home · Appliances · Where is I lying? Input distribution device (IDU). Types and applications. Why are lies made?

Where is I lying? Input distribution device (IDU). Types and applications. Why are lies made?

To connect and correct operation objects in the electrical field, various devices and instruments are used that have a specific function. An ASU is designed to connect a line to several objects simultaneously (with a local network). The decoding of this abbreviation in electrical engineering sounds like “input distribution device”. It is designed to perform various functions and is additionally equipped with metering devices.

Scope of operation

The main purpose of the equipment is to receive and then further distribute the input electricity. Input and distribution devices are designed for operation at any type of facility, including industrial, household, and construction. Devices must comply with the parameters of the electrical network: voltage and power consumption. The process of assembling and completing the ASU is strictly controlled; a number of strict requirements are imposed on them; all actions are performed only manually.

Manufacturers offer both universal models designed for networks with standard parameters, as well as special ones. The location of distribution devices in buildings is always indicated in the power supply project. It also indicates the characteristics of all equipment included in the kit. After installation and assembly, authorized persons seal the meters in order to block unauthorized access to particularly important devices.

In private households, the installation of input devices is justified only if it is necessary to distribute the total load over several objects, For example:

  • summer cuisine;
  • outbuildings;
  • bath;
  • garage.

In such cases, the main block is installed, and then a separate switchgear is installed for each of the buildings.

Equipment configuration

All models are equipped in different ways, depending on the requirements placed on them during operation or the individual wishes of the future owner. The standard equipment includes protective automation and measuring equipment, In addition, the components of the ASU are:

Depending on the field of operation, switchgears are equipped with quartz fuses and transformers, as well as voltage limiters. Each project represents a set of individual requirements and parameters for organizing the power supply of a facility.

Main functions

In addition to the main function - receiving and distributing incoming electricity, ASUs perform a number of other functions. Thanks to them, at the installation site it is possible to combine all devices into a single system and carry out comfortable and safe control from one point. Installation of distribution devices allows:

The lowest voltage device is the VRSH. Explanation of the abbreviation - introductory switchboard. This is the main equipment included, which monitors and manages electrical networks, and also provides protection against interruptions. The equipment is presented in the form of several functional blocks, which are located in panels with mechanical or electrical connections. It provides input and distribution of input energy to group users.

Classification and types

The device classification system is based on rated current indicators (250A, 400A, 630A), as well as on the additional number of devices included. Manufacturers offer several types of ASU:

  • equipped with automatic switches;
  • with lighting devices;
  • with compartments for connecting measurement and control devices.

In the private sector and in apartment buildings Models that provide the possibility of separately connecting an RCD (device) are relevant. protective shutdown). This function increases the safety of using electrical networks and electrical appliances in particular. If an emergency occurs, a short circuit occurs, your hands touch a bare wire, or there is a voltage drop, the automation will turn off the power.

Equipment equipped with light sensors is intended for outdoor installation. As a rule, these are installed in in public places, in the entrances, on staircase landings, vestibules common use. Models equipped with automatic on/off switches for equipment are the most compact in size and are the most popular in the household sector.

The technical design of the devices determines their classification into floor-mounted and suspended, as well as by location - outdoor or indoor.

Installation features

The functioning of the ASU depends not only on technical parameters, but also proper installation at the site of operation. When purchasing equipment, you must ensure that there is a certificate of compliance with all standards confirming the quality of the product. In addition, an analysis of requirements is carried out: for uninterrupted operation, protective mechanisms and automation are checked, as well as the possibility of installing them at entry and exit points.

Connection of input distribution devices is carried out in strict accordance with the color marking of cables and wires. When purchasing devices, it is important to correctly calculate the required network voltage and current. Installation of equipment is carried out in strict accordance with design documentation.



Typical cabinet layouts VRU-1, VRU-2 were developed back in the USSR for power supply of residential buildings and industrial buildings. They covered the entire range of needs of the then designers, engineers and power engineers. Switchboards VRU-1, VRU-2, VRU-3, etc. with switches and fuses are still found in budget projects (sometimes they are called differently, or).

The ASU shield is metal structure wall-mounted or floor-mounted. Inside there are mounting panels on which the equipment is installed. ASU boards design there are single panel And multi-panel.

Single panel ASU switchboards are equipped with various devices for receiving and distributing electricity from the main source to individual groups of consumers; it also contains electricity meters.

Multi-panel ASU panels contain two or more panels on which additional equipment necessary for a specific electrical installation is installed. Such panels are:

    introductory (contains the equipment of the input and accounting unit);

    input with automatic input of reserve (input panel containing a block with ATS equipment);

    distribution (metering blocks, automatic and non-automatic blocks can be located on this panel automatic control lighting, etc.);

    panel of fire extinguishing devices.

ASU panel with changeover switch

If 2 power cables are suitable for the ASU and there is no need to automatically switch between them, two reversible (changeover) switches are installed at the input, connected in a cross pattern to provide power to certain particularly important consumers in groups. If the circuit is even simpler, you can simply install one reversing switch at the ASU input and switch between inputs to one common load.

Cabinet ASU photo

ASU cabinet for 630 A, KEAZ equipment 100 A ASU cabinet with GSM data transmission on KEAZ equipment ASU panel 250 A, Hyundai components ASU panel 400 A, Hyundai components
Cabinet VRU 630A 2 inputs, switches according to the “cross” pattern. ABB equipment ASU cabinet for 125 A, input components KEAZ, ABB distribution ASU cabinet for 200 A, Hyundai equipment ASU 1250A 2 panels with ATS based on Hyundai circuit breakers with motor drive


The final stage in organizing the electrical transportation network is the installation of distribution and converting devices. They can also be found at intermediate nodes of trunk lines, but this concept of branching energy delivery circuits is most clearly manifested at the stage of direct supply to final objects. Input distribution devices (IDUs) such as transformers, fuse switches, etc. are responsible for this function.

Concept and purpose of ASU

As the name suggests, ASU systems perform the tasks of inputting and distributing electricity at consumption sites. Physically, an ASU is a set of technical means that provide power control, current conversion, its measurement in various parameters and accounting. For a more complete understanding of what an ASU is, it is worth familiarizing yourself with some modifications of devices and their purpose. So, at a basic level it is used next classification:

  • VRU-1. Complete input and distribution equipment, which is used for operation outside switchboard rooms. Such devices can be found on staircases or in basements.
  • VRU-2. Professional sets of control and control equipment designed for use in switchboard rooms. They can be used to ensure the operation of server rooms and technical electrical utility rooms.
  • VRU-3. Small-sized kits that can be part of an electrical panel of a suitable format.

The most commonly used means are VRU-1 and VRU-3. These are devices directly involved in the processes of receiving, accounting and distributing energy in networks at 220/380 V with a frequency of 50 Hz. Some modifications additionally perform protective functions in cases of overloads and short circuits.

Operating principle of the ASU

The work process begins with receiving electricity from the main network. The power cable supplies current to the input automation in accordance with standard values ​​(rated current). Already at this stage, counters and other measuring instruments that measure the parameters of the input current can be switched on. Again, it’s worth recalling what an ASU is in terms of functionality. This is a complex of different devices, sometimes performing tasks of a completely different spectrum. In parallel with the measuring function, a protective function can be performed. Thus, the input switch generally controls the power supply and, when deviations from standard values ​​are detected or emergency situations occur, it turns off the machine. Technically, the switch is implemented in the form of a switch or disconnector - manual or automatic.

Next, a group of arresters comes into operation, ensuring the connection of wires in phases. At this stage, the voltage parameters are necessarily recorded and, if necessary, they are corrected by transformers. Distribution is carried out in groups of wires using circuit breakers with different or similar ratings. The current parameters on each circuit depend on the needs of the consumer to which it leads. The branching task is not determined by the separation of wires according to current characteristics, but by the need to distribute energy in its own directions for each supply point. Distribution automation ensures load uniformity between phases, fixing the demand coefficient of electrical networks, taking into account their maximum load.

Composition of the Verkhovna Rada

Almost all devices of this type are made in the form of a panel enclosed in a metal box. The following devices and functional blocks are placed on this base using pre-installed connectors and modules:

  • Circuit breakers.
  • Meters that record reactive and active energy.
  • Current transformers.
  • Converters.
  • Test devices.
  • Electromagnetic starters.
  • Measuring instruments (voltmeters, ammeters, multimeters, etc.).

Additional equipment depends on the specific set of device functions. They have several panels with control equipment for one-way maintenance. The peculiarity of such equipment is the possibility of independently connecting an auxiliary distribution cabinet with a source uninterruptible power supply(UPS) in case of loss of power to the target object.

Characteristics of the ASU

Most input distribution systems are oriented towards work in three-phase and single-phase networks power point from 100 to 400 A and frequency 50-60 Hz. As for power, then First level represent input and distribution devices from 0.4 kV to 1 kV. They are used to service municipal lighting systems, construction equipment at remote sites, etc. However, to supply large consumers, switchboards with ASU are used, the power of which is at least 10 kV, and sometimes exceeds 25 kV. The choice also takes into account such characteristics as connection time of the backup source (0.2-5 s), degree of protection (from IP00 to IP31 depending on the part of the case) and electrical resistance (from 10 MΩ).

ASU of residential buildings

To service multi-apartment residential buildings, devices for three-phase networks with alternating current, in which a solidly grounded neutral is provided. Among the main tasks in this case are electrical protection of the line in cases of short circuits, overloads and emergency power outages. What is a physical ASU for a residential building? This is a metal cabinet with provided by grounding, in which meters, switches, protection units, emergency panels for entering UPS, load distribution sensors, etc. are installed. In modern designs, the doors of such boxes provide an indication of key parameters of the electrical network.

Implementation of ASU at industrial facilities

First of all, multi-panel cabinets are used, designed for branched control of several energy supply circuits. Power indicators and the degree of protection with insulation in this case are higher, but in small enterprises or in individual workshops with normal conditions In operation, household automatic machines can also be used. But what are ASUs intended for operation on large public and industrial facilities? On this moment factory-assembled cabinets of the ShchO-70 line are widely used. From a design point of view, these are panels for one- and two-way control, which also include automatic transfer switches and switches designed for long working sessions in a mode independent of the main power source.

Installation of ASU

Installation of a cabinet with an ASU is carried out on the basis design scheme, compiled in accordance with the operating conditions at the specific location of application. First, mounting holes are drilled to secure brackets and screws for the metal structure. According to the instructions, the installation of input and distribution devices is carried out at a height of at least 30 cm, and a dielectric insulating ceiling must be provided between the rear panel and the wall. There are also floor structures, the installation of which is carried out on a special foundation or platform, which is attached to concrete screed.

Connecting equipment

After installing the ASU housing, the functional filling is assembled and connected. An aluminum armored circuit is used for cable entry. It is directly connected to the switch and control relay. Next, crimped wires extend from the relay into separate functional segments. Input distribution devices VRU-1 have two input blocks that can be connected to different supply networks. But an insulating partition must be maintained between them. At the final stage, the separated and connected wires are fixed with nylon ties at the bottom of the panel.

Conclusion

ASU systems perform important tasks in organizing electrical networks. The functionality of such equipment can be considered both as control and measuring, and as protective and control. Even 0.4 kV input distribution devices give ample opportunities regarding control of the operation of the laid network, taking into account the volumes of supplied energy both at the input and output. But the main task still lies in the physical distribution of power supply channels while ensuring a sufficient degree of reliability and safety of equipment operation. IN latest models The ASU also places emphasis on improving control ergonomics with expanded automatic functions.

GOST R 51732-2001

STATE STANDARD OF THE RUSSIAN FEDERATION

DEVICES
INPUT-DISTRIBUTION

General technical conditions

GOSSTANDARD OF RUSSIA

Moscow

Preface

1 DEVELOPED by JSC Central Design Bureau "Elektromontazh" INTRODUCED Technical Committee on standardization TC 331 “Low-voltage switching equipment for distribution and control” 2 ADOPTED AND ENTERED INTO EFFECT by Resolution of the State Standard of Russia dated April 5, 2001 No. 169-st 3 INTRODUCED FOR THE FIRST TIME

Introduction

This standard was developed with the aim of providing regulatory support for the development and implementation in production of input distribution devices that meet modern regulatory requirements for electrical installations of residential and public buildings different number of storeys, as well as the requirements of IEC standards regarding electrical and fire safety. The standard contains requirements for input and distribution devices used in high-rise and low-rise residential and public buildings (see. building codes SNiP 2.08.01-89, SNiP 2.08.02-89, SNiP 2.09.04-87), as well as in individual houses and cottages. This standard, in contrast to GOST 19734-80, contains requirements regarding the possibility of connecting input distribution devices to four- and five-wire supply (distribution) networks with a solidly grounded neutral (type of system grounding, respectively, TN - C and TN - S or TN - C - S according to GOST 30331.2-95 / GOST R 50571.2-94). This standard takes into account the requirements established by GOST R 51321.3-99 for switchgear used in places accessible to unqualified personnel. The standard provides for input distribution devices installed in individual houses and cottages, two methods of protection against electric shock, defined by classes I and II according to GOST R IEC 536-94. For input distribution devices installed in multi-storey and low-rise buildings (up to five floors), class I is established. Appendix B provides a method for determining the rated currents of ASUs and the rated operating currents of devices built into them.

1 area of ​​use. 2 2 Normative references. 2 3 Definitions. 3 4 Classification. 6 5 Basic parameters.. 6 6 General technical requirements. 7 6.1 General requirements. 7 6.2 Design. 7 6.3 Internal circuits. 10 6.4 Contact clamps.. 12 6.5 Accessories. 13 6.6 Degree of protection.. 14 6.7 Protection against damage electric shock.. 15 6.8 Electrical characteristics. 16 6.9 Protective coatings. 17 6.10 Reliability. 17 6.11 Marking. 17 6.12 Basic information about the ASU, given in operational documents. 17 6.13 Completeness. 18 6.14 Preservation and packaging. 18 7 Safety requirements. 18 8 Acceptance rules. 18 8.2 Acceptance tests. 18 8.3 Qualification tests. 19 8.4 Periodic tests. 21 8.5 Type tests. 21 9 Test methods. 21 10 Transportation and storage. 28 11 Operating instructions. 28 12 Manufacturer's guarantees. 28 Appendix A Schematic diagrams of inputs to the ASU.. 28 Appendix B Sample diagrams location of equipment in the ASU.. 29 Appendix B Determination of the rated currents of the ASU and the rated operating currents of the devices built into them. 32 Appendix D Designations of ASU types.. 34

STATE STANDARD OF THE RUSSIAN FEDERATION

INPUT AND DISTRIBUTION DEVICES
FOR RESIDENTIAL AND PUBLIC BUILDINGS

Are commontechnicalconditions

Input-distributional boards for dwellings and public buildings.
General specifications

dateintroduction 2002-01-01

1 area of ​​use

1.1 This standard applies to input distribution devices (hereinafter referred to as ASUs) intended for receiving, metering and distributing electrical energy in electrical installations of residential and public buildings, as well as for protecting distribution and group circuits extending from the ASUs during overloads and short circuits. 1.2 The standard applies to ASUs connected to power supply networks with a voltage of 380/220 V alternating current frequency 50-60 Hz with a solidly grounded neutral. 1.3 The standard establishes requirements for ASUs used in high-rise and low-rise residential and public buildings, as well as in individual residential buildings and cottages. 1.4 Climatic modification of the ASU - UHL4 according to GOST 15150 and GOST 15543.1. By agreement between the manufacturer and the consumer, ASUs can be manufactured in a different climatic design. Requirements determined by climatic design for more severe operating conditions must be given in the technical specifications for specific types of ASUs. 1.5 The standard establishes requirements for ASUs manufactured for the needs of the country’s economy and export. 1.6 All clauses of the standard, except 6.2.11, 6.2.14, 6.2.21, 6.3.12, are mandatory.

2 Normative references

This standard uses references to the following standards: GOST 2.601-95 one system design documentation. Operational documents GOST 9.032-74 Unified system of protection against corrosion and aging. Paint and varnish coatings. Groups, technical requirements and designations GOST 9.302-88 Unified system of protection against corrosion and aging. Metallic and non-metallic inorganic coatings. Control methods GOST 9.303-84 Unified system of protection against corrosion and aging. Metallic and non-metallic inorganic coatings. General requirements for the selection of GOST 9.401-91 Unified system of protection against corrosion and aging. Paint and varnish coatings. General requirements and methods of accelerated testing for resistance to climatic factors GOST 9.410-88 Unified system of protection against corrosion and aging. Polymer powder coatings. Typical technological processes GOST 12.1.004-91 System of occupational safety standards. Fire safety. General requirements GOST 12.2.007.0-75 System of occupational safety standards. Electrical products. General safety requirements GOST 12.4.026-76 System of occupational safety standards. Signal colors and safety signs GOST 27.003-90 Reliability in technology. Composition and general rules for specifying reliability requirements GOST 27.410-87 Reliability in technology. Methods for monitoring reliability indicators and plans for control tests for reliability GOST R IEC 536-94 Classification of electrical and electronic equipment according to the method of protection against electric shock GOST 4751-73 Eye bolts. Technical specifications GOST 10434-82 Electrical contact connections. Classification. General technical requirements GOST 11516-94 Hand tools for work under voltage up to 1000 V AC and 1500 V DC GOST 13716-73 Sling devices for vessels and apparatus. Technical conditions GOST 14192-96 Marking of cargo GOST 14254-96 (IEC 529-89) Degrees of protection provided by shells (IP code) GOST 15140-78 Paint and varnish materials. Methods for determining adhesion GOST 15150-69 Machines, instruments and others technical products. Versions for different climatic regions. Categories, operating, storage and transportation conditions regarding the impact of climatic factors external environment GOST 15543.1-89 Electrical products. General requirements regarding resistance to external climatic influences GOST 16962.1-89 (IEC 68-2-1-74) Electrical products. Test methods for resistance to external climatic influences GOST 16962.2-90 Electrical products. Test methods for resistance to mechanical external influences GOST 17516.1-90 Electrical products. General requirements for resistance to mechanical external influences GOST 18690-82 Cables, wires, cords and cable fittings. Labeling, packaging, transportation and storage GOST 19734-80 Input and distribution devices for residential and public buildings. General technical conditions GOST 21130-75 Electrical products. Grounding clamps and grounding signs. Design and dimensions GOST 21991-89 (IEC 447-74) Electrical equipment. Electrical devices. Direction of movement of controls GOST 22789-94 (IEC 439-1-85) Complete low-voltage devices. General technical requirements and test methods GOST 23216-78 Electrical products. Storage, transportation, temporary anti-corrosion protection, packaging. General requirements and test methods GOST 27483-87 (IEC 695-2-1-80) Fire hazard tests. Test methods. Heated wire tests GOST 27924-88 (IEC 695-2-3-84) Fire hazard tests. Test methods. Tests for poor contact using incandescent elements GOST 30331.1-95 (IEC 364-1-72, IEC 364-2-70) / GOST R 50571.1-93 (IEC 364-1-72, IEC 364-2-70) Electrical installations of buildings . Basic provisions of GOST 30331.2-95 (IEC 364-3-93) / GOST R 50571.2-94 (IEC 364-3-93) Electrical installations of buildings. Part 3. Main characteristics of GOST 30331.3-95 (IEC 364-4-41-92) / GOST 50571.3-94 (IEC 364-4-41-92) Electrical installations of buildings. Part 4. Security requirements. Protection against electric shock GOST R 50030.1-99 (IEC 947-1-88) Low-voltage distribution and control equipment. Part 1. General requirements GOST R 50462-92 (IEC 446-89) Identification of conductors by colors or digital designations GOST 50571.10-96 (IEC 364-5-54-80) Electrical installations of buildings. Part 5. Selection and installation of electrical equipment. Chapter 54. Grounding devices and protective conductors GOST R 51321.3-99 Complete low-voltage distribution and control devices. Part 3. Additional requirements for switchgear and control devices intended for use in areas accessible to unqualified personnel and test methods.

3 Definitions

In this standard, the following terms with corresponding definitions apply: 3.1 General terms and definitions 3.1.1VRU: Electrical device low voltage, containing equipment that provides the ability to input, distribute and meter electricity, as well as control and protect outgoing distribution and group electrical circuits in residential and public buildings, which is located in the form of appropriate functional blocks in one or more interconnected (mechanically and electrically) ) panels or in one cabinet, depending on the type of building according to 3.2. 3.1.2 function block: Part of interconnected devices of an ASU or panel (multi-panel ASU), ensuring the performance of a specific function according to 3.1.1. Note - The units of the unit may not be united by a single removable structural base. 3.1.3 input block: A functional block through which electricity is supplied to the ASU and containing switching and protective devices in accordance with Appendix A, and also including part of the volume of the ASU for placing, fastening and connecting the supply network conductors to the device(s). 3.1.4 automatic backup power supply unit (ABP): A functional block containing monitoring and control equipment for the starting switching devices of the input block, to which mutually redundant power supply networks are connected. 3.1.5 electricity metering unit: A functional block containing a direct or transformer connection meter, current transformers and a test adapter box. Note - Test adapter box is a device containing a terminal block for connecting a control three-phase meter. 3.1.6 distribution block: A functional block containing protective devices of distribution and group circuits and including part of the volume of an ASU or panel for placing and connecting conductors. 3.1.7 automatic lighting control unit: A functional block containing protective devices for group circuits of public lighting and elements for automatically turning them on and off depending on the degree of natural light and/or time of day according to a given program. Note - ASUs may contain units with non-automatic control of general house lighting. 3.2 Terms and definitions related to the design of ASUs (types of ASUs) 3.2.1multi-panel ASU: ASU, in which functional units are located in several panels, the number of which is determined by the composition and number of devices required for a specific electrical installation of an apartment building (with more than five floors) or a public building. 3.2.2 single-panel ASU: ASU made on the same on a constructive basis, as the panels of a multi-panel ASU, and containing all the necessary functional blocks for the electrical installation of a building or part of it (with the number of floors no more than five). 3.2.3 cabinet ASU: An ASU containing all the necessary functional units for the electrical installation of an individual house or cottage, installed in a cabinet-type shell. 3.3 Terms and definitions related to multi-panel ASU panels 3.3.1panel: A detachable part of a multi-panel ASU, made on a single structural basis with other panels and containing the corresponding functional blocks. 3.3.2 introductory panel: Panel of a multi-panel ASU, usually containing the equipment of the input unit(s) and metering unit(s). 3.3.3 input panel with AVR (panel with AVR): The introductory panel according to 3.3.2, which also contains a block with ATS equipment. 3.3.4 distribution panel: A multi-panel ASU panel containing devices of the distribution unit(s) and in which metering units, automatic or non-automatic lighting control units, etc. can also be placed. 3.3.5 fire protection device panel (PPU panel): Distribution panel of a multi-panel ASU, connected to the input panel with an ATS and designed to power electrical equipment and control circuits of fire extinguishing equipment, alarm circuits of fire-fighting devices, evacuation lighting and other electrical receivers necessary for warning and extinguishing a fire. 3.4 Terms and definitions related to structural elements of the ASU 3.4.1frame: The load-bearing part of the ASU panel on which the devices of the functional units are mounted, as well as shell elements and internal protective fences. 3.4.2 shell: Part of the ASU that provides protection from external influences and direct access to live parts from all sides, and also performs a function in a cabinet-mounted ASU load-bearing structure. 3.4.3shell element: Part of the outer shell of the ASU (walls, doors, plugs, covers, etc.). 3.4.4 compartment: Part of the internal space of the ASU, intended to accommodate the functional unit(s), fenced on all sides by partitions and/or walls and closed by a separate internal door or door of the ASU. 3.4.5 internal safety guard: A guard located behind the panel (cabinet) door that prevents unintentional direct contact with non-insulated live parts and provides protection from arc exposure during switching operations. 3.4.6 operational panel: The internal protective fence of the ASU, to which the device controls are located and which prevents access to live parts when the ASU door is open. 3.4.7 partition: Part of a panel (cabinet) separating one functional unit from another or separating circuits for various purposes. 3.4.8busbars: A system of conductors connected to the input block and intended for connecting to them phase, zero protective PE and zero working N conductors of several distribution and group electrical circuits. Note - The term "tire" does not define its design. 3.5 Terms related to the supply network and circuits extending from the ASU 3.5.1power supply network: Three-phase electrical distribution network with solidly grounded neutral, providing power supply to the ASU from an external source. 3.5.2 electrical distribution circuit: A three-phase electrical circuit extending from the ASU and feeding floor panels and/or other distribution points of the electrical installation of a residential (public) building. 3.5.3 group electrical circuit: Electrical circuit, extending from the ASU and intended to power lamps, sockets and other common house electrical receivers of the electrical installation of a residential (public) building. 3.5.4 combined neutral working and protective conductor (PEN conductor): According to GOST 30331.1 / GOST 50571.1. 3.5.5 neutral protective conductor (PE): According to GOST 30331.1 / GOST 50571.1. 3.5.6 zero working conductor (N): According to GOST 30331.1 / GOST 50571.1. 3.6 Terms and definitions related to the electrical parameters of the ASU 3.6.1rated current of the device: According to GOST 50030.1. 3.6.2 rated operating current of the device built into the ASU: The highest current value determined (in accordance with Appendix B) according to the conditions of the permissible temperature rise of the device and the elements of the circuit in which it is connected. 3.6.3 rated current ASU: Rated operating current of the input device, determined according to the conditions of permissible temperature rise in accordance with Appendix B. 3.6.4 rated current of multi-panel ASU: Rated current of the input panel. Note - If at the input of a multi-panel ASU there are two input devices with the same rated current to ensure the possibility of transferring the entire load connected to them to one of them, then the rated current of the ASU corresponds to the rated operating current of one device. 3.6.5 rated current of distribution panel: The highest current value determined under the conditions of permissible temperature rise (in accordance with Appendix B) for a given distribution circuit. 3.6.6 rated short-time withstand current of the circuit: According to GOST 22789. 3.6.7 rated conditional current short circuit chains: According to GOST 22789.

4 Classification

ASUs should be classified according to the characteristics given in Table 1. Table 1 - Classification of ASUs

Classification sign

Multi-panel

Single panel

1 At installation location:
- in electrical rooms
- outside electrical rooms
2 By type of installation:
- floor
- wall
- built into a niche
3 By degree of protection

According to 6.6

4 According to input schemes (scheme numbers - according to Appendix A)
5 According to the method (class) of protection against electric shock according to GOST R IEC 536:
- class I
- class II
6 Based on the presence of an automatic transfer switch (ATS):
- with block
- without block
7 According to the presence of an automatic control unit for general house lighting:
- with block
- without block (for public buildings)
8 On access to personnel services:
- qualified
- unqualified 1)
1) For unqualified personnel, servicing the cabinet ASU is limited to switching operations (GOST R 51321.3). 2) Only by agreement between the manufacturer and the consumer.

5 Basic parameters

5.1 The main parameters of the ASU must correspond to those given in Table 2. Table 2 - The main parameters of the ASU

Parameter name

Multi-panel

Single panel

1 Rated voltage at the ASU input, V
2 Rated currents of input devices, A

50; 63; 100; 125; 160

3 Rated currents of input switching devices of the panel with an automatic transfer switching unit (ATS), A

100; 160; 250; 400

4 Rated currents of ASU and multi-panel ASU panels, A

According to 5.2

5 Rated currents of protective and/or switching protective devices of distribution circuits, A

25; 32; 40; 63; 100; 160; 250

25; 32; 40; 63; 100; 160

10; 16; 25; 32; 40

6 Rated currents of protective devices of group circuits, A
7 Rated operating currents of protective devices built into the ASU, A

According to 5.2

8 Rated differential currents of residual current devices, mA:
- at the ASU input
- distribution chain
- group circuit
9 Rated short-circuit withstand current ( effective value 1)) for input block and prefabricated ASU tires, kA
The peak value of the short circuit current should be taken equal to the product of the effective value and the coefficient k = 1.5.
5.2 For single-panel and cabinet ASUs, as well as for each panel of a multi-panel ASU, their rated currents must be determined, and for devices built into them - rated operating currents in accordance with Appendix B. The obtained parameter values ​​must be given in the technical specifications for specific types of ASUs. 5.3 The main dimensions and weights of single-panel and cabinet ASUs, as well as panels of multi-panel ASUs, must be given in the technical specifications for specific types of ASUs. The overall dimensions of floor-standing ASU panels and cabinets, as a rule, should not exceed 2000 x 800 (1200) x 500 mm (height, width, depth), and wall-mounted and niche-built ASU cabinets - 1000 x 800 x 250 mm. 5.4 It is recommended to designate the types of single-panel and cabinet ASUs and multi-panel ASU panels in accordance with Appendix D.

6 General technical requirements

6.1 General requirements

6.1.1 ASUs must comply with the requirements of this standard, technical specifications for specific types of ASUs and design documentation approved in the prescribed manner. 6.1.2 ASUs of each type must have functional units of devices that meet the requirements of specific electrical installations of the relevant buildings in accordance with 1.3. 6.1.3 The operating conditions of the ASU and resistance to external factors must comply with 6.1.3.1-6.1.3.6. 6.1.3.1 Ambient air temperature - in accordance with the climatic design according to 1.4. 6.1.3.2 Altitude above sea level - no more than 2000 m. 6.1.3.3 Atmosphere type - I according to GOST 15150. 6.1.3.4 ASU must be resistant to the influence of normal and extreme values ​​of climatic factors according to GOST 15543.1 and GOST 15150, corresponding to the climatic design according to 1.4, and to the conditions of transportation and storage according to section 10. 6.1.3.5 ASUs must be resistant to mechanical environmental factors M 1 in accordance with GOST 17516.1. 6.1.3.6 Specific values external influencing factors must be given in the technical specifications for specific types of ASUs. 6.1.3.7 By agreement between the consumer and the manufacturer, the ASU can be manufactured for special operating conditions (for example, for more high temperatures ambient air, seismic conditions, operating conditions at an altitude of more than 2000 m above sea level, etc.). Additional requirements and test methods are established in the technical specifications for specific types of ASUs.

6.2 Construction

6.2.1 Class I ASU structural elements related to frames, shells and other conductive parts should be made primarily of steel with a protective coating. 6.2.2 Class II ASU shells, if they do not serve as supporting elements for live parts, must be made of insulating materials that are resistant to ignition when exposed to wire heated to a temperature of (850±10) °C, when the ASU is built into low-flammable walls - up to (b50±10) °C (see GOST R 51321.3). 6.2.3 Insulating elements of ASU classes I and II, on which current-carrying parts are attached, must be made of insulating materials that are resistant to ignition when exposed to wire heated to a temperature of (960±10) °C in accordance with GOST R 51321.3. 6.2.4 The heat resistance of class II ASU shells, as well as insulating bases according to 6.2.3, must comply with GOST R 51321.3. 6.2.5 The design of each type of ASU must provide one-way service from the front side, and the controls of the devices must be located behind the doors of the ASU. 6.2.6 Single- and multi-panel ASUs intended for installation in electrical switchboard rooms are recommended to be manufactured in a design that protects the ASU from the front and sides, and ASUs installed outside electrical rooms must have a design that protects the ASU from all sides, except for the bottom base adjacent to the floor. The degree of protection of single- and multi-panel, as well as cabinet-mounted ASUs is in accordance with 6.6. 6.2.7 In single- and multi-panel ASUs, the input and output of wires and cables of the power supply network must be provided from below. By agreement between the consumer and the manufacturer, the input and output of outgoing conductors can be provided both downward and upward. In a cabinet-type ASU, the input and output of conductors must be provided both in the bottom and in upper parts closet 6.2.8 In the input and distribution blocks, sufficient space must be provided for placing and connecting conductors to the devices in compliance with the standardized bending radii of insulated wires and cable cores. 6.2.9 Input and distribution blocks must have elements for fastening cables and wires of supply networks and distribution circuits. 6.2.10 If the input panel has two input blocks connected to different power supply networks (Scheme 6, Appendix A), then they must be separated by a partition. A partition should also be provided between the devices of the ATS unit (Scheme 7, Appendix A). 6.2.11 In single-panel and cabinet-mounted ASUs, the input and distribution blocks should be separated by partitions. 6.2.12 If two distribution blocks connected to different inputs are placed in one distribution panel of a multi-panel ASU, then a partition must be provided between them. 6.2.13 When using two input devices in the input block of multi-panel ASUs, they must be located so as to ensure free and safe access to the drive handles and ease of turning the devices on and off. 6.2.14 In the ASU input blocks, if specified in the order, the installation of arresters should be provided to protect the electrical installation from overvoltages. The arresters must be connected after the protective input devices. 6.2.15 In single-panel ASUs and input panels of multi-panel ASUs (by agreement between the consumer and the manufacturer), compartments according to 3.4.4 with doors should be provided to accommodate commercial electricity metering units. The doors must be locked with a key and have elements for sealing them. The compartments can be closed with an ASU door, or panels with a separate lock. 6.2.16 The compartments according to 6.2.15 must be designed to accommodate one or two metering units (if the ASU is powered from two supply networks), each of which includes a meter, a test box and current transformers (if the meters are transformer-connected). Metering blocks belonging to different input blocks should be separated by partitions. In each block, meters should be separated from current transformers by partitions to prevent accidental contact with their exposed live parts. 6.2.17 In a cabinet-mounted ASU, the input terminals for the conductors of the power supply network and the metering circuit should be located behind the operating panel (according to 3.4.6), which should be equipped with elements for sealing, while the metering units may not be separated into separate compartments. 6. 2.18 In cabinet-type ASUs, circuit breakers should be used as protective devices, the controls of which should be located on the operating panel, separating them from live parts. 6.2.19 In cabinet-type ASUs of class I, the operating panel can be made of conductive or insulating material. In class II ASU, this panel should only be insulating. 6.2.20 In cabinet-type ASU of class II, the shell and insulating operating panel according to 6.2.19 must exclude access to both current-carrying and conductive parts located inside the shell. 6.2.21 In distribution panels, it is recommended to provide control devices in front of individual or several protective devices (if they are fuses). Control devices can also be provided in front of automatic lighting control units, regardless of their location. 6.2.22 In the ASU, internal lighting should be provided (in multi-panel ASU - in each panel) for maintenance and repair when the input device is turned off. 6.2.23 Behind the doors of single- and multi-panel ASUs, protective barriers should be provided that completely or partially cover the most dangerous places to prevent accidental contact with non-insulated live parts in the direction of normal access to the devices. 6.2.24 Guards for chopping-type switching input devices must prevent arc surge, dangerous for the operator, and accidental contact with adjacent live parts when performing switching operations. 6.2.25 Removable parts of shells and internal fences should only be removed using a tool. 6.2.26 Device controls in single- and multi-panel ASUs must be located at a height of 600 to 1800 mm from the lower base; counter scales - at a height of 1000-1800 mm. For cabinet-mounted ASUs in the installed position, the height of the device controls and meter scales from the floor is determined taking into account the above values. 6.2.27 In single- and multi-panel ASUs located outside electrical rooms, the doors must be locked with a key, and in single- and multi-panel ASUs designed for installation in electrical rooms, the doors can be locked with a key or without a key (see also 6.2.15 ). In cabinet-style ASUs, the doors can be locked with a key or without a key. If the doors to the ASU are closed without a key, then they must be equipped with a device that prevents them from opening spontaneously. Required amount keys for ASU locks must be installed in the technical specifications for specific types of ASU. 6.2.28 ASU doors and compartment doors, if provided, must open to an angle that provides free access to the equipment, but not less than 95°. 6.2.29 To take meter readings, the compartment doors or doors of single- and multi-panel ASUs must have windows covered with impact-resistant transparent material. Such windows can also be provided in the doors of cabinet-type ASUs. Note - It is allowed not to make windows for taking meter readings in ASUs installed in electrical switchboard rooms. 6.2.30 The panel intended for connecting fire-fighting equipment must have side walls to localize the equipment installed in it, and its front part must be painted red. 6.2.31 In single-panel ASUs, as well as in the outer panels of multi-panel ASUs, the side walls must be removable for ease of maintenance. In panels occupying an intermediate position in multi-panel ASUs, side walls may not be installed unless this is required to localize the device units, as specified, for example, in 6.2.30. 6.2.32 The mechanical strength of means of fastening removable parts and shells, partitions, fences must comply with GOST R 51321.3. 6.2.33 In single- and multi-panel ASUs, in which fuses are used, must be provided on internal sides doors or other “pockets” for storing spare fuse links and accessories for their replacement. 6.2.34 ASUs of all types must be provided with compartments for storing operational documents in accordance with 6.12.1. In addition, the electrical circuits of the ASU must be fixed on the inside of the doors or in other places convenient for viewing. 6.2.35 Installation (fastening) of single- and multi-panel ASUs should be provided on the floor (to the floor). Cabinet ASUs must have modifications according to the type of installation: on the floor, on the wall, built into niches. ASUs must have fastening elements corresponding to the type of their installation. 6.2.36 The ASU in a fixed position must have sufficient rigidity to prevent deformations that negatively affect the operation of devices and instruments during impacts and jolts caused by turning on and off high-current switching devices, as well as during surge currents and short circuits. 6.2.37 ASU shells must withstand impacts of at least 0.7 J. 6.2.38 Single-panel ASU and panels of a multi-panel ASU must have sling devices for lifting, lowering and holding them suspended during installation and rigging work. Sling devices should be provided in each of the four corners on the top surface of the ASU or panel. 6.2.39 The lifting capacity of sling devices when the slings are directed at an angle of 45° should be for single-panel ASUs equal to the mass of the ASU divided by the number of slings involved (no more than two). For multi-panel ASU panels, which can be connected in three panels into transport blocks, the load capacity is equal to the total mass of the three panels divided by the number of slings used (no more than four). 6.2.40 If eye bolts are used as sling devices, then they must comply with GOST 4751. When developing special sling devices in relation to ASU, GOST 13716 should be followed. The safety factor of sling devices in the position connected to the ASU when lifting without jerking should not be less than 1.5.

6.3 Internal circuits

6.3.1 For internal circuits of the ASU, insulated copper wires, copper or aluminum busbars (preferably copper-clad) should be used. Zero protective busbars PE should be made of copper. It is permissible to make PE protective busbars from steel with a metal coating, and their equivalent conductivity must correspond to the conductivity of copper busbars, the cross-section of which is taken in accordance with 6.3.3. Exceeding the temperature of the protective tires during prolonged permissible current , equal to 50% of the rated current of the ASU, should not be more than those established in 6.8.1. Note - The requirement regarding the temperature rise of the protective busbars is due to the possibility of connecting PEN conductors of power supply networks to them in accordance with GOST 30331.3 / GOST R 50571.3. 6.3.2 The cross-section of the prefabricated phase busbars should be selected depending on the values ​​of the rated currents of the input devices given in Table 2, taking into account their permissible heating according to 6.8.1. 6.3.3 The cross-sections of busbars - zero protective PE and zero operating N - should be taken according to Tables 3 and 4, respectively, depending on the cross-section of the busbars. 6.3.4 Connections to phase busbars of conductors of internal circuits belonging to individual protective devices or groups of devices connected to each other by connecting elements, or to blocks, should be made dismountable. 6.3.5 On prefabricated zero operating busbars N and zero protective busbars PE, the possibility of dismountable connection of the corresponding conductors for both internal and external circuits must be provided. 6.3.6 In multi-panel ASUs, prefabricated phase busbars, as a rule, are made within the distribution panels, and zero protective PE and zero operating N busbars are installed within each ASU panel - input and distribution. 6.3.7 Connections of panel busbars according to 6.3.6 must be dismountable, and it is recommended to connect phase busbars with flexible interpanel jumpers, and zero protective and zero operating busbars - directly with each other or using busbar jumpers. 6.3.8 Jumpers according to 6.3.7 must be made of the same material as the busbars they connect, and their cross-section must be no less than the cross-section of these busbars. 6.3.9 If the jumpers according to 6.3.7 have a lower permissible temperature rise against the connected busbars (for example, due to their manufacture from insulated wires), then their cross-section should be increased accordingly. 6.3.10 Busbars must be located and secured so that under normal operating conditions the possibility of an internal short circuit is excluded. 6.3.11 Busbars must be resistant to the electrodynamic and thermal effects of short circuit current in accordance with 6.8.2. 6.3.12 It is recommended to place the zero protective PE and zero operating N busbars in close proximity to each other in places convenient for connecting external conductors. The zero protective busbar should be located below the zero working busbar at a height from the base of the ASU sufficient to ensure the normalized bending radii of cables with the largest cross-section that can be connected to the ASU. 6.3.13 Zero protective busbars PE must have an electrical connection with open conductive parts of the class I ASU, and zero operating busbars N must be isolated from them (with the jumper removed according to 6.3.15). 6.3.14 Zero protective busbars PE in class II cabinet-made ASUs must be insulated from conductive parts in the same way as live parts. 6.3.15 In the delivery state of the ASU, the zero protective PE and zero operating N busbars should be connected by a removable jumper with a cross-section equal to the cross-section of the zero operating busbar N, which should ensure the readiness of connecting the ASU to a four-wire supply network with a combined neutral protective and zero operating conductor - PEN- conductor. If the ASU must be connected to a five-wire network with zero operating N and zero protective PE conductors (TN - S system), then the jumper must be removed, which should be specified in the manufacturer’s operational document. 6.3.16 Zero protective PE and zero working N conductors must be different in color. According to GOST R 50462, protective conductors must have a green-yellow color, zero working conductors must have a blue color. Zero protective and zero operating busbars can be designated respectively by the signs “PE” and “N”, and in multi-panel ASUs these designations must be applied to the busbars of each panel. Other conductors of internal circuits must be designated in accordance with 6.3.27. 6.3.17 The cross-sections of phase conductors connecting single protective devices to busbars must be selected according to the rated currents of these devices and be at least 1.5 mm 2. 6.3.18 The cross-sections of the connecting elements of protective devices (according to 6.3.4) and the conductors connecting these elements with the busbars should be determined depending on the total current of the devices connected to them, multiplied by the simultaneity coefficient according to Appendix B. If to connect the mentioned conductors with The specified connecting elements cannot be used to use the terminal clamps of protective devices included in the connected group of devices (due to the mismatch of the cross-section of the conductors with the terminals of the devices or due to heating conditions), then either clamps on the connecting elements for these conductors or adapter clamps for connecting the conductors to the terminals should be provided devices. 6.3.19 The cross-sections of the conductors of the internal circuits of the units (for example, an automatic lighting control unit) must correspond to the values ​​​​established by the regulatory documents for the devices to which they are connected, or, if such information about the conductors is not available, be selected according to the rated currents of the devices. The method of connecting conductors to devices is determined by the design of their terminals. 6.3.20 Current circuits extending from current transformers to meters must be made of copper insulated wires with a cross-section of at least 2.5 mm 2, voltage circuits - with copper wires with a cross-section of at least 1.5 mm 2. 6.3.21 Control circuits should be made of conductors with a cross-section established for the corresponding equipment they connect. 6.3.22 Wires of internal circuits should not have intermediate connections. 6.3.23 The laying of insulated wires should be carried out in the designated places so that they do not touch uninsulated live parts and sharp edges of the conductive parts of the ASU, and their bending radii are not less than the standardized values. Wires must not interfere with the installation and dismantling of devices. The conductor connecting the neutral arrester to the PE protective bus should be laid separately from other conductors. Control circuit conductors must also be routed separately. 6.3.24 For large flows of small-section wires, they should be laid in the form of bundles or placed in boxes, while the number of wires combined into a bundle or laid in a box is determined by the conditions of their permissible temperature rise at the rated operating currents of the devices to which they are connected . 6.3.25 Where wires pass through partitions or walls of compartments (panels), measures must be taken to prevent damage to their insulation (processing the edges of holes, using bushings). 6.3.26 Wires must be insulated for a voltage of 660 V AC. This requirement also applies to the conductor connecting the arrester (overvoltage limiter) to the PE protective bus. 6.3.27 Wires of internal circuits must have digital markings at the ends in accordance with the electrical diagrams of the ASU. The marking must be in sharp contrast with the color of the wire insulation, be abrasion resistant and easy to read. At the ends of the prefabricated phase busbars, unless otherwise indicated on the diagrams, signs L 1, L 2, L 3 should be applied.

6.4 Terminals

6.4.1 The ASU must be provided with contact clamps (hereinafter referred to as clamps), which must ensure reliable connection of conductors of external and internal circuits and have means for stabilizing contact pressure in accordance with GOST 10434. 6.4.2 Clamps on phase busbars must provide connection copper conductors internal circuits with a cross-section from 1.5 mm 2 to the values ​​determined according to 6.3.17 and 6.3.18. 6.4.3 On the zero protective bus PE and the zero operating bus N, clamps must be provided for conductors of internal circuits and external conductors of distribution and group circuits, as well as for conductors of the supply network. The cross-sections of conductors, the connection of which must be ensured by clamps, are in accordance with 6.4.4. On the PE neutral protective bus, in addition to the specified clamps, the following should be provided: a) a clamp for connecting the neutral protective conductor connecting the ASU PE protective bus with the main grounding bus of the electrical installation, defined by GOST R 50571.10. The conductor cross-section for which the clamp must be designed should be taken according to Table 3; b) a clamp for connecting a grounding conductor with a cross-section in accordance with Table 3, but not less than 25 mm 2 for copper and 50 mm 2 for steel in accordance with GOST R 50571.10. Note - The clamp is used if the ASU protective bus is used as the main grounding bus of the electrical installation; c) a clamp for connecting a potential equalization conductor with a cross-section from 6 to 25 mm 2 in accordance with GOST 50571.10; d) a clamp for connecting a conductor with a cross-section of 10 mm 2 connecting the arrester to the PE protective bus. 6.4.4 The clamps provided on the zero protective bus PE and the zero operating bus N for connecting conductors of internal circuits and external conductors of distribution group circuits must provide connection of conductors with a cross-section from 1.5 mm 2 to the values ​​​​determined according to tables 3 and 4, in depending on the cross-section of phase conductors. The terminals for connecting the corresponding conductors of the supply network must ensure the connection of conductors with a cross-section one step larger than that defined in Tables 3 and 4. The number of terminals on the busbars for the conductors of the supply network should be determined taking into account the input diagrams of the ASU in accordance with Appendix A. Table 3 - Sections of phase and corresponding them of neutral protective conductors PE, mm 2

Phase conductor cross-section S

Cross section of the corresponding protective conductor

Note - If the material of the protective conductor differs from the phase conductor, then its cross-section must be such that it provides conductivity equivalent to the conductivity of the corresponding cross-section of the conductor given in the table.
Table 4 - Cross-sections of phase and corresponding neutral working conductors N, mm 2 The minimum cross-sections of conductors, the connection of which should be allowed by these clamps, are established in the technical specifications for specific types of ASUs. 6.4.5 As a rule, one conductor must be connected to each terminal for PE and N conductors. 6.4.6 Terminals for PE and N conductors of outgoing distribution and group circuits should be marked with serial numbers. 6.4.7 Terminals for connecting protective PE or PEN conductors of power supply networks must be marked with a grounding sign . The dimensions of the sign and the method of execution are in accordance with GOST 21130. 6.4.8 If it is difficult to connect phase conductors of outgoing distribution and group circuits, as well as external conductors of control circuits directly to the terminals of the devices, then intermediate terminals should be provided, connected to these terminals by conductors of internal circuits. For the convenience of connecting external conductors, these clamps should be placed above the zero operating bus in close proximity to it. They must ensure the connection of external conductors of the same cross-sections as the terminals of the devices to which they are connected. The clamps should be marked with serial numbers. 6.4.9 If the terminal terminals of the input devices of single- and multi-panel ASUs cannot provide the possibility of connecting to them the required number of supply network conductors (see Appendix A), then provision should be made for connecting intermediate current-carrying elements with the required number of terminals to the terminals of the devices. Intermediate elements must have electrodynamic and thermal resistance to short circuit currents in accordance with 6.8.2. If necessary, they must be additionally secured. The minimum cross-section of these elements should be selected according to the rated current of the input device of the corresponding ASU.

6.5 Accessories

6.5.1 Components and devices of functional blocks should be selected taking into account the parameters of the ASU given in Table 2. 6.5.2 Apparatuses and instruments, as well as contact terminals must meet the requirements of the relevant state standards. 6.5.3 In input units, automatic switches, non-automatic switches and switches in combination with fuses, fuse-switches should be used; in input units with automatic power reserve switching - contactors, magnetic starters, automatic switches with a drive. Arresters (surge suppressors) should be used in input blocks. Electrical characteristics of arresters are as agreed between the consumer and the manufacturer. 6.5.4 Switching devices installed in input blocks must have an application category of at least AC21 according to GOST R 50030.1. 6.5.5 The breaking capacity of automatic circuit breakers, as well as fuses used with non-automatic circuit breakers at the input of single- and multi-panel ASUs, must not be lower than the values ​​of short-circuit currents given in Table 2. 6.5.6 Devices of input blocks of single- and multi-panel ASUs, as well as their busbars must have electrodynamic and thermal resistance to short-circuit currents according to Table 2. 6.5.7 In distribution blocks to protect distribution and group circuits, the following should be used: a) one- and three-pole circuit breakers with combined releases of types B, C and D according to customer order. By agreement between the consumer and the manufacturer, two- and four-pole switches can be used. It is recommended to use automatic circuit breakers for rated currents up to 63 A with a single sized module and with hardware-free mounting on standardized rails; b) residual current devices with built-in overcurrent protection (releases according to listing a) or without it, if overcurrent protective devices are provided in the protected circuits; c) fuses, preferably with a trip indicator (in single- and multi-panel ASUs). 6.5.8 Rated currents of protective devices according to 6.5.7 - according to table 2. 6.5.9 The breaking capacity of protective devices according to 6.5.7 must be (unless otherwise specified by the consumer) not lower than 3 kA for rated currents up to 25 A, 6 kA - for rated currents up to 63 A and 10 kA - for rated currents up to 125 A. The breaking capacity of devices for rated currents of 160 A and above must be not lower than the values ​​of short circuit currents given in table 2. 6.5.10 In metering units it should be used three-phase meters active energy of direct connection to the corresponding currents or three-phase meters of transformer connection at current values ​​exceeding those permissible for direct connection meters. Note - By agreement between the manufacturer and the consumer, meters may not be supplied or may be supplied separately. 6.5.11 Current transformers in metering units should be used for rated currents corresponding to the rated currents of the circuit protective devices, unless otherwise specified by the consumer. In distribution panels, the rated currents of the current transformers must correspond to the rated currents of those panels and/or the rated current of the distribution unit or distribution circuit. 6.5.12 The accuracy class of current transformers must be 0.2 or 0.5. The accuracy class of the meters is not lower than 2.0. 6.5.13 Test boxes used in metering units must have elements for their sealing. 6.5.14 In automatic control units for general house lighting, unless otherwise specified by the consumer, the following should be provided: a) photo relay and/or time relay; b) switching devices of control circuits; c) automatic switches of types B, C to protect group circuits. 6.5.15 The characteristics of the devices of the automatic lighting control unit (6.5.14 a, b) should be indicated in the technical specifications for specific types of ASU. 6.5.16 The devices and components of the ASU must be marked in accordance with the electrical circuit diagram. The marking must be durable and readable and can be placed on or near the bodies of devices and components. 6.5.17 Specific values ​​of parameters of devices and instruments must correspond to the consumer’s order. 6.5.18 The installation of component devices in the ASU should be carried out taking into account the requirements of their manufacturers’ instructions regarding the position of the devices, maintaining distances to conductive parts, cross-sections of connected conductors, etc.

6.6 Degree of protection

The degree of protection of the ASU in accordance with GOST 14254 from touching live parts and other external influences in the mounted position must be no lower: a) in single- and multi-panel ASUs installed on the floor in electrical rooms: - with the doors closed on the service side and on the sides - IP 2 X; - top, bottom and back - IP 00; - with open doors (degree of protection provided by protective barriers in accordance with 6.2.23 in the direction of normal access to the equipment) - IP2X; - commercial metering compartment with its door or panel door closed - IP2X; b) in single- and multi-panel ASUs installed in buildings on the floor outside electrical rooms: - with the doors closed - IP 31, from the side of the lower base adjacent to the floor - IP00; - with open doors (degree of protection provided by protective barriers in accordance with 6.2.23 in the direction of normal access to devices) - IP2X; c) in cabinet-type ASUs of classes I and II with behind closed doors: - floor-mounted and wall-mounted - IP31; - built into niches - IP31 (built-in part - IP 20). With the doors open and any type of installation of a cabinet ASU, the degree of protection provided by the operating panel must be at least IP 2 XC.

6.7 Protection against electric shock

6.7.1 To prevent accidental contact with live parts of the ASU, the degree of protection provided by the shell in accordance with GOST 14254 must comply with 6.6, and design measures in accordance with 6.2 must also be carried out. 6.7.2 In ASUs of all types of class I, open conductive parts must have electrical connections between themselves and with the PE zero protective bus in accordance with 6.3.13 and comply with the requirements of 6.7.5. In single- and multi-panel ASUs, these connections must withstand short-circuit currents in accordance with 6.8.2. If ASUs are installed on the door electrical devices, then the door should be connected to the conductive frame or shell with a flexible copper jumper with a cross-section in accordance with GOST 22789. 6.7.3 Conducting parts located inside the insulating shell of a class II cabinet ASU should not have an electrical connection with the PE zero protective bus and the conductors connected to it. This also applies to built-in components, even if they have terminals for the protective conductor. 6.7.4 Exposed conductive parts must not cross the enclosure of a Class II ASU. 6.7.5 The electrical resistance between the terminal for connecting the neutral protective PE (PEN) conductor of the power supply network to the assembled neutral protective PE busbar and each part of the ASU according to 6.7.2 should not be more than 0.1 Ohm. 6.7.6 ASUs that contain fuses must be equipped with devices for installing and removing fuse-links from their contact bases. 6.7.7 Controls of input and protective devices of distribution and group circuits must be made of insulating material or have insulation on their conductive parts. 6.7.8 The controls of the devices must have clearly fixed “on-off” positions in accordance with the markings on the devices. If, after installing the devices in the ASU, it is impossible to judge their switching position, then the devices must have duplicate designations of the positions of their control elements. 6.7.9 The directions of movement of the device controls in the installed position must comply with GOST 21991. 6.7.10 The class II ASU nameplate must bear the sign ÿ, indicating protection against electric shock by double or reinforced insulation. 6.7.11 One of the terminals of the secondary windings of the current transformers must be connected to the assembled zero protective PE busbar. 6.7.12 On the outside of the doors, as well as on the internal fences (per 6.2.23, 6.2.24), the warning sign “Caution! Electrical voltage" according to GOST 12.4.026. 6.7.13 The design of the ASU must ensure the safety of qualified personnel performing the following operations without removing the voltage: - visual inspection of the devices, their technical data recorded on the nameplates; - replacement of fuse links; - setting the time relay to the appropriate operating mode; - search for damage using special devices(voltage indicators, voltmeters, etc.); - checking the markings of conductors. 6.7.14 The fences provided in the ASU must be installed and removed using a tool without the risk of contact with bare live parts or damage to the insulation of live parts.

6.8 Electrical characteristics

6.8.1 At rated currents of cabinet-type and single-panel ASUs, as well as at rated currents of multi-panel ASU panels, the temperature of their parts above the ambient air temperature and the permissible heating temperature of these parts at an ambient temperature of 35 °C should not exceed the values ​​given in the table 5 . Note - The heating temperature is the sum of the upper value of the operating ambient temperature and the corresponding temperature rise value. Table 5 - Temperature rise, °C

Part of the ASU

Permissible temperature rise above ambient temperature 35 °C 1)

Permissible temperature heating

1 Contact connections of device terminals, contact clamps with internal and external conductors
2 Bare conductors (busbars)
3 Conductors with polyvinyl chloride insulation
4 Controls made of insulating material
5 Available shell parts:
- metal
- made of insulating material
1) At an upper ambient temperature value other than 35 °C, the permissible temperature rises can be changed within the limits of the specified permissible heating temperatures. 2) The permissible heating temperature of conductors with other types of insulation is established in the technical specifications for specific types of ASUs.
6.8.2 Input blocks and prefabricated phase busbars of single- and multi-panel ASUs must withstand the thermal and electrodynamic effects of rated short-term withstand short-circuit currents, the values ​​of which are given in Table 2. Zero busbars N and PE of these ASUs, as well as connections of conductive parts with PE busbars must be resistant to short circuit currents equal to 60% of the current values ​​given in Table 2. The short circuit current exposure time is 0.2 s. Note - Input blocks and prefabricated phase busbars of a cabinet ASU with a rated short-term withstand current not exceeding 10 kA are not subjected to tests for the effects of this current in accordance with GOST 22789. 6.8.3 Air gaps and creepage distances between non-insulated live parts of the ASU, as well as between them and conductive parts, in addition to the distance to the door, must be at least 12 mm. The air distance to the door is at least 50 mm. Notes 1 The specified distances are given with connected conductors of internal and external circuits. These distances do not apply to devices installed in the ASU. 2 The distances between busbars are also set based on their electrodynamic resistance to short circuit currents. 6.8.4 The insulation of the internal circuits of the ASU in a cold state under normal test conditions in accordance with GOST 15150 must withstand an alternating current test voltage of 2500 V with a frequency of 50 Hz for 1 min. 6.8.5 The electrical strength of the insulating shell of a class II cabinet-made ASU must be 1.5 times higher than that given in 6.8.4 (test voltage 3750 V). 6.8.6 The electrical insulation resistance of the internal circuits of the ASU in a cold state must be at least 10 MOhm.

6.9 Protective coatings

6.9.1 Metal parts of the ASU must have protective paint, powder polymer and/or metal coatings. 6.9.2 Paint and varnish coatings must comply with GOST 9.401, powder coatings - GOST 9.410. 6.9.3 Paint and powder polymer coatings of the external surfaces of the ASU must comply with class IV, internal surfaces- VI class according to GOST 9.032. 6.9.4 Metal coatings must comply with the requirements of GOST 9.303. 6.9.5 Specific types of protective coatings, their thickness, adhesion score, as well as control methods must be specified in the technical specifications for specific types of ASUs.

6.10 Reliability

6.10.1 Reliability indicators of ASUs and methods for their control are established in the technical specifications for specific types of ASUs at the request of the consumer, taking into account GOST 27.003 and GOST 27.410. 6.10.2 The established service life is 25 years, with the possible replacement of individual components of the ASU.

6.11 Marking

6.11.1 Each single-panel and cabinet ASU and each panel of a multi-panel ASU must have a nameplate with permanent markings attached to the door from the outside. 6.11.2 The dimensions of markings and the method of their application are established in the technical documentation for specific types of ASUs. 6.11.3 The nameplate must contain the following data: 1) name of the manufacturer or its trademark; 2) mark of conformity; 3) type designation; 4) rated voltage; 5) rated current of the ASU (ASU panels); 6) degree of protection; 7) sign for class II ASU; 8) mass of the ASU or panel; 9) designation of technical conditions; 10) year of manufacture; 11) other technical data at the discretion of the manufacturer.

6.12 Basic information about the ASU given in operational documents

6.12.1 The operational document for each type of ASU should be considered the Operation Manual, unless otherwise provided in the technical specifications for specific types of ASU. 6.12.2 The manufacturer must provide the following basic information about the ASU in the operational documents: 1) name of the manufacturer; 2) certification information; 3) scope and operating conditions; 4) climatic version; 5) typeVRU ________ __________ ; type designation 6) rated voltage; 7) rated frequency; 8) rated currents of ASUs and multi-panel ASU panels; 9) rated currents of devices (input and protective distribution and group circuits); 10) rated operating currents of devices according to listing 9, based on the conditions of permissible heating; 11) maximum switching capacity of circuit breakers and breaking capacity of fuses (according to the manufacturer); 12) rated differential currents of residual current devices; 13) rated and maximum currents of meters; 14) degree of protection according to GOST 14254; 15) protection class according to GOST R IEC 536; 16) cross-sections and number of supply network conductors connected to the ASU; 17) electrical diagram of the ASU; 18) installation instructions, including instructions for connecting ASUs in electrical installations with various types of grounding systems; 19) indication of safety measures during operation; 20) overall and installation dimensions; 21) mass of the ASU and individual panels of a multi-panel ASU.

6.13 Completeness

The completeness is established in the technical specifications for specific types of ASUs. Supplied ASUs must be accompanied by a certificate of conformity.

6.14 Preservation and packaging

6.14.1 Preservation and packaging of ASUs must comply with GOST 23216. 6.14.2 Parts of ASUs subject to preservation and methods for its implementation are established in the technical specifications for specific types of ASUs. 6.14.3 Packaging of ASUs must prevent them from being damaged during transportation and storage. 6.14.4 If the ASU must be supplied with meters, then in order to avoid damage, the latter can be separately packaged in accordance with the requirements of the meter standard. 6.14.5 If, by agreement between the manufacturer and the consumer, the ASU is supplied without meters, then at the place of their installation there must be a label indicating the type and characteristics of the corresponding meter, fasteners, and conductors in accordance with 6.3.20. 6.14.6 The internal packaging of the ASU in accordance with GOST 23216 is established in the technical specifications for specific types of ASU. 6.14.7 Types of transport packaging and its dimensions are established in the technical specifications for specific types of ASUs. 6.14.8 Operational documentation must be placed in a waterproof bag in the compartment provided in each ASU in accordance with 6.2.34. The rest of the documentation (packing list, certificate, etc.) must be packaged and placed in cargo spaces in accordance with GOST 23216 and technical specifications for specific types of ASUs. 6.14.9 Transport marking - in accordance with GOST 14192. 6.14.10 Preservation and packaging of ASU supplied for export must also comply with the requirements of the contract.

7 Safety requirements

7.1 The ASU in relation to protection against electric shock must meet the requirements of 6.6 and 6.7. 7.2 Fire safety of the ASU must be ensured by the measures provided for in 6.2.3, 6.2.4, 6.5.4-6.5.9, 6.8.1-6.8.6 of this standard and GOST 12.2.007.0. 7.3 The probability of a fire occurring in (from) the ASU should not exceed 10 -6 1/year according to GOST 12.1.004. Note - The possibility of fire is not included in the certification requirements.

8 Acceptance rules

8.1 The ASU must be subjected to acceptance, qualification, periodic and type tests by the manufacturer.

8.2 Acceptance tests

8.2.1 Each cabinet and single-panel ASU and each panel of a multi-panel ASU of the submitted batch must be subjected to acceptance tests. The inspection and testing program is in accordance with Table 6.

Table 6 - Acceptance testing program

technical requirements

test methods

1 Checking the functioning of doors and their locking devices
2 Checking the presence of a jumper between the protective and zero operating buses
3 Checking the color marking of the zero protective and zero working conductors, as well as the presence of the designations “PE” and “N”, respectively, on the zero protective and zero working busbars
4 Checking the cross-sections of metering circuit conductors
5 Checking compliance of conductor insulation with voltage 660 V
6 Checking the presence of digital markings of wires and designations of prefabricated phase busbars
7 Checking the markings of terminals for conductors of distribution and group circuits
8 Checking the marking of the terminals of the protective conductors of the power supply networks with a grounding sign
9 Checking the markings of devices, their parameters and location in the ASU
10 Check electrical resistance between the terminal of the neutral protective conductor of the supply network and the conductive parts
11 Checking the functioning of the controls of the devices and the correct direction of their movement
12 Checking the presence of ASU markings of protection class II
13 Checking the presence of connection of the secondary windings of current transformers with the zero protective PE bus
14 Voltage warning sign check
15 Insulation resistance measurement
16 Checking paints and powders polymer coatings
17 Check metal coatings
18 Checking the ASU markings
19 Checking the completion of the operational document
20 Checking the completeness
21 Checking preservation and packaging
Note - The sequence of checks during acceptance tests is established by the manufacturer in the technological documentation.
Inspection of paint and powder polymer coatings according to 6.9.2 and 6.9.3, metal coatings according to 6.9.4 should be carried out selectively. The scope of control is established in the technical specifications for specific types of ASUs. It is allowed to check coatings on samples (fragments of shells or frames), on which the coating must be made using the same technology as on the ASU. The samples must be made of the same material as the corresponding parts. 8.2.2 To check the appearance of the ASU, as well as to perform other verification operations, samples of the ASU or their fragments approved in the prescribed manner should be used. 8.2.3 By agreement between the consumer and the manufacturer, the scope of acceptance tests can be expanded and established in the technical specifications for specific types of ASUs. 8.2.4 ASUs that fail to pass tests and inspections are subjected to repeated testing after the deficiencies are eliminated. It is allowed to carry out repeated tests on points of non-compliance of the ASU. The results of repeated tests are final.

8.3 Qualification tests

8.3.1 ASUs from the first industrial batches that have passed acceptance tests are subjected to qualification tests. The scope of qualification tests is in accordance with Table 7.

Table 7 - Qualification and periodic testing program

Name of inspections and tests

Type of test

Qualification

Periodic

technical requirements

test methods

1 Checking the main dimensions, weight
2 Checking compliance with the requirements for the design of the ASU and its clamps

6.2.1 , 6.2.5-6.2.26 , 6.2.29-6.2.31 , 6.2.33-6.2.35 , 6.2.38 , 6.3.1-6.3.10 , 6.3.12-6.3.14 , 6.3.17-6.3.19 , 6.3.21-6.3.25 , 6.4.1 , 6.4.5 , 6.4.8 , 6.4.9 , 6.7.1-6.7.4 , 6.7.13 , 6.7.14

3 Checking the possibility of connecting conductors of appropriate sections to the terminals
4 Tests for resistance to climatic factors
5 Test for mechanical factors
6 Fire test
7 Heat resistance test
8 Mechanical strength test of threaded means of fastening removable parts
9 Testing the rigidity of the ASU structure
10 Mechanical shock resistance test
11 Testing of lifting sling devices
12 Checking the characteristics of the types of component equipment used in the ASU

6.5.1-6.5.15 , 6.7.7

13 Checking the degree of protection
14 Rated operating current overtemperature test
15 Short circuit current test
16 Measuring clearances and creepage distances
17 Dielectric strength test
18 Reliability test
19 Calculation of the probability of a fire occurring in (from) the ASU
8.3.2 Type representatives of cabinet-type ASUs and single-panel ASUs, as well as type representatives of input and distribution panels of multi-panel ASUs, which must be subject to qualification tests, are established in the technical specifications for specific types of ASUs, taking into account the test results in accordance with Appendix B. 8.3.3 Qualification tests (except for fire hazard tests according to 6.2.2, 6.2.3, 7.3 and heat resistance according to 6.2.4) two samples of each type representative must be subjected. 8.3.4 Samples according to 8.3.3 are tested for compliance with the requirements given in table 7, and one of them is checked sequentially according to points 1, 2, 3, 12, 9, 10, 11, 8, 4, 5, the second - according to 16 , 17, 14, 15, 13, 18. To check the rigidity of structures according to paragraph 9 of Table 7, single- and multi-panel ASUs with input devices for the highest rated current are tested (see Table 2). 8.3.5 Each group of tests according to 8.3.4 is performed in the given sequence of listing the items in Table 7. 8.3.6 To carry out tests for fire hazard and heat resistance (items 6, 7 of Table 7), three samples of insulating shells must be selected for each type of test ( ASU class II) and insulating bases on which contact clamps are attached in ASU classes I and II. The procedure for testing for fire hazard is in accordance with GOST 27483 and/or GOST 27924, for heat resistance - in accordance with GOST R 51321.3. 8.3.7 If the tested samples according to 8.3.4, 8.3.6 do not comply with at least one point of the technical requirements, then repeated tests must be carried out on a double number of samples for the points of non-conformity. The results of repeated tests are final. 8.3.8 The number of samples and the scope of reliability tests, as well as tests related to determining the likelihood of a fire (clauses 18 and 19 of Table 7) - in accordance with the technical conditions for specific types of ASUs. Note - The required number of samples for experimental and calculation determination of the probability of a fire according to 9.40 is agreed with the institute fire department Ministry of Internal Affairs.

8.4 Periodic testing

8.4.1 ASUs that have passed acceptance tests must be subjected to periodic testing. 8.4.2 Types of ASU (cabinet and/or single-panel) and multi-panel ASU panels that must be subject to periodic testing - in accordance with 8.3.2. For periodic testing, three samples of each type of ASU of the corresponding type or panels of a multi-panel ASU are selected in accordance with the technical specifications for specific types of ASU, taking into account the requirements given in Appendix B. 8.4.3 First, one sample is tested in the volume given in Table 7. Tests carried out in the following sequence of points in Table 7: 2, 12, 16, 17, 14, 15, 13. 8.4.4 If, when testing one sample, positive results, then the other two samples are not tested. In case of unsatisfactory test results, repeated tests are carried out on two other samples for points of non-conformity, and both samples must pass all tests. 8.4.5 Periodic tests must be carried out at least once every three years to the extent given in Table 7. 8.4.6 The results of periodic tests can be used for certification purposes in agreement with the certification body.

8.5 Type tests

8.5.1 Type tests of the ASU are carried out to assess the effectiveness and feasibility of changes made to the design or technological process. 8.5.2 Type tests are carried out according to a program that includes a partial or full scope of qualification tests in accordance with Table 7. Depending on the nature of the changes, the program may include tests that are not included in the scope of qualification tests. 8.5.3 The selection of ASU type representatives, their number and test rules are established in the type test program.

9 Test methods

9.1 Checking the dimensions and mass of the ASU according to 5.3 should be carried out by means that must be provided for in the technical specifications for specific types of ASU. 9.2 Checking compliance with the design requirements of the ASU according to 6.2.1, 6.2.5-6.2.26, 6.2.29-6.2.31, 6.2.33-6.2.35, 6.2.38, 6.3.1-6.3.10, 6.3. 12-6.3.14, 6.3.17-6.3.19. 6.3.21-6.3.25, 6.4.1, 6.4.5, 6.4.8, 6.4.9, 6.7.1-6.7.4, 6.7.13, 6.7.14 are compared with the design documentation. 9.3 Checking the possibility of connecting conductors of the corresponding sections to the terminals according to 6.4.2-6.4.4 is carried out by trial installation, for which conductors of the largest and smallest sections must be connected to the terminal and the degree of their fastening in the terminal must be checked. The testing procedure is established in the technical specifications for specific types of ASUs, depending on the design of the clamps. 9.4 Testing for the influence of environmental climatic factors according to 6.1.3.4 must be carried out in accordance with GOST 16962.1. Test methods are established in the technical specifications for specific types of ASUs. 9.5 Tests for the influence of mechanical environmental factors according to 6.1.3.5 must be carried out in accordance with GOST 16962.2. Test methods are established in the technical specifications for specific types of ASUs. 9.6 Tests for fire hazard of the insulating shells of cabinet ASUs according to 6.2.2 and insulating bases according to 6.1.3, on which the contact clamps are attached, should be carried out with a heated wire in accordance with GOST 27483. Preparation of samples for testing - according to the same standard. The heating temperature of the samples is according to 6.2.2 and 6.2.3. Tests of the insulating base of the terminals must be carried out in the ASU or outside it. During testing, the insulating base must be in working position. A heated wire in a loop is brought into contact with each part being tested once at any location. Tests are carried out under normal climatic conditions in accordance with GOST 15150. Criteria for assessing test results are in accordance with GOST 27483. If the ASU includes contact clamps for rated currents up to 63 A, the design of which complies with GOST 27924, then tests of insulating bases with clamps installed on them can be carried out according to this standard using incandescent elements. Preparation of samples for testing, their conduct, as well as criteria for assessing test results - in accordance with GOST 27924. Notes 1 It is allowed not to test the shells of class II cabinet ASUs and insulating bases of clamps if they are manufactured according to regulatory documentation, which provides for fire hazard testing. 2 The insulating bases of the clamps are not tested if they are made of non-combustible materials (ceramics, porcelain, etc.). 9.7 The heat resistance test according to 6.2.4 of the shells of cabinet ASUs of class II and the insulating bases on which the clamps in ASUs of classes I and II are attached should be carried out in accordance with GOST R 51321.3. 9.8 Checking the functioning of doors and their locking devices in accordance with 6.2.27 and 6.2.28 is carried out by testing them in operation three times. 9.9 Checking the mechanical strength of screw fastening devices for removable parts according to 6.2.32 should be carried out in accordance with GOST R 51321.3. The test results are considered satisfactory if during the test there were no damages listed in the specified standard. 9.10 Checking the rigidity of ASU structures according to 6.2.36 is carried out in a position fixed to the floor by turning on and off manually driven input devices and starting devices in ATS panels five times. The results of checking the rigidity of the ASU are considered positive if, during the process of turning the devices on and off, no residual deformation occurred in the frame elements, and possible elastic deformation did not negatively affect the operation of the automatic control units for general house lighting, i.e. under the influence of the shock, the automation elements did not operate, and the meter was not damaged in the metering unit. The rigidity of the ASU structures is considered sufficient if the indicated or other defects were not also identified when testing the ASU for the effects of short circuit current according to 9.29. 9.11 The shells of cabinet ASUs of classes I and II, as well as the shells of single- and multi-panel ASUs of class I are subjected to mechanical shock resistance tests in accordance with 6.2.37. The shells of cabinet ASUs are tested as wall installation(impacts are applied from all sides except the back), and ASU shells built into niches (impacts are applied only on the front side). The shells of single- and multi-panel ASUs are exposed to impacts from the front and sides. When striking the front side, all types of ASU doors must be closed. The number of blows, the method of their implementation and the evaluation of test results - in accordance with GOST R 51321.3. The testing must also not destroy the transparent material protecting the meter reading windows. Individual cracks are allowed that do not impair the view of the meter scales. 9.12 Testing of sling devices in accordance with 6.2.38-6.2.40 is carried out by lifting the ASU with an additional load amounting to 50% of the mass of the ASU, using the minimum number of sling devices in accordance with 6.2.39. Additional load can be created by a dynamometer according to Figure 1, illustrating the lifting of a single-panel ASU. Lifting is carried out using cable slings terminated with hooks and designed for the appropriate load. The direction of the slings should be at an angle of 45° relative to vertical axis ASU (see Figure 1).

1 - dynamometer 1; 2 - sling; 3 - sling device; 4 - VRU; 5 - dynamometer 2

Picture 1

Load holding time of sling devices - 10 min. Sling devices are considered to have passed the test if the devices themselves or their connections to the frame have not ruptured, or cracks and tears have not appeared in them. Notes 1 Sling devices can be tested on a tensile testing machine using an appropriate fragment of the ASU, which ensures that forces are applied to them at a given angle. 2 If the mass of the test sample is not the maximum for a given type of ASU, then bringing the load to the maximum value should be achieved using dynamometer 2 (see Figure 1). 9.13 The presence of a jumper between the protective and zero operating busbars is checked according to 6.3.15 visually, and the reliability of its connection to the busbars is checked with the appropriate tool (wrench, screwdriver). 9.14 Checking the color marking of the zero protective and zero working conductors, as well as the presence of the designations “PE” and “N”, respectively, on the zero protective and zero working busbars according to 6.3.16 is carried out visually. 9.15 Checking the cross-section of copper conductors of metering circuits according to 6.3.20 is carried out visually. 9.16 Checking the compliance of wire insulation with a voltage of 660 V according to 6.3.26 is carried out according to their markings in accordance with GOST 18690 and/or a certificate. 9.17 Checking the digital marking of wires of internal circuits and the designation of prefabricated phase busbars according to 6.3.27 is carried out visually and by comparison with the electrical diagram. 9.18 Checking the marking with serial numbers of terminals for zero working and zero protective conductors of distribution and group circuits according to 6.4.6 is carried out by comparison with the design documentation. 9.19 Checking the marking of terminals for protective conductors of power supply networks with a grounding sign according to 6.4.7 is carried out visually. 9.20 Checking the compliance of the types of devices used in the ASU and their characteristics with the requirements of 6.5.1-6.5.15, 6.7.7 is carried out by comparison with the design documentation. 9.21 The marking of devices according to 6.5.16 is checked by comparison with the electrical diagram, their parameters according to 6.5.17 - by comparison with consumer orders and the location of devices according to 6.5.18 - according to the design documentation. 9.22 Checking the degree of protection according to 6.6 should be carried out in accordance with GOST 14254. The ASU must be tested for the degree of protection in the installed position with external conductors connected. Evaluation of test results - in accordance with GOST 14254. 9.23 Checking the electrical resistance according to 6.7.5 between the terminal for connecting the neutral protective conductor of the supply network and the conductive parts of the ASU is carried out by measuring the resistance with an ohmmeter with the appropriate measurement limit. 9.24 Checking the functioning of the device controls in accordance with 6.7.8 is carried out by turning the devices on and off three times, and clear fixation in the “on” and “off” positions must be ensured. Checking duplicate designations of devices, if provided, is carried out visually. At the same time, the correct direction of movement of the device controls is checked in accordance with 6.7.9 by comparing the actual direction of movement with that specified in the technical specifications for specific types of ASUs and GOST 21991. 9.25 The presence of class II ASU markings in accordance with 6.7.10 is checked visually. 9.26 Checking the connection of the secondary windings of current transformers with the zero protective busbar PE is carried out visually, while checking the reliability of the connection of the conductors with the terminals of the current transformers and with the zero protective busbar, using the appropriate tool (screwdriver, wrench). 9.27 Checking for the presence of a voltage warning sign on the outside of the doors according to 6.7.12 is carried out visually. 9.28 Testing the ASU for temperature rise over 6.8.1 9.28.1 Testing of cabinet and single-panel ASUs, as well as panels of a multi-panel ASU for temperature excess, is carried out with their rated currents in the operating position under normal climatic conditions in accordance with GOST 15150. 9.28.2 Values ​​of the rated currents of the ASU (rated operating currents of the input devices), as well as the values ​​of the rated operating currents of the protective devices of the distribution units and their quantity, which must be used during testing, are taken in accordance with the technical specifications for specific types of ASUs. Note - The values ​​of rated currents of ASUs and rated operating currents of protective devices of circuits, as well as their quantity used during testing, are established in the technical specifications for ASUs of specific types in accordance with Appendix B. 9.28.3 Rated current of ASUs of cabinet-type or single-panel ASUs, and also, panels of a multi-panel ASU with distribution units must be distributed between protective devices of distribution and group circuits in such a way that its rated operating current flows through each protective device involved in testing. Note - It is allowed to load one three-phase or three single-phase devices from among those used for testing with a current less than the rated operating current of the device in order to achieve equality of the total operating current of these devices to the rated current of the ASU or panel. 9.28.4 The temperature rise test is carried out with three-phase and/or single-phase current. The voltage of the test circuits is not standardized. Note - Test three-phase current is preferable, since in this case all elements of the internal circuits of the ASU can be simultaneously included in the test circuits. 9.28.5 When testing cabinet and single-panel ASUs with three-phase current, protective devices of distribution and group circuits, including group circuits of the lighting control unit, are connected to three-phase adjustable circuits, each of which is connected into an artificial star. In each phase of these circuits, a test current should be installed (and maintained during testing) equal to the rated operating current of the protective device with an error not exceeding ±5%, while the value of the test current in each phase of the input device should not have a deviation of more than ± 2% of the rated current of the ASU. 9.28.6 When testing cabinet-type ASUs and single-panel ASUs with single-phase current, protective devices and associated elements of internal circuits that are part of the distribution unit and lighting control unit are connected in series to the test circuits for the corresponding rated operating currents, and the poles of the input device of each ASU - in series into the test circuit for the rated current of the ASU. The input block fuses and busbars are included in the same circuit. Notes 1 If, when testing with single-phase current of the ASU, not all terminals (for example, on busbars) could be inserted into the test circuits, then their tests are carried out separately. 2 If the design of the terminals on the zero operating N and zero protective PE busbars is identical to the tested terminals on the phase busbars, then they may not be subjected to temperature rise tests. 9.28.7 Testing for temperature rise of multi-panel ASUs can be carried out separately for each panel or ASUs consisting of two or three panels, one of which is with an input unit, and the rest with distribution units, and the total operating current of the protective devices of the distribution units must correspond to the rated current of the ASUs , and at least one panel with a distribution unit must be loaded with its rated current. In the first case, tests can be carried out with both single-phase and three-phase current; in the second case, it is preferable to carry out tests with three-phase current. 9.28.8 When testing the input panel with single-phase current, the poles of the input device are connected in series into the circuit under test, which also includes fuses, sections of busbars located in the input panel, and flexible inter-panel jumpers designed to connect these sections with the busbars of panels with distribution units . Notes 1 If, when testing with single-phase current, not all terminals (for example, on busbars) of the ASU could be inserted into the test circuits, then their tests are carried out separately. 2 If the design of the terminals on the zero operating N and zero protective PE busbars is identical to the tested terminals on the phase busbars, then they may not be subjected to temperature rise tests. 9.28.9 If the input panels (diagrams No. 5-7, Appendix A) contain two input devices, then they and the elements of the internal circuits related to them are included in the test circuits one by one. 9.28.10 Single-phase current testing of multi-panel ASU panels with distribution units is similar to that described in 9.28.6. 9.28.11 Testing of multi-panel ASUs with three-phase current, panel by panel or as an assembly, should be carried out as described in 9.28.5. 9.28.12 To supply test current to the ASU or to the input panels in accordance with 9.28.8, the conductors of the test circuits are selected according to the rated current of the ASU. Conductors for performing test circuits, which include protective devices of distribution units and automatic switching units for public lighting, are selected according to the rated currents of the devices. 9.28.13 Testing for temperature rise of the protective bus PE according to 6.3.1 should be carried out together with the zero operating bus N with a jumper installed between them according to 6.3.15, for which the test conductors should be connected to the terminals available on them (for the corresponding conductors of the supply network) circuit and set a current in it equal to 50% of the rated current of the ASU. 9.28.14 The selection of cross-sections and lengths of copper conductors of test circuits is in accordance with GOST 22789, but not less than the cross-sections of conductors of internal circuits. The ends of the test circuit conductors must be thoroughly stripped and securely connected to the terminals of the devices and the corresponding terminals. 9.28.15 When conducting tests, temperature measurements must be carried out using thermocouples on the ASU elements specified in Table 5. The installation locations of thermocouples are in accordance with the technical specifications for specific types of ASU. These locations must be indicated in the test reports. Note - Temperature measurements of insulated conductors combined into bundles or laid in boxes must be performed on conductors with worse conditions cooling. This also applies to flexible interpanel bridges. 9.28.16 The duration of the temperature rise test is until a steady-state thermal regime is achieved, at which the temperature change is no more than 1 °C/h. 9.28.17 Temperature monitoring of ASU parts, as well as ambient air, must be carried out in accordance with GOST 22789. 9.28.18 ASU is considered to have passed the test if the temperature of their parts exceeds the established one upper value ambient air temperature is not more than the permissible values ​​​​according to 6.8.1. The insulation resistance of live parts measured at the end of the test must be at least 6 MΩ. 9.29 Testing the ASU for short-circuit current 9.29.1 Single- and multi-panel ASUs are subjected to tests for electrodynamic and thermal effects with a short-term withstand short-circuit current according to 6.8.2. 9.29.2 The test three-phase alternating current circuit includes: in single-panel ASUs - an input unit and busbars, in multi-panel ASUs - an input unit with its busbar, as well as busbars of one panel with a distribution unit. Note - If two input blocks with the same rated current are located in the input panel, then one of them may be tested. 9.29.3 When preparing to test the ASU for the effects of short-circuit current, it is necessary: ​​a) the busbars are securely connected at the ends opposite the power supply with short-circuiting jumpers with a cross-section equal or equivalent in conductivity to the cross-section of the busbars; b) turn off the protective devices of distribution and group circuits; c) short-circuit the secondary circuits of the current transformers; d) block the protective devices at the input to prevent them from triggering earlier than the time set in 6.8.2 when a short circuit current flows. Note - Circuit breakers can be bridged with jumpers, fuse links are replaced with current-carrying elements with low resistance. 9.29.4 For the test circuit, insulated conductors must be used, selected according to the rated current of the ASU. Conductors must be secured so that they can withstand the mechanical effects of short-circuit current flowing through them. 9.29.5 Before connecting the ASU to the test three-phase circuit , it must be calibrated according to the oscillogram in such a way that it achieves a short-circuit current, the average effective value of which in three phases must be equal to or close to the value according to Table 2 for the corresponding ASU, while at least in one of the phases the peak value is reached current (see table 2) with an error not exceeding ±5%. 9.29.6 The conductors of the test circuit must be connected to the input terminals of the input device. The current value in the test circuit with the ASU connected should be close to or equal to the value obtained during calibration of the test circuit. The current flow time in the test circuit is 0.2 s. 9.29.7 The impact of short circuit current on the elements of the ASU included in the test circuit must be one-time. 9.29.8 The test results are considered positive if there is no damage or destruction of the supporting insulating elements on which the busbars and other live parts are installed, or there is no deformation of the busbars and flexible jumpers that reduce the electrical strength of the insulation due to a possible reduction in air gaps and creepage distances. The input device must not have any damage that would prevent its further proper operation. The devices and devices that are part of the tested ASU or ASU panel, but which were not included in the test circuits, should also not be damaged. The heating temperature of busbars and other non-insulated current-carrying parts of the ASU included in the test circuit should not exceed 200 °C, taking into account the temperature they had before the test; conductors with polyvinyl chloride insulation - no more than 160 °C. 9.29.9 Tests of the ASU for the effects of short-circuit current can be carried out with a conditional short-circuit current according to 3.6.7, equal to the value of the rated short-term withstand current according to Table 2, while the circuit calibration and testing must be at a voltage equal to 1.05 of the rated operating voltage voltage. The duration of the short circuit current is until the input protective device is triggered. The procedure for calibrating the test circuit and conducting the test is in accordance with GOST 22789. 9.29.10 To check the resistance of the zero operating busbars N of single- and multi-panel ASUs to the electrodynamic and thermal effects of short-circuit currents, the corresponding current should be passed through them once, the value and time of exposure of which tires are specified in 6.8.2. 9.29.11 To carry out tests according to 9.29.10, the zero operating bus N should be short-circuited with the nearest phase bus. The short-circuiting jumper must have a cross-section equal to the cross-section of the zero operating busbar. The conductors of a single-phase test circuit must be connected: one to the phase bus (after the protective device), the second to the zero bus N, using a clamp for connecting the zero working conductor of the supply network. The cross-section of the conductors of the test circuit must be equal to the cross-section of the zero operating bus N or equivalent to it in conductivity. 9.29.12 Zero running tire N is considered to have passed the test according to 9.29.10 if it has not undergone deformation with the consequences set out in 9.29.8, and its heating temperature does not exceed the value specified in 9.29.8. 9.29.13 To check the reliability of electrical connections between the open conductive parts of single- and multi-panel ASUs and the PE zero protective bus according to 6.7.2, these parts and the protective bus should be included in a single-phase test circuit and a short-circuit current should be passed once, the value and duration of which specified in 6.8.2. 9.29.14 Before testing according to 9.29.13, the ASU or panel must be isolated from the floor and third-party conductive parts. The conductors of the test circuit are connected: one to the terminal for the protective PE or PEN conductor of the power supply network, and the second to the shell of a single-panel ASU or panel of a multi-panel ASU at the most distant point from the said terminal. The cross-section of the conductors of the test circuit must be equal or equivalent to the cross-section of the PE zero protective busbar. 9.29.15 The electrical connections of the ASU parts with each other and with the PE protective bus are considered reliable if, after testing for short-circuit current in accordance with 9.29.13, the electrical resistance measured between the connection points of the test circuit conductors does not exceed 0.1 Ohm. 9.30 Measurement of air gaps and creepage distances according to 6.8.3 should be carried out with measuring instruments installed in the technical specifications for specific types of ASUs. 9.31 Testing the electrical strength of the insulation of internal circuits according to 6.8.4 and shells made of insulating material according to 6.8.5 should be carried out in accordance with GOST 22789. Tests of multi-panel ASUs are carried out panel by panel. When testing ASUs of all types, the meter should be turned off and the jumper removed according to 6.3.15. Evaluation of results - in accordance with GOST 22789. 9.32 Insulation resistance measurements according to 6.8.6 are carried out: between current-carrying parts of different phases, between phases and the neutral working conductor (with the jumper removed according to 6.3.15), as well as between them and the PE protective bus. Measurements must be carried out with a megohmmeter for a voltage of at least 1000 V. Measurements are carried out with the counters turned off. 9.33 Inspection of paint and varnish and powder polymer coatings according to 6.9.2 and 6.9.3 (appearance, coating thickness) should be carried out in accordance with GOST 9.032 and GOST 9.410, respectively. The adhesion strength of coatings is in accordance with GOST 15140. 9.34 Inspection of metal coatings according to 6.9.4 should be carried out in accordance with GOST 9.302. 9.35 The reliability test according to 6.10 is carried out in accordance with the technical specifications for specific types of ASUs. 9.36 Checking the marking of the ASU according to 6.11 is carried out by comparing it with technical documentation. 9.37 Control of the operational document according to 6.12.1 should be carried out for compliance with GOST 2.601 and for completeness of its completion according to 6.12.2 in relation to the ASU of the corresponding type. 9.38 The completeness check according to 6.13, 6.7.6 is carried out for compliance with the requirements of technical specifications for specific types of ASUs. 9.39 The preservation and packaging of the ASU according to 6.14 is checked visually. 9.40 The probability of a fire occurring in (from) the ASU is determined in accordance with the methodology given in GOST 12.1.004 (Appendix 5).

10 Transportation and storage

10.1 The conditions for transportation of the ASU in terms of the influence of climatic environmental factors are similar to storage conditions 5 according to GOST 15150, in terms of the influence of mechanical factors during transportation - group C in accordance with GOST 23216. 10.2 The storage conditions for the ASU in terms of the influence of climatic environmental factors - 2 according to GOST 15150 The permissible shelf life before commissioning is no more than two years. 10.3 Transportation and storage of ASUs supplied for export must comply with the requirements of the contract.

11 Operating instructions

11.1 The operation of the ASU must be carried out in accordance with the manufacturer’s operational documentation, as well as the “Rules for the operation of consumer electrical installations” and “Safety rules for the operation of consumer electrical installations”, approved by Glavgosenergonadzor. 11.2 When operating the ASU, hand tools must be used in accordance with GOST 11516.

12 Manufacturer's warranty

12.1 The manufacturer guarantees compliance of the ASU with the requirements of this standard if the consumer complies with the conditions of transportation, storage, installation and operation. 12.2 The warranty period is two years from the date of commissioning of the ASU.

APPENDIX A

(required)

Schematic diagrams of inputs to the ASU

L - phase conductors; N - zero working conductor; PE - neutral protective conductor; PEN - combined neutral working and protective conductor; P - jumper according to 6.3.15

Note - Application of diagrams for the corresponding type of ASU - according to Table 1.

APPENDIX B

Approximate layout of equipment in the ASU

1 - shell (panel body); 2 - input block; 3 - clamps for connecting supply network conductors with the grounding type of the TN - C system (with a jumper installed 18 in the position indicated in Figures B.1a and B.1b); 4 - clamps for connecting supply network conductors with the TN - S or TN - C - S system grounding type (jumper 18 between the PE and N buses is not installed, see Figure B.1c); 5 - input device; 6 - terminals of the input device; 7 - intermediate current-carrying elements according to 6.4.6, having additional terminals for connection to the input panel (Figure B.1a or Figure B.1b) of the input panel with ATS (Figure B.1c) and/or implementation of the switching circuit (Figure B.1b) , as well as for connecting supply network conductors in accordance with Appendix A (see diagrams 3, 4, 6, 7, 8); 8 - metering unit compartment; 9 - devices and instruments of the metering unit; 10 - wall of the metering unit compartment; 10" - partition between devices of the AVR unit; 11 - internal circuits (including busbars related to the input unit); 12 - jumper (interpanel) for connecting the phase conductors of the input panel with the distribution panel; 13, 14 - prefabricated zero operating N and zero protective PE busbars with terminals for connecting the corresponding conductors of distribution and group circuits; 15, 16 - interpanel jumpers for connecting, respectively, prefabricated zero operating N and zero protective PE busbars of ASU panels; 17 - clamp for connecting the potential equalization conductor; 18 - jumper; 19 - clamp for connecting the protective conductor from the main grounding bus of the electrical installation according to 6.4.3 a; 20 - clamp for connecting the grounding conductor according to 6.4.3 b (when using a prefabricated zero protective busbar as the main grounding busbar of an electrical installation); 21 - clamp for connecting the conductor of the surge suppressor (arrestor) 6.4.3 g; 22 - clamps intended according to item 7; 23 - clamps for connecting equipment of the ATS unit; 24 - equipment of the ATS unit.

Figure B.1 - Equipment layout diagrams in input panels of multi-panel ASUs: a) with one input; b) with two inputs; c) with two mutually redundant inputs with ATS equipment

1 - terminals of protective devices of panels (distribution unit) for connecting distribution circuits; 2 - protective device, 3 - device outputs; 4- connecting elements for connecting the terminals of protective devices according to 6.3.4; 4- busbars (phase); 5 - manadgement Department; 6 - jumper for connecting the control device or busbars to the input panel; 7, 8 - busbars - zero operating N and zero protective PE with clamps for connecting the corresponding conductors of distribution and group circuits; 9, 10 - interpanel jumpers for connecting, respectively, prefabricated zero operating N and zero protective PE busbars of ASU panels; 11 - clamp for connecting the potential equation conductor according to 6.4.3 V; 12 - shell (body) of the panel; 13 - metering unit devices; 14 - partitions between distribution blocks powered from two inputs; 15 - lighting control unit; 16 - lighting control unit equipment

Figure B.2 - Equipment layout diagrams in distribution panels of multi-panel ASUs:

a) with a distribution unit powered from one input; b) with distribution and metering units powered from one input; c) with distribution units powered from two inputs; d) with distribution, metering and control units for general house lighting, powered from two inputs

1 - input block; 2 - clamps for connecting supply network conductors with the grounding type of the TN - C system (with a jumper installed 24 in position according to Figure B.3); 2 - clamp for connecting the neutral working conductor N of the supply network with the grounding type of the TN - S or TN - C - S system (with the jumper removed 24); 3 - input device; 4 - internal circuit conductors; 5 - partition between input and distribution blocks; 6 - metering unit devices; 7 - metering unit compartment; 8 - connecting jumper; 9 - phase busbars; 10 - devices of the lighting control unit; 11 - lighting control unit; 12-14 - terminals for connecting the group circuit; 15 - protective devices of the distribution unit; 16 - distribution block; 17-19 - terminals for connecting the distribution circuit; 20 - clamp for connecting the potential equalization conductor according to 6.4.3 V; 21 - prefabricated zero operating bus N; 22 - 23 - clamp for connecting the protective conductor from the main grounding bus of the electrical installation according to 6.4.3 a; 24 - jumper; 25 - clamp for connecting the grounding conductor according to 6.4.3 b (when using a prefabricated zero protective busbar as the main grounding busbar of an electrical installation); 26 - clamp for connecting a surge suppressor (arrestor) 6.4.3 g; 27 - shell (housing) of class I ASU

Figure B.3 - Layout of equipment in a single-panel ASU

1 - input block; 2 - clamps for connecting power supply conductors with grounding type TN-C systems(with jumper installed 20 in position according to Figure B.4a); 2" - clamp for connecting the neutral working conductor N of the supply network with the grounding type of the TN-C-S system with the jumper removed 20; 3 - input device; 4, 8 - internal circuit conductors; 5 - 6 - input and accounting blocks; 7 - metering unit devices; 9 - distribution block; 10 - protective device of a single-phase group circuit; 11 - 12-14 - terminals for connecting single-phase group circuits; 15-17 - terminals for connecting distribution circuits; 18 - prefabricated zero operating bus N; 19 - prefabricated zero protective busbar PE; 20 - jumper; 21 - clamp for connecting the potential equalization conductor; 22 - 23 - 24 - Class II ASU shell

Figure B.4a - Layout of equipment in a class II cabinet ASU (with an insulating shell)

1 - input block; 2 - clamps for connecting the power supply network with the grounding type of the TN - C system (with a jumper installed 18 according to Figure B.4b); 2" - clamp for connecting the neutral working conductor N of the supply network with the grounding type of the TN - S or TN - C - S system with the jumper removed 18; 3 - input device; 4 - partition between input and distribution blocks; 5 - accounting unit; 6 - metering unit devices; 7 - internal circuit conductors; 8 - distribution block; 9 - protective device of a single-phase group circuit; 10 - terminals of protective devices 9; 11 - distribution circuit protective apparatus; 12 - terminals of protective devices 10, 13 - conductors of internal circuits connecting the terminals of devices 9 and 11 with intermediate clamps 14; 14 - intermediate clamps according to 6.4.5 for connecting phase conductors of distribution and group circuits; 15, 16 - prefabricated zero N and prefabricated zero protective PE busbars with clamps for connecting the corresponding conductors of distribution and group circuits; 17 - clamp for potential equalization conductor; 18 - jumper; 19 - clamp for connecting the grounding conductor according to 6.4.3 b (when using a prefabricated zero protective PE busbar as the main grounding busbar of an electrical installation); 20 - clamp for connecting a surge suppressor (arrestor) 6.4.3 g; 21 - shell (housing) of class I ASU

Figure B.4b - Layout of equipment in a cabinet ASU of class I (with a conductive shell)

APPENDIX B

Determination of rated currents of ASUs and rated operating currents of devices built into them

B.1 Due to insufficiently effective heat removal from devices and current-carrying parts located in the shells of the ASU, the rated operating currents according to 6.3.2 of the built-in devices must be established by calculation and experiment of such values ​​that exclude the possibility of operation of protective devices not related to with emergency mode, and the heating (temperature rise) of the ASU parts does not exceed the permissible values ​​given in 6.8.1 of this standard. B.2 The rated operating currents of ASU input devices and the rated operating currents of protective devices of distribution and group circuits should be determined at the stage of development of specific types of ASUs. B.3 The rated current of the ASU is the rated operating current of its input device. Notes 1 If the input block includes two input devices connected to mutually redundant lines (diagram No. 7 with ATS, Appendix A), then the rated current of the ASU corresponds to the rated operating current of one device. 2 If the input unit includes two input devices with the same rated current, intended for continuous operation with a load of each significantly lower than the rated operating current of the device (Scheme 6, Appendix A), and in certain (also long) periods any of which can be loaded at the rated operating current with the second one disconnected, then the rated current of the ASU corresponds to the rated operating current of one device. 3 For multi-panel ASUs, rated currents should be determined both for input panels (rated currents of ASUs) and for panels containing distribution units in accordance with B.10. B.4 Determination of rated operating currents of input devices (rated currents of ASU) and rated operating currents of protective devices extending from ASU circuits should be carried out experimentally based on pre-established calculations (during the development of ASU) values ​​of rated currents of devices, accepted according to Table 2 of this standard . B.5 In cabinet and single-panel ASUs, to experimentally determine the rated operating currents of input devices, as well as protective devices of outgoing distribution and group circuits, the rated current of the input device (determined by calculation) should be distributed among the minimum possible number of these devices included in the distribution block, such in such a way that a current flows through each of them equal to its rated current multiplied by the simultaneity factor selected according to Table B.1 for cabinet ASU (mainly single-phase loads) and according to Table B. 2 for single-panel ASUs (mainly three-phase loads), depending on the number of outgoing circuit devices used for testing. If the rated current of the input device cannot be reached by the load of the number of protective devices accepted for testing, then one three-phase or three single-phase devices can be loaded with a lower current. When testing the temperature rise of the terminals of input devices, protection devices of outgoing circuits, conductors of internal circuits and parts of the ASU should not exceed the values ​​​​established in 6.8.1. Table B.1 Table B.2 B.6 If the distribution of the rated current of the input device (cabinet or single-panel ASU) adopted in B.5 among the protective devices of the outgoing circuits leads to higher values ​​of temperature rise of the protective devices, as well as the input device and other parts ASU against the permissible values ​​​​according to 6.8.1, then the rated currents of the input and protective devices must be reduced to values ​​at which the temperature rise of the specified ASU elements satisfies the requirements of 6.8.1. These values ​​are taken as the rated operating currents of the devices. If the temperature rise of the input device at its rated current does not exceed the permissible value according to 6.8.1, and the protective devices of the outgoing circuits connected to it have temperature rises above the permissible values, then the currents of the protective devices must be reduced by redistributing the rated current of the input device to a larger number of protective devices, provided that the reduced current values ​​are not less than those required by the consumer. If it is impossible to reduce the rated operating currents, then it is necessary either to select protective devices (and, if necessary, an input device) for higher rated currents, or to change the cooling conditions so that the values ​​of temperature rises are introduced into the established standards. B.7 If a single-panel ASU, along with a distribution unit according to 3.1.6, includes a control unit for general house lighting according to 3.1.7, then for each unit the rated operating current must be separately determined according to B.8, while the rated operating current of the ASU input device will be equal to their sum. Note - In cabinet-mounted ASUs, the rated operating current of the general house lighting control unit (if provided) is not determined separately due to the limited number of protective devices included in it, which should be taken into account in the distribution unit when conducting tests according to B.5, B.6. B.8 Rated operating current of each unit in V. 7 can be pre-determined by the sum of the rated currents of the protective devices included in it, multiplied by the simultaneity factor selected from Table B.1 for the lighting control unit and from Table B.2 for the distribution block. B.9 In multi-panel ASUs, the rated currents must be determined separately for each panel. The rated currents of panels with distribution units, including lighting control units, must not exceed the rated currents of the corresponding input panels. B.10 Determination of the rated current of the input panel with a given rated current of the input device comes down to the experimental determination of its rated operating current (see B.3) from the condition of the permissible temperature rise of the device and other parts of the panel in accordance with 6.8.1 of this standard. B.11 The rated currents of distribution panels of multi-panel ASUs with two distribution units or with a distribution unit and a control unit for general house lighting, as well as the rated operating currents of the protective devices included in them are determined similarly to B.7 and B.8. Note - If the distribution panel contains units powered from various inputs (see diagram 6 of Appendix A), then for each supply circuit its rated operating current is determined, while the rated current of the panel is not determined. B.12 If a control device is provided in the panel in front of the distribution unit and/or in front of the lighting control unit, then it must be selected according to the rated operating current of the corresponding unit, determined according to B.8, followed by checking it for temperature rise according to B.5 while simultaneously loading both blocks. B.13 Methodology for testing ASUs for temperature rise related to the determination of rated currents of ASUs and rated operating currents of protective devices - in accordance with 9.28 of this standard. B.14 The obtained values ​​of rated currents of single-panel and cabinet ASUs and panels of multi-panel ASUs (based on the permissible temperature rise according to 6.8.1) must be correlated with an ambient temperature of 35 °C, taking into account which the heating of the current-carrying parts of the ASU should not exceed the values ​​​​according to 6.8. 1 . Note - It is also recommended to determine the values ​​of the rated currents of the ASU in relation to an ambient temperature of 25 °C and provide them in operational documents and information materials. B.15 Based on the test results for single-panel and cabinet ASUs, as well as for the incoming panels of multi-panel ASUs, their type representatives for subsequent periodic tests for temperature rise should also be determined. Test results of type representatives according to established criteria can be extended to other versions of ASUs or panels of multi-panel ASUs included in the same standard size range as the standard representative of the corresponding type of ASU. For the same purpose, type representatives of multi-panel ASU panels should be determined, containing distribution units with protection devices of predominantly the same type. For example, representative panels with fuses and circuit breakers. Note - Type representatives of ASU or ASU panels are characterized by highest values heating temperatures of their parts, but not exceeding the permissible values ​​​​according to 6.8.1. B.16 Type representatives of single-panel and cabinet ASUs or panels of multi-panel ASUs must be indicated in the technical specifications for specific types of ASUs, and for each type representative the devices loaded with their rated operating currents when tested for temperature rise according to 6.8.1 of this standard must be indicated.

APPENDIX D

Designations of ASU types

D.1 Designations of types of ASUs of all types (multi-panel, single-panel and cabinet) are recommended to be formed according to the structure given in D.4. D.2 The first digit in the structure of the ASU type indicates the design development of the corresponding type of ASU. To digitally designate the design developments of multi-panel ASUs, a series of numbers from 1 to 10 can be used. To designate the developments of single-panel and cabinet ASUs, one and two zeros should be placed in front of each digit of this series, respectively. The digital designation of the ASU development can be supplemented by the letter designation of the ASU manufacturer. D.3 The third digit in the type structure (after the rated current) indicates the modification of the ASU. Numerical designations are assigned to modifications of ASUs that differ in classification (Table 1) and other characteristics, as well as parameters given in Table 2. To number modifications of input and distribution panels of multi-panel ASUs, a series of three-digit numbers can be used, respectively, from 100 to 199 and from 200 to 299 , and for numbering modifications of single-panel and cabinet ASUs - respectively, series of numbers from 300 to 399 and from 400 to 499. Notes 1 Modifications of each type of ASU are their various designs (in multi-panel ASUs - panels), developed on a single structural basic basis corresponding to the type ASU, which can be characterized by overall dimensions, degree of protection according to GOST 14254, method of protection against electric shock (classes I and II according to GOST R IEC 536), the highest possible meaning rated current, etc. 2 Characteristics of ASU modifications (multi-panel ASU panels) are given in the technical specifications for specific types of ASU, as well as in operational documents and information materials. D.4 Designation structure for ASU types (multi-panel ASU panels).

Examples of designations for the types of panels of a multi-panel ASU Input panel ASU, 4th design, manufacturer N, for a rated current of 360 A, digital designation 102, Climatic performance UHL4:

VRU-4N-360-102 UHL4

Distribution panel ASU, 4th design, manufacturer N, rated current 200 A, digital designation 210, climatic version UHL4:

VRU-4N-200-210 UHL4

Note - If the distribution panel is powered from two inputs (see paragraph B.11 of Appendix B), then their rated currents should be indicated as a sum, for example VRU-4N-(120+80) UHL4. An example of a type designation for a single-panel ASU ASU of the 02nd design, manufacturer N, for a rated current of 200 A, digital designation 301, climatic version UHL4:

VRU-02N-200-301 UHL4

An example of designation of the type of ASU cabinet version ASU 003 design, manufacturer C, rated current 100 A, digital designation 405, climatic version UHL4:

VRU-003-100-405 UHL4

Key words: input and distribution devices for residential and public buildings, general technical conditions

For connecting internal electrical networks of electrical installations to external power supplies cable lines, as well as for the distribution of electrical energy and protection against overloads and short circuits of outgoing lines. input (VU) or input-distribution devices (IDU).

The input device is also intended to delineate responsibility for the operation of electrical networks between city network personnel and consumer personnel. Behind the input device Electricity of the net are under the control of the consumer. When powering small-power electrical installations belonging to the 3rd category of uninterruptible power supply via one cable, three-pole BPV type input boxes are used as input devices for currents of 100, 250, 350 A with one block of “PN-2 fuses and a circuit breaker. Also used are Y3700 boxes with one three-pole automatic switch of the A3700 series for currents of 50 - 600 A. For three- and five-story residential buildings, ShV series cabinets are used as input devices.

Input and distribution devices for public buildings

For public buildings, high-rise residential buildings and small enterprises, ASU input and distribution devices are used, made in the form of one-way or two-way service panels. Any input-distribution device is completed from input and distribution panels, or factory-made cabinets. In large cities, electrical installation companies develop and use their own design series of ASUs.

Introductory panels are manufactured the following types: VR, VP, VA. The input panel equipment is designed for rated currents of 250, 400 and 630 A.

On the VR-250 input panels for currents of 250 A, PN-2-250 fuses, a switch R or a switch switch of the RP series are installed. On the input panels VP-400 and VP-630, switches-switches of the RB series and fuses PN-2-400, switch-switches of the series RB and fuses PN-2-630 are installed, respectively. VA panels are installed circuit breaker A3726 series for a rated current of 25 A.

Distribution panels are manufactured in the following types: distribution panels with automatic switches on outgoing lines, distribution panels with automatic control of staircase and corridor lighting, distribution panels with metering department. The distribution panels are equipped with automatic circuit breakers of the A37, AE20, AE1000 and AP50B series, magnetic starters of the PML series, intermediate relays RPL and package switches PV, PP.

When assembling the ASU, the input and distribution panels of one input are located side by side. ASU panels are manufactured by the manufacturer as separate panels with built-in devices and instruments, as well as connecting conductors between the panels.

The figure shows circuit diagram one of the input panels with a switch for one input.

Thanks to the large variety of input and distribution panel circuits VRU-UVR-8503, any ASU can be configured according to the given electrical circuits for powering the internal networks of buildings.

Scheme of the input panel with a switch at the input: 1 - measuring instruments, 2 - current transformers, 3 - electricity meter, 4 - anti-interference capacitors, 5 - fuse, b - switch, 7 - cable input, 8 - circuit breaker, 9 - incandescent lamp

At large enterprises that consume significant power, input and distribution cabinets and factory-made panels of the ShchO-70 series are used as input and distribution devices. They are also used at substations in distribution devices 0.4 kV. Structurally, they can be single-sided or double-sided. Switches with fuses or automatic circuit breakers of the AVM series are installed on the input panels, and switches with fuses or automatic circuit breakers of the A37 series are installed on the distribution panels.

Panel panels for one-way maintenance are installed directly against the wall of the electrical room. They are served with front side. Panels of double-sided service panels are called free-standing or free-standing and are located at a distance of at least 0.8 m from the wall.

Single-sided service panels require less area for installation and maintenance than double-sided service panels. In addition, they are more economical. However, double-sided service panels are more convenient to use.

In addition to panel-type switchboards, factories produce input-distribution and distribution switchboards assembled from separate blocks: fuse, circuit breaker, fuse-switch, circuit breaker, meter.

The premises of input and distribution devices (electrical switchboards) are located in convenient places, where only service staff. Gas pipelines should not pass through electrical switchboards, and other pipelines should be without connections, valves, or gate valves. It is allowed to install ASU not in special premises, but on stairwells, in corridors, etc., but the cabinets must be locked, the handles of the control devices must not be brought out or be removable. It is not allowed to install ASU in damp rooms and in places prone to flooding.