An effective remedy Industrial ventilation ensures proper cleanliness and acceptable parameters of the air microclimate in the working area.

Ventilation is an organized and regulated air exchange that ensures the removal of polluted air from a room and the supply of fresh air in its place.

By way of air movement There are natural and mechanical ventilation systems.

A ventilation system in which the movement of air masses is carried out due to the resulting pressure difference between the outside and inside the building is called natural ventilation.

When the wind acts on the surfaces of the building on the leeward side, excess pressure is formed, on the leeward side - a vacuum. The distribution of pressures on the surface of buildings and their magnitude depend on the direction and strength of the wind, as well as on the relative position of the buildings.

Unorganized natural ventilation - infiltration , or natural ventilation - carried out by changing the air in the premises through leaks in fences and elements building structures due to the difference in pressure outside and inside the room. Infiltration can be significant for residential buildings and reach 0.5 - 0.75 room volume per hour, and for industrial enterprises up to 1 - 1.5.

For constant air exchange, required by the conditions of maintaining the purity of the air in the room, it is necessary organized ventilation . Organized natural ventilation can be:

Exhaust without organized air flow (duct);

Supply and exhaust with an organized air supply (channel and channelless aeration).

Channel natural exhaust ventilation without an organized air supply is widely used in residential and administrative buildings

Aeration is called organized natural general ventilation premises as a result of the intake and removal of air through the opening transoms of windows and lanterns.

As a method of ventilation, aeration has found wide application in industrial buildings, characterized by technological processes with large heat releases. Entrance of outside air into cold period years are organized so that cold air didn't get into work area. For this outside air served into the room through openings located at least 4.5 m from the floor. In the warm season, the influx of outside air is oriented through the lower tier of window openings.

When calculating aeration, the requirements of SNiP 2.04.05-91 are used.

The main advantage of aeration is the ability to carry out large air exchanges without the expenditure of mechanical energy.

To the disadvantages of aeration It should be noted that during the warm period of the year, the efficiency of aeration can significantly decrease due to an increase in the temperature of the outside air, and, in addition, the air entering the room is not cleaned or cooled.


Ventilation, by which air is supplied to or removed from industrial premises through ventilation duct systems using special mechanical stimulators for this, is called mechanical ventilation. .

Mechanical ventilation has a number of advantages:

Large radius of action due to the significant pressure generated by the fan;

The ability to change or maintain the required air exchange regardless of the outdoor temperature and wind speed;

Subject the air introduced into the room to preliminary purification, drying or humidification, heating or cooling;

Organize optimal air distribution with air supply directly to workplaces;

Capture harmful emissions directly at the places of their formation and prevent their spread throughout the entire volume of the room, as well as the ability to purify polluted air before releasing it into the atmosphere.

Disadvantages of mechanical ventilation The significant cost of the structure and its operation and the need for noise control measures should be taken into account.

Mechanical ventilation systems are divided into:

1. General exchange.

2. Local.

3. Mixed.

4. Emergency.

5. Air conditioning systems.

General ventilation designed to assimilate excess heat, moisture and harmful substances throughout the entire working area of ​​the premises. It is used if harmful emissions enter directly into the air of the room; workplaces are not fixed, but are located throughout the room.

Based on the method of air supply and removal, four general ventilation schemes are distinguished:

Supply;

Exhaust;

Supply and exhaust;

Recirculation systems.

According to the supply system air is supplied to the room after it has been prepared in the supply chamber. This creates excess pressure in the room, due to which the air escapes outside through windows, doors or into other rooms. The supply system is used to ventilate rooms into which it is undesirable for polluted air from neighboring rooms or cold air from outside to enter.

Exhaust system designed to remove air from the room. At the same time, a reduced pressure is created in it and the air from neighboring rooms or outside air enters this room.

Supply and exhaust ventilation - the most common system in which air is supplied into the room by a supply system and removed by an exhaust system.

In some cases, to reduce operating costs for air heating, ventilation systems with partial recirculation are used. In them, the air sucked from the room by the exhaust system is mixed with the air coming from outside. The amount of fresh and secondary air is controlled by valves . The ventilation system with recirculation is allowed to be used only for those rooms in which there are no emissions of harmful substances.

In a normal microclimate and the absence of harmful emissions, the amount of air during general ventilation is taken depending on the volume of the room per worker.

By using local ventilation the necessary meteorological parameters are created at individual workplaces. Local exhaust ventilation is the most widely used. The main method of combating harmful secretions is to install and organize suction from shelters.

Local suction designs can be completely closed, semi-open or open.

Closed suctions are the most effective. These include casings and chambers that hermetically or tightly cover technological equipment .

If it is impossible to arrange such shelters, then use suction with partial shelter or open: exhaust hoods, suction panels, fume hoods, side suction, etc.

One of the most simple types local suction - exhaust hood. It serves to trap harmful substances that have a lower density than the surrounding air.

The required air exchange in local exhaust ventilation devices is calculated based on the localization conditions of impurities released from the source of formation.

Mixed ventilation system is a combination of elements of local and general ventilation. local system removes harmful substances from casings and covers of machines. However, some harmful substances penetrate into the room through leaks in shelters. This part is removed by general ventilation.

Emergency ventilation is provided in those production premises in which a sudden entry into the air is possible large quantity harmful or explosive substances.

To create optimal meteorological conditions in industrial premises, the most advanced type of industrial ventilation is used - air conditioning.

Air conditioning is called its automatic processing in order to maintain predetermined meteorological conditions in production premises, regardless of changes in external conditions and indoor conditions.

When air conditioning, the air temperature, its relative humidity and the rate of supply to the room are automatically adjusted depending on the time of year, external meteorological conditions and the nature of the technological process in the room.

Such strictly defined air parameters are created in special installations called air conditioners. In some cases, in addition to providing sanitary norms The air microclimate in air conditioners is subject to special treatment: ionization, deodorization, ozonation, etc.

Air conditioners can be:

1. Local (for servicing individual premises).

2. Central (for servicing several separate premises).

Air conditioning plays an essential role not only from the point of view of life safety, but also in many technological processes in which fluctuations in temperature and air humidity are not allowed (especially in radio electronics). Therefore, air conditioning installations in last years are increasingly used in industrial enterprises.

MINISTRY OF EDUCATION AND SCIENCE OF UKRAINE

KRASNODON MINING TECHNIQUE

Abstract on the subject “SAFETY

TECHNOLOGICAL

PROCESSES AND PRODUCTIONS»

on the topic: “INDUSTRIAL VENTILATION »

Student group 1EP-06

Uryupova Oleg

Checked by: Drokina T.M.

Krasnodon 2010


Ventilation is a complex of interconnected devices and processes for creating the required air exchange in industrial premises. The main purpose of ventilation is to remove contaminated or overheated air from the working area and supply clean air, as a result of which the necessary conditions are created in the working area. favorable conditions air environment. One of the main tasks that arises when installing ventilation is determining the air exchange, i.e. the amount ventilation air necessary to ensure an optimal sanitary and hygienic level of the indoor air environment.

Depending on the method of air movement in industrial premises, ventilation is divided into natural and artificial (mechanical).

The use of ventilation must be justified by calculations that take into account temperature, air humidity, release of harmful substances, and excess heat generation. If there are no harmful emissions in the room, then ventilation should provide an air exchange of at least 30 m3 / h for each worker (for rooms with a volume of up to 20 m3 per worker). When harmful substances are released into the air of the working area, the necessary air exchange is determined based on the conditions of their dilution to the maximum permissible concentration, and in the presence of thermal excess - from the conditions of maintaining permissible temperature in the work area.

Natural ventilation production premises is carried out due to the temperature difference in the room from the outside air (thermal pressure) or the action of wind (wind pressure). Natural ventilation can be organized or unorganized.

With unorganized natural ventilation air exchange is carried out by displacing internal thermal air with external cold air through windows, vents, transoms and doors. Organized natural ventilation, or aeration, provides air exchange in pre-calculated volumes and adjustable in accordance with meteorological conditions. Channelless aeration is carried out using openings in the walls and ceiling and is recommended in large rooms with significant excess heat. To obtain the calculated air exchange, ventilation openings in the walls, as well as in the roof of the building (aeration skylights) are equipped with transoms that open and close from the floor of the room. By manipulating the transoms, you can regulate the air exchange when changing outside temperature air or wind speed (Fig. 4.1). The area of ​​ventilation openings and skylights is calculated depending on the required air exchange.

Rice. 4.1. Scheme of natural ventilation of the building: A- with no wind; b- in the wind; 1 - exhaust and supply openings; 2 - heat generating unit

In small industrial premises, as well as in premises located in multi-storey industrial buildings, channel aeration is used, in which contaminated air is removed through ventilation ducts in the walls. To enhance the exhaust, deflectors are installed at the exit from the ducts on the roof of the building - devices that create draft when the wind blows on them. In this case, the wind flow, hitting the deflector and flowing around it, creates a vacuum around most of its perimeter, which ensures air suction from the channel. The most widely used deflectors are the TsAGI type (Fig. 4.2), which are a cylindrical shell mounted above the exhaust pipe. To improve air suction by wind pressure, the pipe ends in a smooth expansion - a diffuser. A cap is provided to prevent rain from entering the deflector.

Rice. 4.2. TsAGI type deflector diagram: 1 - diffuser; 2 - cone; 3 - legs holding the cap and shell; 4 - shell; 5 - cap

Calculation of the deflector comes down to determining the diameter of its pipe. Approximate diameter of the pipe d TsAGI type deflector can be calculated using the formula:

Where L- ventilation air volume, m3/h; - air speed in the pipe, m/s.

The air speed (m/s) in the pipe, taking into account only the pressure created by the action of the wind, is found using the formula

where - wind speed, m/s; - the sum of the local resistance coefficients of the exhaust air duct in its absence e = 0.5 (at the entrance to the branch pipe); l- length of the branch pipe or exhaust air duct, m.

Taking into account the pressure created by the wind and thermal pressure, the air speed in the nozzle is calculated using the formula

where is thermal pressure Pa; here is the height of the deflector, m; - density, respectively, of outdoor air and indoor air, kg/m3.

The speed of air movement in the pipe is approximately 0.2...0.4 wind speed, i.e. If the deflector is installed without exhaust pipe directly in the ceiling, then the air speed is slightly higher.

Aeration is used for ventilation of large industrial premises. Natural air exchange is carried out through windows, skylights using heat and wind pressure (Fig. 4.3). Thermal pressure, as a result of which air enters and leaves the room, is formed due to the temperature difference between the external and internal air and is regulated by varying degrees of opening of the transoms and lanterns. The difference between these pressures at the same level is called internal excess pressure. It can be both positive and negative.

Rice. 4.3. Building aeration scheme


At negative value(excess of external pressure over internal) air enters the room, and when positive value(internal pressure exceeds external pressure) air leaves the room. At = 0 there will be no air movement through the holes in the outer fence. The neutral zone in the room (where = 0) can only exist under the influence of excess heat alone; when there is wind with excess heat, it sharply shifts upward and disappears. The distances of the neutral zone from the middle of the exhaust and supply openings are inversely proportional to the squares of the areas of the openings. At, where are the areas, respectively, of the inlet and outlet openings, m2; -height of the level of equal pressures, respectively, from the inlet to the outlet, m.

Air flow G, which flows through a hole having an area F, calculated by the formula:

Where G- massive second consumption air, t/s; m is the flow rate factor depending on the outflow conditions; r - air density in the initial state, kg/m3; - pressure difference inside and outside the room in a given hole, Pa.

The approximate amount of air leaving the room through 1 m2 of opening area, taking into account only thermal pressure and provided that the areas of the holes in the walls and lanterns are equal and the flow coefficient m = 0.6, can be determined using a simplified formula:


Where L- amount of air, m3/h; N- distance between the centers of the lower and upper holes, m; - temperature difference: average (in height) indoors and outdoors, ° С.

Aeration using wind pressure is based on the fact that excess pressure occurs on the windward surfaces of the building, and rarefaction occurs on the windward sides. The wind pressure on the surface of the fence is found by the formula:

Where k- aerodynamic coefficient, showing what proportion of the dynamic wind pressure is converted into pressure in a given section of the fence or roof. This coefficient can be taken on average equal to + 0.6 for the windward side, and -0.3 for the leeward side.

Natural ventilation is cheap and easy to operate. Its main disadvantage is that the supply air is introduced into the room without preliminary cleaning and heating, and the exhaust air is not cleaned and pollutes the atmosphere. Natural ventilation is applicable where there are no large emissions of harmful substances into the work area.

Artificial (mechanical) ventilation eliminates the disadvantages of natural ventilation. With mechanical ventilation, air exchange is carried out due to the air pressure created by fans (axial and centrifugal); air in winter time It is heated, cooled in the summer and, in addition, cleaned of contaminants (dust and harmful vapors and gases). Mechanical ventilation can be supply, exhaust, supply and exhaust, and according to the place of action - general and local.

At supply ventilation system(Fig. 4.4, A) air is taken from the outside using a fan through a heater, where the air is heated and, if necessary, humidified, and then supplied to the room. The amount of air supplied is controlled by valves or dampers installed in the branches. Polluted air exits through doors, windows, lanterns and crevices uncleaned.

At exhaust ventilation system(Fig. 4.4, b) polluted and overheated air is removed from the room through a network of air ducts using a fan. Polluted air is cleaned before being released into the atmosphere. Clean air is sucked in through windows, doors, leaky structures.

Supply and exhaust system ventilation(Fig. 4.4, V) consists of two separate systems - supply and exhaust, which simultaneously supply the room fresh air and remove contaminated material from it. Supply ventilation systems also replace air removed by local suction and spent on technological needs: fire processes, compressor units, pneumatic transport, etc.

To determine the required air exchange, it is necessary to have the following initial data: the amount of harmful emissions (heat, moisture, gases and vapors) per 1 hour, the maximum permissible amount (MAC) of harmful substances in 1 m3 of air supplied to the room.

Rice. 4.4. Scheme of supply, exhaust and supply and exhaust mechanical ventilation: A- supply; 6 - exhaust; V- supply and exhaust; 1 - air inlet for intake of clean air; 2 - air ducts; 3 - filter for air purification from dust; 4 - air heaters; 5 - fans; 6 - air distribution devices (nozzles); 7 - exhaust pipes for the discharge of exhaust air into the atmosphere; 8 - devices for purification of the removed air; 9 - air inlets for exhaust air; 10 - valves for regulating the amount of fresh secondary recirculation and exhaust air; 11 - room served supply and exhaust ventilation; 12 - air duct for the recirculation system

For rooms with the release of harmful substances, the required air exchange L, m3 / h, is determined from the condition of the balance of harmful substances entering it and diluting them to acceptable concentrations. Balance conditions are expressed by the formula:

Where G- rate of release of harmful substances from technological installation, mg/h; G etc- the rate of entry of harmful substances with the influx of air into the working area, mg/h; Gud- the rate of removal of harmful substances diluted to permissible concentrations from the work area, mg/h.

Replacing in expression G etc And Gud by the product and, where and are, respectively, the concentration (mg/m3) of harmful substances in the supply and removed air, a and the volume of supply and removed air in m3 per 1 hour, we obtain

To maintain normal pressure in the working area, equality must be satisfied, then


The necessary air exchange, based on the content of water vapor in the air, is determined by the formula:

where is the amount of removed or supply air indoors, m3/h; G P- mass of water vapor released in the room, g/h; - moisture content of removed air, g/kg, dry air; - moisture content of supply air, g/kg, dry air; r - density of supply air, kg/m3.

where are the masses (g) of water vapor and dry air, respectively. It must be borne in mind that the values ​​and are taken from the tables physical characteristics air depending on the value of the standardized relative humidity exhaust air.

To determine the volume of ventilation air based on excess heat, it is necessary to know the amount of heat entering the room from various sources(heat arrival), and the amount of heat spent to compensate for losses through the building’s enclosures and other purposes, the difference expresses the amount of heat that goes to heat the air in the room and which must be taken into account when calculating air exchange.

The air exchange required to remove excess heat is calculated using the formula:

where is the excess amount of heat, J/s, is the temperature of the removed air, ° K; - supply air temperature, ° K; WITH- specific heat capacity of air, J/(kg×K); r - air density at 293° K, kg/m3.

Local ventilation Is there an exhaust or supply? Exhaust ventilation are suitable when pollution can be captured directly at the point of its origin. For this purpose, fume hoods, umbrellas, curtains, side suction at bathtubs, casings, suction at machine tools, etc. are used. Supply ventilation includes air showers, curtains, and oases.

Fume hoods work with natural or mechanical exhaust. To remove excess heat from a cabinet or harmful impurities naturally requires the presence of a lifting force, which occurs when the temperature of the air in the cabinet exceeds the temperature of the air in the room. The exhaust air must have sufficient energy to overcome aerodynamic resistance on the way from the entrance to the cabinet to the point of release into the atmosphere.

Volume flow rate of air removed from fume hood with natural exhaust (Fig. 4.5), (m3 / h)

Where h- height of the open cabinet opening, m; Q- amount of heat generated in the cabinet, kcal/h; F- area of ​​the open (working) opening of the cabinet, m2.


Rice. 4.5. Scheme of a fume hood with natural exhaust: 1 - level zero pressure; 2 - diagram of pressure distribution in the working hole; T1- room air temperature; T 2 - gas temperature inside the cabinet

Required exhaust pipe height (m)

where is the sum of all resistances of a straight pipe along the path of air movement; d- straight pipe diameter, m (preset).

With mechanical extraction

Where v- average suction speed in sections of an open opening, m/s.

Onboard suctions arranged near production baths for removal of harmful vapors and gases that are released from bath solutions. For bath widths up to 0.7 m, single-sided suction units are installed on one of its longitudinal sides. When the bath width is more than 0.7 m (up to 1 m), double-sided suction is used (Fig. 4.6).

The volumetric flow rate of air sucked from hot baths by single- and double-sided suction units is found using the formula:

Where L- volumetric air flow, m3/h, k 3 - safety factor equal to 1.5...1.75, for baths with special harmful solutions 1,75...2; k T- coefficient for taking into account air leaks from the ends of the bath, depending on the ratio of the width of the bath IN to its length l; for single-sided simple suction; for double-sided - ; WITH- dimensionless characteristic equal to 0.35 for single-sided suction and 0.5 for double-sided suction; j is the angle between the suction boundaries (Fig. 4.7); (in calculations it has a value of 3.14); TV And Tp- absolute temperatures, respectively, in the bath and air in the room, °K; g=9.81 m/s2.

Exhaust hoods used when the released harmful vapors and gases are lighter than the surrounding air and its mobility in the room is insignificant. Umbrellas can be either with natural or mechanical exhaust.

Rice. 4.6. Double-sided bath suction

With natural exhaust the initial volumetric air flow rate in the thermal jet rising above the source is determined by the formula:


Where Q- amount of convective heat, W; F- horizontal projection area of ​​the heat source surface, m2; N- distance from the heat source to the edge of the umbrella, m.

With mechanical extraction the aerodynamic characteristic of the umbrella includes the speed along the axis of the umbrella, which depends on the angle of its opening; with an increase in the opening angle, the axial speed increases compared to the average. At an opening angle of 90°, the axial speed is l.65 v (v- average speed, m / s), at an opening angle of 60 °, the speed along the axis and along the entire section is equal to v .

In general, the flow rate of air removed by the umbrella is

Where v- average speed of air movement in the intake opening of the umbrella, m/s; when removing heat and moisture, the speed can be taken as 0.15...0.25 m/s; F- design cross-sectional area of ​​the umbrella, m2.

The receiving hole of the umbrella is located above the heat source; it must correspond to the configuration of the umbrella, and the dimensions are taken somewhat larger than the dimensions of the heat source in the plan. Umbrellas are installed at a height of 1.7...1.9 m above the floor.

To remove dust from various machines, dust collection devices are used in the form of protective and dust removal casings, funnels, etc.


Rice. 4.7. The angle between the boundaries of the suction torch at different locations baths: A- near the wall (); b- next to the bathroom without suction (); V- separately (); 1 - bath with suction; 2 - bath without suction.

In calculations, take p = 3.14

Air volume flow L(m3/h) removed from grinding, grinding and roughening machines is calculated depending on the diameter of the wheel d To p(mm), namely:

at< 250 мм L = 2,

at 250...600 mm L = 1,8 ;

at > 600 mm L = 1,6.

The air flow rate (m3/h) removed by the funnel is determined by the formula:

Where VH- initial speed of the exhaust torch (m/s), equal to speed transportation of dust in the air duct, accepted for heavy emery dust 14...16 m/s and for light mineral dust 10...12 m/s; l- working length of the exhaust torch, m; k- coefficient depending on the shape and aspect ratio of the funnel: for a round hole k= 7.7 for rectangular with aspect ratio from 1:1 to 1:3 k = 9,1; V k- the required final speed of the exhaust torch at the circle, taken equal to 2 m/s.


LITERATURE

1. Life safety/Ed. Rusaka O.N.- S.-Pb.: LTA, 1996.

2. Belov S.V. Life safety is the science of survival in the technosphere. NMS materials on the discipline “Life Safety”. - M.: MSTU, 1996.

3. All-Russian monitoring of the social and labor sphere 1995. Statistical collection. - Ministry of Labor of the Russian Federation, M.: 1996.

4. Hygiene environment./Ed. Sidorenko G.I..- M.: Medicine, 1985.

5. Occupational hygiene when exposed to electromagnetic fields./Ed. Kovshilo V.E.- M.: Medicine, 1983.

6. Zolotnitsky N.D., Pcheliniev V.A.. Occupational safety in construction. - M.: Higher School, 1978.

7. Kukin P.P., Lapin V.L., Popov V.M., Marchevsky L.E., Serdyuk N.I. Fundamentals of radiation safety in human life.- Kursk, KSTU, 1995.

8. Lapin V.L., Popov V.M., Ryzhkov F.N., Tomakov V.I. Safe human interaction with technical systems. - Kursk, KSTU, 1995.

9. Lapin V.L., Serdyuk N.I. Occupational safety in foundry production. M.: Mashinostroenie, 1989.

10. Lapin V.L., Serdyuk N.I. Occupational safety management at an enterprise. - M.: MIGZH MATI, 1986.

11. Levochkin N.N. Engineering calculations on labor protection. Publishing house of Krasnoyarsk University, -1986.

12. Occupational safety in mechanical engineering./Ed. Yudina B.Ya., Belova S.V. M.: Mechanical Engineering, 1983.

13. Labor protection. Information and analytical bulletin. Vol. 5.- M.: Ministry of Labor of the Russian Federation, 1996.

14. Putin V.A., Sidorov A.I., Khashkovsky A.V. Occupational safety, part 1. - Chelyabinsk, ChTU, 1983.

15. Rakhmanov B.N., Chistov E.D. Safety during operation of laser installations. - M.: Mashinostroenie, 1981.

16. Saborno R.V., Seledtsov V.F., Pechkovsky V.I. Electrical safety at work. Methodological instructions. - Kyiv: Vishcha School, 1978.

17. Reference book on labor protection/Ed. Rusaka O.N., Shaidorova A.A.- Chisinau, Publishing House “Cartea Moldovenasca”, 1978.

18. Belov S.V., Kozyakov A.F., Partolin O.F. and others. Means of protection in mechanical engineering. Calculation and design. Directory/Ed. Belova S.V.-M.: Mechanical Engineering, 1989.

19. Titova G.N. Toxicity of chemicals. - L.: LTI, 1983.

20. Tolokontsev N.A. Fundamentals of general industrial toxicology. - M.: Medicine, 1978.

21. Yurtov E.V., Leikin Yu.L. Chemical toxicology. - M.: MHTI, 1989.

One of the main means of collective protection of workers from negative impact harmful factors of the air environment (dust, gas, increased heat and humidity) is ventilation.

Ventilation is a complex of interrelated devices and processes designed to create an organized air exchange necessary for removal from production premises contaminated or superheated (cooled) air with the supply of clean and cooled (heated) air instead, which allows creating favorable air conditions in the working area.

The amount of air required to ensure the required parameters of the air environment in the working area is determined depending on the amount of harmful factors released in such a way as to ensure maximum allowable concentrations and levels.

Under ventilation system understand a set of ventilation units with different purposes that can serve separate room or building. The classification of the main types of ventilation is presented in Fig. P1.9.

Depending on the method of air movement in work areas, ventilation is divided into artificial (mechanical), natural and combined.

With natural ventilation, air exchange is carried out in two ways:

Unorganized (ventilation and air infiltration through window, door openings, cracks and microcracks);

Organized (due to aeration and with the help of deflectors).

Natural unorganized air exchange in a room is caused by the action of two factors: thermal air movement and wind pressure. Thermal movement is created by the difference in the weight of air columns outside and inside the room. Thus, there is a pressure difference, which causes air exchange. Wind pressure is caused by the action of the wind, due to which excess pressure occurs on the windward surfaces of the building, and rarefaction occurs on the leeward sides. The resulting pressure difference causes air to enter from the windward side of the building and exit through openings on the opposite windward side. In some cases, unorganized air exchange is not enough to remove harmful emissions from the room, so a special device is used - a deflector (see Fig. A1.10). The deflector is the end of a pipe designed to remove air from the upper zone of the room. The wind flow, hitting the deflector and flowing around it, creates a vacuum that ensures air suction from the room through the deflector channel. Aeration is organized natural air exchange, carried out in pre-calculated volumes and regulated in accordance with external meteorological conditions.

The advantage of natural ventilation is the simplicity of the devices and minimal operating costs. The disadvantage is the influence of natural factors (wind, ambient temperature) on its effectiveness, as well as the fact that air is supplied and removed from the room that has not undergone special treatment (not cleared of dust and other harmful impurities, not cooled or not heated). Therefore, natural ventilation is used mainly where there are no significant emissions of harmful factors.

At artificial ventilation air movement is activated mechanical devices. The classification of mechanical ventilation is shown in fig. P1.11.

According to the nature of the room coverage ventilation systems can be general exchange, local (local) and combined.

With general ventilation, air change occurs throughout the entire volume of the room. This type of ventilation can be carried out either naturally (aeration) or mechanically.

The purpose of local ventilation is to localize harmful emissions in places of formation and remove them from the room. It can be carried out mechanically with the help of fans and naturally with the help of deflectors.

At combined system simultaneously with the general air exchange, the individual most intense sources of emissions are also localized.

Local ventilation can be supply or exhaust.

The supply air is provided for the purpose of supplying clean air to the work area to create a microclimate in individual places (air showers, curtains and oases). An air shower is a stream of air directed at a person. Air curtain helps prevent penetration into manufacture building through the cold air gate in winter. Air oases improve weather conditions for limited area room, which is separated for this purpose on all sides light partitions and is flooded with air colder and cleaner than the air in the room.

Exhaust ventilation is installed in places where harmful emissions are formed in the form of cabinets, umbrellas, suction from various equipment, vacuum cleaners, dust collectors, ejection units, individual suction units, and so on.

General exchange mechanical ventilation It can be supply, exhaust, supply and exhaust, and can also be carried out using air conditioners. With supply general ventilation Fresh air is taken from places outside the building and distributed throughout the volume of the room. Polluted air is displaced by fresh air through doors, windows, lanterns and cracks in building structures. Forced ventilation used in the presence of heat and the absence of gas emissions.

Exhaust general ventilation allows you to remove contaminated and overheated air from the entire volume of the room. To replace the removed air, clean air is sucked in from the outside through doors, windows, and cracks in building structures.

Supply and exhaust general exchange mechanical ventilation consists of two separate units. Clean air is supplied through one, polluted air is removed through the other.

Air conditioning is ventilation unit, which, with the help of automatic control devices, maintains the specified parameters of the air environment in the room.

There are two types of air conditioners: full air conditioning units, which ensure the constancy of temperature, relative humidity, speed and air purity, as well as partial air conditioning units, which ensure the constancy of only a part of these parameters or one parameter, most often temperature.

Depending on the method of refrigeration, air conditioners are divided into autonomous and non-autonomous. In stand-alone air conditioners, the cold is produced by its own built-in refrigeration units. Non-autonomous air conditioners are supplied with coolants centrally.

According to the method of preparing and distributing air, air conditioners are divided into central and local. The design of central air conditioners provides for the preparation of air outside the serviced premises and its distribution through the air duct system. In local air conditioners, air is prepared directly in the premises served; the air is distributed concentratedly, without air ducts.

Life safety Viktor Sergeevich Alekseev

25. Industrial ventilation and conditioning

Ventilation– indoor air exchange carried out using various systems and devices.

As a person stays indoors, the air quality in the room deteriorates. Along with exhaled carbon dioxide Other metabolic products, dust, and harmful industrial substances also accumulate in the air. In addition, the temperature and humidity rise. Therefore, there is a need for room ventilation, which ensures air exchange– removing polluted air and replacing it with clean air.

Air exchange can be carried out naturally - through vents and transoms.

The best method of air exchange is artificial ventilation, in which fresh air is supplied and polluted air is removed mechanically - using fans and other devices.

Most perfect form artificial ventilation is air conditioning- creation and maintenance of indoors and transport using technical means the most favorable (comfortable) conditions for people, to ensure technological processes, operation of equipment and devices, preservation of cultural and artistic values.

Air conditioning is achieved by creating optimal parameters of the air environment, its temperature, relative humidity, gas composition, air speed and air pressure.

Air conditioning units are equipped with devices for cleaning air from dust, for heating, cooling, drying and humidifying it, as well as for automatic regulation, control and management. In some cases, using air conditioning systems, it is also possible to carry out odorization (saturation of air with aromatic substances), deodorization (neutralization unpleasant odors), regulation of ionic composition (ionization), removal of excess carbon dioxide, oxygen enrichment and bacteriological air purification (in medical institutions where there are patients with airborne infection).

Distinguish central systems air conditioning systems, which usually serve the entire building, and local ones, which serve one room.

Air conditioning is carried out using air conditioners various types, the design and arrangement of which depends on their purpose. Various devices are used for air conditioning: fans, humidifiers, air ionizers. In the premises, the optimal air temperature in winter is from + 19 to +21 C, in summer – from +22 to +25 C with a relative air humidity of 60 to 40% and an air speed of no more than 30 cm/s.

From the book Anesthesiology and Resuscitation author

55. Artificial ventilation of the lungs Artificial ventilation of the lungs (ALV) provides gas exchange between the surrounding air (or a certain mixture of gases) and the alveoli of the lungs;

From the book Anesthesiology and Resuscitation: Lecture Notes author Marina Aleksandrovna Kolesnikova

Lecture No. 15

From the book First Aid Manual by Nikolay Berg

ARTIFICIAL VENTILATION OF THE LUNGS If during the initial assessment of the victim it is established that he is unconscious and not breathing, it is necessary to start artificial ventilation of the lungs. A healthy person inhales about 500 ml of air during quiet breathing. This is true

From the book Energy at Home. Creating a harmonious reality author Vladimir Kivrin

From the book Normal Physiology author Nikolay Alexandrovich Agadzhanyan

Ventilation of the lungs and pulmonary volumes The amount of pulmonary ventilation is determined by the depth of breathing and the frequency of respiratory movements. A quantitative characteristic of pulmonary ventilation is the minute volume of breathing (MVR) - the volume of air passing through the lungs in 1 minute.