displayed on the screen in standby mode do not interfere with entering the password using the numeric buttons.
  • Added display of the number of sections containing actuators that are blocked or in manual control mode (automation is disabled), added viewing of sections with automation states “Blocking” and “Manual control” (“Automation is disabled”). A filter has been added to the event log by event type "Blocking";
  • Setting up event broadcasting for the “S2000 Remote Control” object in the PProg program now only affects the operational display of ongoing events on the screen, and all events are available in the log. This makes it possible to disable the live display of events. When the event display is turned off, the indication of the object’s state - the presence of alarms, fires, starts, shutdowns, faults and shutdowns - is retained.
  • The user number has been added to the “Partition armed” and “Partition disarmed” events, if a partition (group of partitions) is armed or disarmed not entirely by the partition control command, but in parts. Examples:
    • a section (group) was armed (disarmed) as a result of local control of the loops of this section (arming or disarming with keys recorded in the “S2000-4”, “Signal-10” receiving and control unit);
    • a group of partitions was armed (disarmed) as a result of arming (disarming) the partitions of the group. The “Partition removed” event has also been generated when it is disabled. These changes are useful when using notification transmission in the Ademco Contact ID or LARS protocols.
  • Two parameters have been added to the LARS protocol settings: which user number to transmit in the “partition taken” and “partition removed” events if the user number is unknown, and which user number to transmit if the user number in the event exceeds the maximum possible value. The default settings of these parameters correspond to the operating tactics of "S2000M" version 2.06: the events "partition taken" and "partition removed" are not transmitted if the user is unknown, and events with a user number that is too large are transmitted with the maximum allowable user number. The operation tactics of "S2000M" version 2.07 can be obtained if you set "1" as the number for the unknown user.
  • The names of the events have been changed: “WATER LEAKAGE” to “FLOODING”, “NO WATER LEAKAGE” to “DZ RESTORATION”, “OVERGR.RIP DEVICE” to “CURRENT IS NORMAL”.
    Bugs fixed:
  • It was possible for a one-time false activation of the relay after configuration by the PProg program if the relay control programs were changed.
  • Fixed a bug in the "input loops" function. The conflict of “input loops” configured simultaneously in the “S2000M” and the receiving and control unit has been eliminated (with simultaneous configuration, the “input loops” will work according to the settings of the receiving and control unit).
  • The event with the result of the operation was not displayed when directly controlling the device's AL (password with access level 253 - 255).
  • The "Partition Armed" event was not generated if the partition was armed with a key with alarm control rights (a key recorded in the "S2000-4" or "Signal-10" receiving and control unit), and the partition had an alarm zone with arming delay on guard. The messages “Partition taken” / “Partition removed” might not be generated if some of the partition inputs were set / removed by alarm loop control scripts.
  • If the user first selected an action with the "RESET", "START", "STOP" key or pressed the context menu key, then identified himself (entered a password) and then exited viewing sections with the " ×", the message "Invalid partition" might be displayed.
  • There may have been no initial indication of the state of the actuators (outputs of the “technological equipment” type) on the “S2000-BI/BKI” after the “S2000M” was exited from the programming mode before the state of the actuators changed.
  • The transfer of control requests from "S2000-K" and "S2000-KS" to the "Orion Pro" workstation did not work when the "CENTRAL CONTROL" parameter was enabled.
    Compatibility Details:
  • Configuration with the program "Pprog.exe" version 3.03 build 1 or higher.

The fire-security monitoring and control panel "S2000M" is designed to work as part of an addressable fire-security alarm system and control of fire-fighting equipment. Together with ISO “Orion” devices, it can perform the functions of a block-modular security and fire alarm control device, a control device for light, sound and voice warning, gas, powder aerosol and water fire extinguishing, smoke protection, and building engineering systems. Information interaction between the blocks is carried out via a wired RS-485 communication line. The functions of the device can be expanded by connecting additional units.

Peculiarities

Indication of the “Alarm”, “Fire”, “Start”, “Stop”, “Fault”, “Disabled” modes. Ability to view individual zones (sections) and system elements that have these states, with display on a symbolic indicator. Sound signaling of alarms, fires, starts and malfunctions on the built-in sound signaling device. Indication of the status of security zones, fire-fighting equipment and other actuators on the blocks "S2000-BI", "S2000-BKI", "S2000-PT", "Potok-BKI"
Automatic control of light and sound warning devices, smoke protection, engineering equipment, alarm, fire, start and fault signal transmission outputs using control and start and signal and start units, receiving and control units. Automatic start and stop of voice alarm devices of the "Horn" series. Automatic control of operating modes of the access control and management subsystem to unblock escape routes in case of fire.
Manual control from the remote control keyboard and display units:
control of security and fire alarm operating modes: arming, disarming, resetting alarms, disabling detectors and actuators (only those controlled by the remote control);
manual start and stop of light, sound and voice warning systems, smoke protection, and engineering equipment;
control of "S2000-ASPT" devices using "S2000-PT" units: manual start and stop of the fire extinguishing installation, suspension of the start delay and immediate start without delay, selection of automatic or manual control mode for the fire extinguishing installation, alarm reset;
control of Potok-3N devices using Potok-BKI units: manual start and stop of the fire extinguishing installation, selection of automatic or manual installation control mode
Possibility of connecting to the Orion Pro automated workstation to expand the capabilities of monitoring the status of the protected object and control
Possibility of transmitting notifications to the security console using communication blocks "S2000-IT", "UO-4S", "S2000-PGE" and "S2000-PP". Possibility of connecting the ATS100 radio transmitter of the LARS radio security system, RS-202TD of the "Reef String 202" ("LONTA 202") radio security system or TRX-150 for transmitting notifications via radio channel
Event log with the ability to view it on the remote control screen and print it on a printer with a serial RS-232 interface
Configuring the remote control in the program "Pprog.exe"