Mechanical and electrical temperature sensors in contact with the medium whose temperature is being measured (this does not include radiation pyrometers) are subject to the following methodological errors.

1. Error due to losses from thermal radiation and thermal conductivity. This error is due to the fact that the temperature of the pipeline walls differs from the measured temperature of the gas or liquid flowing through this pipeline. As a result, along with beneficial heat exchange between the medium and the sensor, harmful heat exchange occurs between the sensor and the walls of the pipeline due to radiation and thermal conductivity (due to the outflow of heat to the location where the sensor is attached). This leads to the fact that the temperature of the sensor differs from the temperature of the medium and a methodological error occurs. To reduce this error, it is necessary to increase the length of the immersed part and the perimeter of the sensor, reduce the wall thickness, and thermally insulate inner surface pipeline, the non-immersed part of the sensor and its mounting location.

2. Error due to incomplete braking of the gas flow. In thermometers designed to measure true temperature T counter flow of air, an error occurs, the cause of which is an increase in the temperature of the sensor due to the conversion of the kinetic energy of the air flow into heat when it is braked by the sensor.

Full braking temperature

Due to incomplete flow deceleration, the sensor temperature does not reach the temperature T P, it is determined by the formula

,

Where r – braking coefficient depending on the shape of the sensor.

For some sensor forms the coefficient r has the following meanings:

for a cylinder located transverse to the flow, r = 0,65;

for a cylinder located along the flow, r=0,87;

for sphere r = 0,75.

Relative error of true temperature measurement

.

This error can be taken into account by introducing a correction; in navigation computing devices, this correction is introduced automatically.

In thermometers designed to measure temperature T P inhibited gases, the error arises due to incomplete inhibition of the flow by the sensor.

Relative error of braking temperature measurement

.

This error can also be taken into account by introducing a correction.

3. Dynamic error. This error is due to the fact that heat is transferred from the medium to the sensing element with some delay due to the finite rate of heat transfer, which depends on the material of the mass and the surface of the thermal cartridge.

The thermal inertia of a thermometer in a linear approximation is characterized by its transfer function (3.3):

,

Where S T – sensitivity


T 1 – time constant()

  • 2.5. Induction converters
  • 2.6. Thermoelectric converters
  • 2.7. Piezoelectric transducers
  • 2.8. Converters with spatial encoding devices
  • 2.9. Gyroscopic instruments and devices
  • 2.9.1. Three-degree gyros
  • 2.9.2. Two-degree gyroscopes
  • Chapter 3. Fiber Optic Sensors
  • 3.1. Interaction of optical radiation with optical media
  • 3.2. Principles of conversion in fiber-optic sensors of physical quantities
  • 3.3. Amplitude waters (waters with intensity modulation)
  • 3.4. Polarization type fiber optic sensors
  • 3.5. Fiber optic sensors based on micromechanical resonators excited by light
  • 3.6. Characteristics of microresonator waters of physical quantities
  • 3.7. Optical multiplexing of waters of physical quantities
  • 3.8. Fiber Optic Gyroscopes
  • 3.9. Optical elements used in fiber optic sensors
  • Chapter 4. Features of designing pressure sensors
  • 4.1. Pressure measurement tasks
  • 4.2. Principles of constructing analog and discrete pressure sensors
  • 4.3. Impact of influencing factors on pressure sensors
  • 4.4. Dynamic errors when measuring variable pressures
  • 4.5. Features of operation and installation of pressure sensors
  • Chapter 5. Temperature and heat flow sensors
  • 5.1. Physical basis of temperature measurements
  • Values ​​of wavelengths corresponding to the spectral maximum of radiation and the total spectral luminosity for various temperatures of a black body
  • 5.2. Errors in temperature measurements using contact sensors
  • 5.3. Main tasks of heat flow measurements
  • 5.4. Classification of heat flow sensors
  • 5.5. Physical models of “thermal” heat flow sensors
  • 5.6. Non-contact temperature meters
  • 5.7. Thermal photodetectors
  • 5.8. Application of pyroelectrics
  • Chapter 6: Magnetic Field Controlled Components and Sensors
  • 6.1. Magnetoelastic transducers
  • 6.2. Galvanomagnetic recombination converters
  • 6.3. Wiegand sensors
  • Chapter 7. Features of the design and application of biological, chemical, medical sensors
  • 7.1. Biosensors
  • 7.2. Gas composition sensors
  • 7.3. Chemical measurements
  • 7.4. Medical sensors
  • Chapter 8 Smart Sensors
  • 8.1. Features of “intelligent” sensors of physical quantities
  • 8.2. Functionality and requirements for smart sensors
  • 8.3. Microprocessor modules for intelligent information processing
  • 8.4. Measuring channel of “smart” sensors
  • 8.5. Basic criteria for choosing a microcontroller
  • 8.6. Universal converter interface
  • 8.7 Standardization of smart sensor interfaces (ieee p 1451 family)
  • 8.8. Error correction in smart sensors
  • 8.9. Prospects for the development and production of intelligent microsensory products in the Republic of Belarus
  • 8.10. Examples of implementation of “intellectualization” of sensors
  • Chapter 9. Interfacing converters with measuring equipment
  • 9.1. Connection diagrams of measuring transducers
  • 9.2. Temperature compensation of strain gauges
  • 9.3. Temperature compensation using bridge circuits
  • 9.4. Installation of strain gauges
  • 9.5. Noises
  • 9.6. Protective rings
  • 9.7. Random noise
  • 9.8. Noise figure
  • Chapter 10 features of design and testing of sensors
  • 10.1. Execution depending on the influence of environmental climatic factors
  • 10.2. Design depending on the degree of protection from exposure to solids (dust) and fresh water
  • 10.3. Design depending on resistance to sinusoidal vibration
  • 10.4. Sensor reliability
  • Literature
  • Content
  • Chapter 1. Features of sensor equipment 81
  • Chapter 2. Principles of conversion in sensors 110
  • 2.9.1. Three-degree gyroscopes 171
  • 2.9.1.6. Vibration gyroscope 176
  • 2.9.2. Two-degree gyroscopes 177
  • Chapter 3. Fiber Optic Sensors 182
  • Chapter 4. Design Features
  • Chapter 5. Temperature sensors and
  • Chapter 6. Components and sensors,
  • Chapter 7. Design Features
  • Chapter 8 “smart” sensors 347
  • Chapter 9. Interfacing Converters
  • Chapter 10 performance features and
  • 5.2. Errors temperature measurements contact sensors

    Errors in temperature measurements are discussed in many monographs and publications, the number of which amounts to hundreds and even thousands. Here we will consider this problem briefly, simplified, schematically based on the most typical measurement situations. The main goal of this consideration is to focus on the correct choice of sensor, meaningful, expedient organization of a measurement experiment that ensures a reduction; inevitable errors, as well as the possibility of their approximate assessment.

    We will consider here only errors of thermal origin, caused by various thermophysical characteristics of the sensor and the measured object, as well as the influence on the formation of the temperature field of the sensor not only of the main type of heat transfer, due to which the temperature of the sensitive element of the sensor should be equal to the measured temperature of the object, but also of secondary types of heat transfer, distorting the temperature field of the sensor. These reasons lead to the fact that when measuring stationary temperatures, the steady-state temperature value of the sensor differs from the measured temperature of the object. This difference is the error caused by secondary types of heat transfer.

    When measuring non-stationary temperatures, an error is added, which is usually called dynamic, caused by the thermal inertia of the sensor. And secondary types of heat transfer contribute to this error.

    In addition, in the presence of external energy sources, in the event of their interaction with the sensor, it is also possible to distort the temperature of the sensor, which is in the nature of additional heating, forming a corresponding sensor error. Such errors include errors caused by the conversion of the kinetic energy of a high-speed gas flow during its braking at the sensor into the enthalpy of the sensor, as well as heating of the sensitive element of the resistance thermometer by the measuring current.

    As already noted, the temperature of the surfaces of structural elements is measured using resistance thermometers and thermocouples. The smaller the size of the sensor, the smaller its own heat capacity and thermal resistance, and the smaller the influence of secondary types of heat transfer (in this case, the main heat transfer process is conductive heat exchange between the measured surface and the sensor), the smaller the errors in such measurements.

    Consider measuring the temperature of a plate of thickness L 0 flat resistance thermometer. On both sides of the plate, the conditions presented in Fig. 5.3, a. Here α 1 and α 2 are the coefficients of convective heat exchange between the surfaces of the plate and the medium; T 1 And T 2 ambient temperature; T C1 and T C2 is the temperature of the plate surfaces; l d sensor thickness. Both the sensor and the plate have a relatively finite thickness l d And l 0 , other sizes are unlimited. Thus, it is assumed that the case b) corresponds to the case where the sensor is located on the side opposite to the heating source, the case V) from the side of the heating source, and installing the sensor does not change the heat transfer coefficients α 1 and α 2 .

    It is assumed that the temperature measured by the sensor corresponds to the placement of the sensing element in its central section (L D /2).

    Let us denote by Λ 0 and Λ d the thermal conductivity coefficients of the plate and sensor, respectively.

    When measuring the stationary temperature of a plate, the error has the form:

    for the occasion b):

    (5.12)

    for the occasion V):

    (5.13)

    Because the L d d = P d , L 0 / Λ 0 = P 0 thermal resistances of the sensor and plate, respectively, we can rewrite the given error relations in terms of thermal resistances: case b):

    (5.14)

    (5.15)

    When measuring non-stationary temperatures, expressions for steady-state errors under the assumption that the measured surface temperature varies linearly T WITH = T 0 + And α 2 = 0, have the form:

    happening b):

    (5.16)

    happening V):

    (5.17)

    (5.18)

    (5.19)

    The assumption that the heat transfer coefficient on the side opposite the heating source is equal to zero means the assumption of adiabatic insulation of the plate, i.e. it is assumed that all the heat entering it is spent on heating it. This case, to a first approximation, is realized when physical insulation of the plate is introduced on the side opposite to the heating source, or at very low heat transfer coefficients (calm air, rarefied environment during flights at high altitudes). It was thanks to this assumption that it was possible to obtain such simple expressions T mouth .

    If the plate is thin and its material has a high thermal conductivity coefficient, then Δ T mouth almost independent of thermal resistance plates. Addiction Δ T mouth from α 1 is hyperbolic in nature, a noticeable dependence at small values α 1 and the dependence practically disappears when α 1 >1000 W/m 2 deg. Thus, the error value is mainly determined by the thermophysical parameters of the sensor. These parameters for the main reinforcing materials of surface resistance thermometers are given in Table. 5.4.

    Table 5.4

    Values ​​of C d, P d for materials reinforcing the surface of resistance thermometers

    Let us consider the error in measuring the plate temperature with a thermocouple for the case shown in Fig. 5.4.

    P lamina thickness L 0 be in heat exchange with the environment on both sides of the plate. Accordingly, the heat exchange coefficients with the environment α 1 And α 2 and ambient temperature T 1 And T 2 . Radius of thermocouple thermoelectrodes r d , thermal conductivity of thermoelectrodes is assumed to be the same Λ d .

    We consider the influence of a thermocouple as the action of a heat source Qπ R 2 L 0 (R is the radius of the source).

    (5.20)

    We consider the influence of a thermocouple as the action of a heat source Q, occupying an area in the plate with a volume π R 2 L 0 (R is the radius of the source).

    Then the temperature of the plate in the zone remote from the action of the source is

    (5.21)

    and relative error

    (5.22)

    Where K 0 (μ ), K 1 (μ ) – modified Bessel functions of zero and first order;

    (5.23)

    (5.24)

    – heat transfer coefficient of thermocouple thermoelectrodes. Here δ from And Λ from– respectively, the thickness and thermal conductivity coefficient of the insulation of thermocouple thermoelectrodes; α d– heat exchange coefficient of thermoelectrodes with environment;

    (5.25)

    Thermocouple errors for the case shown in Fig. 5.4 are limiting. They can be significantly reduced if the thermoelectrodes are first laid along the measured isothermal surface at a sufficient length (the criterion for sufficiency is the ratio l/ r d>50), and then move away from the surface.

    Consideration of the errors of the sensor measuring the temperature of the medium will be reduced to the general diagram presented in Fig. 5.5. The medium can be either gas or liquid.

    Designations in Fig. 5.5 T Wed– temperature of the measured medium; T d – temperature measured by the sensor; T st– temperature of the sensor body. It is assumed that T Wed > T d > T st > T To α Wed - coefficient of convective heat exchange between the medium and the sensor; ε d , ε st– emissivity coefficients of the sensor surface and wall; q conv , q cond , q glad– convective, conductive y, radiation heat flows (the last two characterize the thermal losses of the sensor for the measurement situation under consideration); V av – free-flow velocity.

    To simplify the consideration, the distribution of temperature and velocity of the medium in the line is assumed to be uniform. The sensor is considered as a rod with a uniform distribution of thermophysical characteristics (for real structures, effective values ​​should be taken). The rod is a temperature meter for the medium. In the stationary case, if there were no heat losses from the rod to the colder body (q cond) and losses due to radiation to the colder walls (q rad) and if there were no errors due to braking, then the sensor would measure the temperature of the medium. If the temperature of the medium changes over time, then a dynamic error occurs due to the thermal inertia of the sensor. In reality, sensor errors are formed by the following components:

    The combined manifestation of errors caused by conductive heat loss and dynamic heat loss can be called static-dynamic error

    (5.27)

    With the formulated simplifications, this error

    (5.28)

    (it is assumed that the temperature at the sensor changes abruptly to T av from the initial value T d (0) = 0). Here

    (5.29)

    – temperature of convective heating of the sensor;
    –specific heat capacity, specific gravity, cross-sectional area of ​​the sensor rod;

    (5.30)

    – temperature of conductive heat transfer of the sensor rod; A– effective coefficient of thermal diffusivity of the sensor rod; L rod length.

    It can be seen that the presence of a heat sink from the rod to the sensor body leads to the formation of a static error

    (5.31)

    It can also be seen that the dynamic error decreases in the presence of conductive heat transfer.

    In fact, the rate of change in the temperature of the sensor rod

    (5.32)

    and thermal inertia is the reciprocal of tempo.

    Depending on heat transfer conditions and rod structure

    , (5.33)

    Where ψ(α dk )  coefficient of unevenness of the temperature field of the rod; a dt , coefficient of “conductive heat transfer” of the rod; F – thermal factor. Because the

    (5.34)

    (5.35)

    Reciprocal of tempo M called thermal inertia coefficient

    ε = 1/M,(5.36)

    and addiction ε (a dk ) characteristic curve of thermal inertia.

    Thus, the error caused by the joint manifestation of thermal inertia and heat removal depends on the coefficients of convective and conductive heat transfer, the thermal factor Ф and the coefficient of unevenness of the temperature field of the rod ψ(α dk ).

    The overall error in measurements increases with increasing heat sink to the body, because in the presence of a heat sink, the more quickly the steady-state temperature value is realized, the more it is distorted by the static error of the heat sink.

    Determining the values ​​of static errors and characteristic curves of thermal inertia comes down to finding three parameters that characterize the sensor: α dt , ψ(α dk ) , Φ . Magnitude ψ(α dk ) can be represented in the form

    (5.37)

    (5.38)

     equivalent of the thermal resistance of the sensor rod. For a rod shape in the form of a plate n = 3, in the form of a cylinder - n = 4, in the form of a ball - n = 5 (strictly valid for conditions of regular thermal regime second kind).

    If the rod has a heterogeneous structure - a uniform shell (protective casing) with a core with low thermal conductivity and noticeable thermal resistance, then the limiting value of the coefficient of thermal inertia is determined by the core of the rod (ε ∞ = HF), and the static error is the thermal conductivity of the shell. In this case, the value α dt is easily calculated if you know the geometric dimensions of the shell and the thermal conductivity coefficient of the casing material.

    Summary data on the values ​​of static-dynamic parameters of some representative design types of sensors are given in Table. 5.5.

    Table 5.5

    Static-dynamic parameters of temperature sensors

    Sensor type

    α dt , W/(m 2 K)

    W s/(m 2 K)

    X 10 4 ,

    The dynamic error when knowing the coefficient of thermal inertia ε is estimated by the formula:

    (5.39)

    Where b– rate of temperature change.

    The error caused by the radiation heat exchange of the sensor with the walls of the pipeline, which have a temperature lower than the measured temperature of the medium, can be estimated from the following consideration.

    If the gas whose temperature is measured is transparent, then the specific heat flux from the sensor to the walls is:

    (5.40)

    (5.41)

    – coefficient of radiant heat exchange between the sensor and the wall ( ε s – black body emissivity coefficient); s d / s st the ratio of the surface areas of the sensor and the wall exposed to radiation heat exchange.

    If we consider the stationary problem of equality of the heat flux supplied to the sensor due to convection and heat loss to the walls due to radiation, then the joint solution of q conv and q rad relative to T d allows you to get a steady value T d And

    (5.42)

    An effective way to reduce errors caused by radiation losses (by almost an order of magnitude) is to introduce an anti-radiation screen between the sensor and the walls. It is also necessary to keep in mind that at ambient temperatures above plus 500°C, the gas’s own radiation appears, which itself has a shielding effect. Approximately the same effect can be achieved by introducing coatings of the sensitive element of the sensor that have low emissivity coefficients (silver, gold, platinum).

    When the flow is decelerated at the sensor, the sensor measures a temperature that exceeds the equilibrium thermodynamic temperature of the gas flow, but does not reach the stagnation temperature value, since the deceleration of the flow at the sensor is incomplete. If Tsr equilibrium thermodynamic temperature of the gas flow, and T*- braking temperature

    (5.43)

    Where K = c h / c v - ratio of specific heat capacities of gas at constant pressure and constant volume; M =V Wed / V sound Mach number, i.e. the ratio of the flow speed to the local speed of sound, then

    (5.44)

    Where r recovery coefficient, characterizing the incompleteness of conversion of the kinetic energy of the flow at the sensor into thermal energy.

    Most favorable with from the point of view of the definability and stability of the coefficient of restitution is the longitudinal flow around bodies, in which independence of the coefficient is observed in a wide range of Mach and Reynolds numbers r.

    So for a plate thermometer the value r is 0.85. Flow sensitive elements of sensors on a thin-walled tube of small diameter have r = 0.86...0.9, for longitudinally streamlined wire thermocouples r = 0,85... 0,87.

    In cross flow around open wire thermocouples r≈ 0.68 ± 0.08.

    An effective way to increase the recovery coefficient is to use braking chambers in sensors (an open input with an output hole reduced in area by 25...50 times). With longitudinal flow around a thermocouple in the braking chamber r ≈ 0.98, with transverse r ≈ 0,92... 0,96.

    If the working junction of the thermocouple is made in the form of a ball whose diameter exceeds the diameter of the thermoelectrodes, then both in longitudinal and transverse flow r ≈ 0,75.

    The correction for determining the static temperature of the flow from the measured equilibrium temperature (or the error if it is not taken into account) has a negative sign and is equal to:

    (5.45)

    Errors caused by the uneven distribution of temperature across the flow cross section when measured by sensitive elements distributed over the surface require separate consideration.

    The role of errors in high-temperature measurements caused by the loss of insulation of reinforcing materials is significant.

    For resistance thermometers, the possibility of heating the sensitive element of the thermometer by the measuring current and the associated error, the magnitude of which depends both on the intensity of heat exchange between the thermometer and the environment, and on the thermal resistance and heat capacity of the materials reinforcing the sensitive element, must be taken into account.

    When measuring temperature in fields of penetrating radiation, errors due to both instantaneous and integral effects depending on the magnitude of the radiation must be taken into account.

    It should be understood that obtaining the information necessary to estimate errors is by no means easier than obtaining basic information. Therefore, they often resort to assessing the maximum error values ​​in order to make sure that they are acceptable.

    However, the main thing is to understand the nature of errors and the patterns of their manifestation, since this is the key to the appropriate selection of a sensor and the proper organization of measurements.

    Design and production of sensors, devices and systems

    UDC 681.586"326:621.3.088.228

    ON NORMALIZING THE TEMPERATURE ERROR OF STRAIN GAUGE SEMICONDUCTOR SENSORS

    V. M. Stuchebnikov

    For strain gauge sensors of mechanical quantities operating in a wide temperature range, the standardization of additional temperature error using the linear temperature coefficient leads to a significant distortion of the measurement results. The article shows that it is more correct to normalize the temperature error zone in the temperature range in which the sensors are thermally compensated. This is especially important for semiconductor strain gauge sensors with nonlinear temperature dependence of the output signal.

    Additional temperature error is important characteristic sensors of mechanical quantities, which determines the error of their measurement. Therefore, it is always indicated among the main parameters of these sensors. Most manufacturers normalize the additional temperature error using a linear temperature coefficient, that is, as a percentage of the sensor output range of one or ten degrees Celsius (or Fahrenheit in English-speaking countries). In this case, as a rule, it is assumed that the sign of the temperature error can be of any kind, so it is usually indicated as ±y %/°C (or ±y %/10 °C). So it is recommended to normalize the temperature error and regulations IEC (for example,), and after them Russian standards (for example,).

    This article discusses the disadvantages of this method of normalizing the additional temperature error of sensors of mechanical quantities, which are especially evident in strain gauge sensors. semiconductor sensors, which today constitute the majority of sensors used for pressure, force, motion parameters, etc. In specific examples, strain gauge pressure sensors based on heteroepitaxial silicon-on-sapphire (SOS) structures, widely used in Russia, are used.

    It is quite obvious, firstly, that the specified rationing makes sense only when linear dependence sensor output signal from temperature. However, a linear approximation of the temperature dependence of the output signal of a strain gauge sensor with an acceptable degree of accuracy can only be used for sensors with metal strain gauge resistors and/or in a relatively small temperature range. Since semiconductors are characterized by a strong and nonlinear dependence of parameters on temperature, the output signal of semiconductor strain gauge sensors, as a rule, is significant.

    strongly nonlinearly depends on temperature, which is especially noticeable when operating in a wide temperature range.

    Secondly, this rationing actually disorients the consumer, forcing him to double the real measurement error. The fact is that for specific sensors with a linear temperature dependence of the output signal, the slope of this dependence has a very definite sign, so the signal can only either decrease or increase with temperature. By expressing the normalization of the temperature error in %/°C indicating a certain value and sign, the consumer can actually evaluate and take into account the measurement error, for example, pressure, at certain temperature; however, if the sign is not determined, then the measurement uncertainty increases greatly.

    This is illustrated in Fig. 1. In Fig. 1a shows the case when the measured pressure (proportional to the sensor output signal) decreases linearly with increasing temperature. In this case, at a known temperature "meas", the consumer can take into account the temperature error and bring the pressure measured by the sensor rms to the actual pressure rn, which is normalized at the "normal" temperature "n:

    Рн = Rizm - U ("izm - "nX (1)

    where y is the slope of the dependence p (") (y< 0). Конечно, при этом, как минимум, сохраняется неопределенность фактического давления, определяемая основной погрешностью датчика (полоса, ограниченная штриховыми прямыми на рис. 1, а).

    The situation is completely different when the sign of the temperature error is not determined (see Fig. 1, b). In this case, even at a known measurement temperature, the uncertainty of the measured pressure is Dr = (рн1 - рн2) even without taking into account the main error of the sensor.

    Of course, if the measurement temperature is unknown even approximately, and all that is known about it is that it

    Rice. 1. Temperature error of pressure measurement with a linear dependence of the sensor output signal on temperature in the case of a negative (a) and uncertain (b) sign of the linear temperature coefficient y

    lies within the (max - min) operating temperature range, the resulting pressure measurement uncertainty is

    "Рм = (Р2 - Р1) = IУI ("max - "min) (2)

    regardless of whether the sign of the slope coefficient of the straight line p(") is known or not.

    Let us consider the case of nonlinear temperature dependence of the output signal of a strain gauge transducer (TC). For example, for pressure transformers based on SOS structures, the temperature drift of which is compensated by a circuit with thermally independent resistors, the dependence of the output signal on temperature is close to parabolic. Silicon TCs with diffusion or implanted strain gauges have a similar dependence. Accordingly, the pressure measured by a sensor with such a TP (proportional to the output signal of the sensor) is also not

    linearly depends on temperature (Fig. 2), unless special measures are taken to further correct it in electronic circuit, for example, using a microprocessor. In this case, in accordance with the letter of the regulatory documents, if we normalize the temperature error linear coefficient, then it is necessary to indicate the maximum (in absolute value) value of the slope + umax of the tangent to the parabola (thin straight lines in Fig. 2). As a result, the standard total temperature error in the operating temperature range "max..." min should be determined by expression (2):

    "Рн = (Р2 - Р1) = 1 Umax _ ("max - "min") (3)

    Obviously, this value far exceeds the actual total temperature error (see Fig. 2)

    "Rf = (Rn - Rmin). (4)

    It follows that with a nonlinear temperature dependence of the sensor output signal, it is meaningless to use the linear temperature coefficient y to normalize the additional temperature measurement error, since within the operating temperature range it changes in magnitude and sign (including passing through zero), and existing rules in the operating manual it is necessary to indicate the maximum (in absolute value) value of Y.

    It is for this reason that in MIDA-13P pressure sensors, as a measure of additional temperature error, the temperature error zone is normalized in the operating temperature range "Rf", which is indicated in the sensor passport. Statistical data on the size of the temperature error zone of MIDA-13P sensors are given in the article. It is necessary to say that Gosstandart fully agrees with this approach and all regulatory documents of MIDA sensors are recognized by the State Register of the Russian Federation.

    Rice. 2. Determination of the zone of temperature error in pressure measurement for a sensor with a nonlinear temperature dependence of the output signal:

    "Рф - actual zone of temperature error; "Рн - standard zone of temperature error when normalizing the temperature error by a linear coefficient of temperature dependence

    ZepBOGB & Sysfems No. 9.2004

    Rice. 3. Typical temperature dependence of the additional temperature error in pressure measurement with a MIDA-13P sensor, temperature compensated in a 120-degree temperature range (-40...+80 °C)

    "Normal" temperature "n = (20 ± 5) °C. With thermal compensation in another temperature range of the same width (for example, 200...320 °C), the temperature dependence of the error has a similar form (but in this case for the given example “normal” temperature should be Tn = (260 ± 5) °C)

    Measurement errors in the temperature error zone (along with the linear temperature coefficient) are also allowed by some foreign standards.

    A few more points need to be made. Firstly, in sensors with a temperature dependence of the output signal close to parabolic (namely, this is what it is in MIDA pressure sensors), the temperature error zone is minimal when the “normal” temperature “n”, at which the sensor is calibrated and its main error is determined, is in the middle of the operating temperature range (in which temperature compensation of the output signal is carried out).In MIDA-13P sensors this is performed automatically (operating temperature range from -40 to +80 °C, normalization at 20 + 5 °C - see Fig. 3 In high-temperature MIDA-12P sensors, in which the temperature of the measured medium can reach 350 °C, the situation is somewhat more complicated and will be discussed in more detail below.

    Secondly, if in the case of a linear temperature dependence, when the operating temperature range is reduced, the total temperature error decreases linearly, then with a parabolic dependence this decrease is quadratic - for example, with a symmetrical reduction in the operating temperature range by half (for example, from -40...+80 ° From to -10...+50 °C) the temperature error zone is reduced by four. This makes it possible to create high-precision pressure sensors operating in a limited temperature range without the use of complex electronics. Thus, in the range of 0...40 °C, the typical temperature error zone of MIDA-13P pressure sensors with a resistive temperature compensation circuit does not exceed 0.2% (see Fig. 3).

    Thirdly, if the “normal” temperature at which the main sensor error is determined (usually room temperature) is not in the center of the temperature compensation range, then ignoring the nonlinearity of the temperature dependence of the error

  • MID PRESSURE SENSORS FOR TRADE ENERGY ACCOUNTING SYSTEMS

    STUCHEBNIKOV VLADIMIR MIKHAILOVICH - 2009

  • Construction of an observing device in the class of one-parameter structurally stable mappings

    DAUTBAYEVA A.O., SKAKOVA A.ZH. - 2010

  • When choosing pressure sensors, any consumer sets the goal of measuring pressure with the accuracy stated in the technical documentation. This is one of the sensor selection criteria. In the passport for the sensor, GOST standards require that acceptable values ​​be indicated basic error measurements (+ - from true pressure). These values ​​according to GOST 22520 are selected from the range 0.075; 0.1; 0.15; 0.2; 0.25; 0.4; 0.5%; etc. depending on the technical capabilities of the product. The main error indicator is normalized for normal (i.e. ideal) conditions measurements. Normal conditions are determined according to GOST 12997. These conditions are also specified in the measuring instrument verification procedure. For example, according to MI1997, to determine the main error you need to set following conditions env. Wednesday:
    - temperature 23+-2оС,
    - humidity from 30 to 80%,
    - atm. pressure 84-106.7 kPa,
    - power supply 36+-0.72V,
    - absence of external magnetic fields, etc.
    As you can see, the operating conditions for the sensor when determining the main error are almost ideal. Therefore, each calibration laboratory must have the ability to regulate them. For example, to regulate the temperature in a room, microclimate devices (heater, air conditioner, etc.) are used. But what readings from the sensor we will get in real operating conditions at the facility, for example at +80°C or -30°C, is a question. The answer to this question is given by the indicator additional error, which is also standardized in TU and GOST.
    Additional error- Deviation of the conversion function caused by one influencing quantity (temperature, pressure, vibration, radio interference, supply voltage, etc.). Calculated as difference(ignoring the sign) between the error value in workers(actual) measurement conditions, and the error value under normal conditions.
    Of course, all operating conditions factors influence the output signal. But for pressure sensors (transmitters) the most significant effect is the deviation of the ambient air temperature. In GOST 22520, the additional error is normalized for every 10C deviation from normal conditions(i.e. from 23°C). Tolerances according to GOST look like this:

    If the sensor meets these tolerances during temperature testing, then it “complies with GOST 22520,” which in most cases is written in the documentation for the sensor.
    Let's analyze the accuracy of the sensor, which complies with GOST 22520, when exposed to temperature. For example, a sensor with a basic error of 0.5% and an operating temperature range of -30..+80°C at 30°C can err by 0.5+0.45=0.95%, at 40°C (deviation of 2 deci.°C) 1.4% accordingly, and finally at 80°C we get an accuracy of 3.2% - this is the sum of the main and additional errors. Let me remind you that we are dealing with a 0.5% sensor, and when operating at 80°C we get an accuracy of 3.2% (approx. 6 times worse), and such a sensor meets the requirements of GOST 22520.
    The results do not look very nice and will certainly not please the buyer of a sensor with a stated accuracy of 0.5%. Therefore, most manufacturers do thermal compensation of the output signal and the requirements for additional sensors are tightened in the specifications for a specific sensor. errors due to temperature. For example, for SENSOR-M sensors, in the technical specifications we set a requirement of less than 0.1% per 10°C.
    Purpose of temperature compensation– reduce additional error from temperature to zero. Nature additional We will consider temperature errors and methods of temperature compensation of sensors in detail in the next article. In this article I would like to summarize.
    Need to take into account main error and additional depending on the required measurement accuracy within operating temperatures sensor Additional error each sensor can be found in the passport, operating manual or technical specifications for the product. If the indicator is additional errors are not specified in those. Documentation for the sensor, then it simply meets the GOST requirements that we analyzed above.
    One should also distinguish temperature compensation range And Operating temperature range. In the temperature compensation range, additional the error is minimal; when you go beyond the temperature compensation range, the requirements apply again