home · measurements · A course of lectures on the discipline “Technical means of automation and. Classification of automation equipment "Omsk State Technical University"

A course of lectures on the discipline “Technical means of automation and. Classification of automation equipment "Omsk State Technical University"

Management, consulting and entrepreneurship

Lecture 2. General information about technical means of automation. The need to study general issues related to technical automation equipment and state system industrial devices and automation equipment GSP is dictated by the fact that technical means

Lecture 2.

General information about technical means of automation.

The need to study general issues relating to technical automation equipment and the state system of industrial instruments and automation equipment (GSP) is dictated by the fact that technical automation equipment is an integral part of the GSP. Technical automation equipment represents the basis for the implementation of information and control systems in the industrial and non-industrial spheres of production. The principles of organizing the GSP largely determine the content of the design stage of technical support for automated process control systems (APCS). In turn, the basis of GSPs are problem-oriented aggregate complexes of technical means.

Typical automation tools can be technical, hardware, software and system-wide.

TO technical means of automation(TSA) include:

  • sensors;
  • actuators;
  • regulatory authorities (RO);
  • communication lines;
  • secondary instruments (displaying and recording);
  • analog and digital control devices;
  • programming blocks;
  • logic-command control devices;
  • modules for collecting and primary processing of data and monitoring the state of a technological control object (TOU);
  • modules for galvanic isolation and signal normalization;
  • signal converters from one form to another;
  • modules for data presentation, indication, recording and generation of control signals;
  • buffer storage devices;
  • programmable timers;
  • specialized computing devices, pre-processor preparation devices.

TO software and hardware automation tools include:

  • analog-to-digital and digital-to-analog converters;
  • control means;
  • multi-circuit analog and analog-to-digital control blocks;
  • multi-connection program logic control devices;
  • programmable microcontrollers;
  • local area networks.

TO system-wide automation tools include:

  • interface devices and communication adapters;
  • shared memory blocks;
  • highways (buses);
  • general system diagnostic devices;
  • direct access processors for storing information;
  • operator consoles.

Technical means of automation in control systems

Any system control must perform the following functions:

  • collecting information about current state technological control object (TOU);
  • determination of quality criteria for TOU work;
  • finding the optimal mode of operation of the TOU and optimal control actions that ensure the extremum of quality criteria;
  • implementation of the found optimal mode at the TOU.

These functions can be performed service personnel or TCA. There are fourtype of control systems(SU):

1) informational;

2) automatic control;

3) centralized control and regulation;

4) automated process control systems.

Information ( manual) control systems(Fig. 1.1) are rarely used, only for reliably functioning, simple technological objects of TOU control.

Rice. 1.1. Structure information system controls:

D - sensor (primary measuring transducer);

VP - secondary indicating device;

OPU - operator control center (boards, consoles, mnemonic diagrams, alarm devices);

Remote control remote control devices (buttons, keys, bypass control panels, etc.);

IM actuator;

RO - regulatory body;

C - alarm devices;

MS mnemonic diagrams.

In some cases, the information management system includes regulators direct action and built into technological equipment regulators.

In automatic control systems(Fig. 1.2) all functions are performed automatically using appropriate technical means.

Operator functions include:

  • technical diagnostics of the ACS condition and restoration of failed system elements;
  • correction of regulatory laws;
  • change of task;
  • transition to manual control;
  • equipment maintenance.

Rice. 1.2. Structure of the automatic control system (ACS):

KP - encoding converter;

LS - communication lines (wires, impulse tubes);

VU - computing devices

Centralized control and regulation systems(SCCR) (Fig. 1.3). ACS are used for simple technical equipment, the operating modes of which are characterized by a small number of coordinates, and the quality of work is characterized by one easily calculated criterion. A special case of ACS is the automatic control system (ASR).

A control system that automatically maintains an extreme TOC value belongs to the class of extreme control systems.

Rice. 1.3. Structure of the centralized control and regulation system:

OPU - operator control center;

D - sensor;

NP normalizing converter;

KP - encoding and decoding converters;

CR - central regulators;

MP multi-channel registration tool (print);

C - pre-emergency signaling device;

MPP - multi-channel indicating devices (displays);

MS - mnemonic diagram;

IM - actuator;

RO - regulatory body;

K controller

ASRs that support the specified value of the output adjustable coordinate of the TOU are divided into:

  • stabilizing;
  • software;
  • followers;
  • adaptive.

Extreme regulators are used extremely rarely.

Technical structures of the SCCR can be of two types:

1) with individual TCAs;

2) with collective TCAs.

In the first type of system, each channel is constructed from TCA individual use. These include sensors, normalizing converters, regulators, secondary devices, actuators, and regulatory bodies.

Failure of one control channel does not lead to a shutdown of the process facility.

This design increases the cost of the system, but increases its reliability.

The second type system consists of TSA for individual and collective use. TSA for collective use includes: switch, CP (encoding and decoding converters), CR (central regulators), MR (multi-channel recording device (print)), MPP (multi-channel indicating devices (displays)).

The cost of a collective system is somewhat lower, but reliability largely depends on the reliability of collective TSAs.

When the communication line is long, individual encoding and decoding converters are used, located near the sensors and actuators. This increases the cost of the system, but improves the noise immunity of the communication line.

Automated process control systems(APCS) (Fig. 1.4) is a machine system in which TSA obtain information about the state of objects, calculate quality criteria, and find optimal control settings. The operator’s functions are reduced to analyzing the received information and implementing it using local automated control systems or remote control of the control room.

Distinguish following types APCS:

  • centralized automated process control system (all information processing and control functions are performed by one control computer UVM) (Fig. 1.4);

Rice. 1.4. Structure of a centralized automated process control system:

USO - communication device with the object;

DU - remote control;

SOI - information display tool

  • supervisory automated process control system (has a number of local automated control systems built on the basis of individual use TSA and a central computer computer (CUVM), which has an information communication line with local systems) (Fig. 1.5);

Rice. 1.5. Structure of the supervisory control system: LR - local regulators

  • distributed automated process control system - characterized by the division of information processing and management control functions between several geographically distributed objects and computers (Fig. 1.6).

Rice. 1.6. Hierarchical structure of technical means of SHG

Page 7


As well as other works that may interest you

7111. Organization and management of the fleet and ports 155 KB
Organization and management of the fleet and ports Lecture notes Enterprise management structure, planning principles Any enterprise, including a transport enterprise, includes three relatively independent, but interconnected common goals...
7112. FINANCIAL ACCOUNTING PRACTICUM 449.5 KB
General information about the organization The cross-cutting task considers the activities of a small enterprise - limited liability company Furniture. The company has one main production workshop, which produces upholstered furniture (sofas). TIN...
7113. Accounting from scratch 3.6 MB
Andrey Vitalievich Kryukov Accounting from scratch Abstract The profession of an accountant has been and remains quite popular today. Everyone knows that every company must have at least one accountant. You also decided to become an accountant, but, for the first time...
7114. Manual for the PTO engineer on as-built documentation 2.08 MB
Manual for VET engineer executive documentation(Young Stationery Rat's Manual on Site version 6.0) Page reserved for typographical output. The published materials are the property of guest workers, for what reason...
7115. Sounds of initial practice in the village. Lyubomirka 5.36 MB
Sounds from initial practice in the village. Lyubomirka 1. Systems and methods of tractor maintenance. Preparing tractors for operation. The tractor steering system includes the following subsystems: engine control: tension regulation, hour...
7116. Basic methods for assessing the economic efficiency of investments in transport 77.5 KB
Basic methods for assessing the economic efficiency of investments in transport. Contents Introduction 3 Investments in transport 4 Features of investment assessment methods 6 Conclusion 11 References 12 Introduction. Transport is one of...
7117. Study of the traction capacity of a traction pulley 568.5 KB
Research on the traction capacity of a traction pulley Introduction Guidelines compiled in accordance with the course program Lifts for students of specialty 170900 (PSM). The Lifts course is one of the final ones in the preparation...
7118. Transport complex of the country, concept and general characteristics 134.5 KB
Topic 1. Transport complex of the country, concept and general characteristics. 1.1. Subject of economics of road transport. Social production, i.e. the unity of productive forces and production relations is studied from two sides. Natural...
7119. Fixed assets in road transport and road infrastructure 159 KB
Topic 2. Fixed assets for road transport and in road construction. 2.1. Concepts about fixed assets. The main factor in the process of production of material goods is labor and means of production. The means of production are divided...

Technical automation equipment

instruments, devices and technical systems intended for production automation (See Production automation). T.s. A. provide automatic receipt, transmission, transformation, comparison and use of information for control and management purposes production processes. In the USSR, a systematic approach to the construction and use of technical systems. A. (their grouping and unification according to functional, informational, and design-technological characteristics) made it possible to unite all technical systems. A. within the framework of the State System of Industrial Instruments and Automation Equipment - GSP.


Great Soviet Encyclopedia. - M.: Soviet Encyclopedia. 1969-1978 .

See what "Technical means of automation" is in other dictionaries:

    TECHNICAL MEANS (AUTOMATED)- 13. TECHNICAL EQUIPMENT (AUTOMATION) automation equipment, which is not used software. Source: RB 004 98: Requirements for certification of control systems important for the safety of nuclear power plants...

    technical means of automation- instruments, devices and technical systems for automated production, providing automatic receipt, transmission, transformation, comparison and information for the purpose of monitoring and managing production... ... Encyclopedic Dictionary of Metallurgy

    Technical means of automation of I&C, technical support of I&C- 7 Technical means of automation of the I&C system, technical support of the I&C system The set of all components of the I&C system, with the exception of people (GOST 34.003 90). The totality of all technical means used in the operation of I&C systems (GOST 34.003 90) Source ... Dictionary-reference book of terms of normative and technical documentation

    SOFTWARE AND HARDWARE TOOLS FOR AUTOMATION- 7. SOFTWARE AND HARDWARE AUTOMATION TOOLS a set of software and hardware automation tools designed to create control software and hardware systems. Source: RB 004 98: Requirements for certification of managers ... ... Dictionary-reference book of terms of normative and technical documentation

    Technical means- 3.2 Technical means of automation systems, a set of technical means (CTS) a set of devices (products) that provide receiving, input, preparation, conversion, processing, storage, registration, output, display, use and... ... Dictionary-reference book of terms of normative and technical documentation

    Means of technical automation systems- 4.8 Source: RM 4 239 91: Automation systems. Dictionary reference on terms. Manual for SNiP 3.05.07 85 ... Dictionary-reference book of terms of normative and technical documentation

    Technical means of process control systems- Automated process control systems, including products of the state system of industrial instruments and automation equipment (GSP), aggregate measuring instruments (AS IMS), computer equipment (SVT) Source: RD 34.35.414 91: Rules of the organization ... ... Dictionary-reference book of terms of normative and technical documentation

    AUTOMATION SYSTEMS TECHNICAL EQUIPMENT- 4.8. TECHNICAL TOOLS OF AUTOMATION SYSTEMS Hardware hardware A set of tools that ensures the functioning of automated systems of various types and levels: devices, functional blocks, regulators, actuators, aggregate complexes,... ... Dictionary-reference book of terms of normative and technical documentation

    GOST 13033-84: GSP. Devices and means of automation electric analog. General technical conditions- Terminology GOST 13033 84: GSP. Electrical analog instruments and automation equipment. Are common specifications original document: 2.10. Power requirements 2.10.1. The products must be powered from one of the following sources: ... ... Dictionary-reference book of terms of normative and technical documentation

    Technical- 19. Technical instructions on the production technology of construction and installation work during electrification railways(power supply devices). M.: Orgtransstroy, 1966. Source: VSN 13 77: Instructions for installing contact networks of industrial ... Dictionary-reference book of terms of normative and technical documentation

Books

  • Technical means of automation and control Textbook, Kolosov O., Yesyutkin A., Prokofiev N. (eds.). The textbook, to varying degrees (without pretending to cover the “immense”), reinforces and complements the materials presented in accordance with the work programs of a complex of disciplines of the professional cycle...
  • Technical means of automation. Textbook for academic bachelor's degree, Rachkov M.Yu.. The textbook discusses the classification of technical automation equipment, methods for selecting technical equipment by type of production, as well as equipment control systems. A description is provided...

Theme 2

1. Sensors

A sensor is a device that converts the input effect of any physical quantity into a signal convenient for further use.

The sensors used are quite varied and can be classified according to various signs(see table 1).

Depending on the type of input (measured) quantity, there are: mechanical displacement sensors (linear and angular), pneumatic, electrical, flow meters, speed, acceleration, force, temperature, pressure sensors, etc.

Based on the type of output value into which the input value is converted, non-electrical and electrical are distinguished: direct current sensors (emf or voltage), alternating current amplitude sensors (emf or voltage), alternating current frequency sensors (emf or voltage), resistance sensors (active, inductive or capacitive) etc.

Most sensors are electrical. This is due to the following advantages of electrical measurements:

Electrical quantities convenient to transmit over a distance, and the transmission is carried out with high speed;

Electrical quantities are universal in the sense that any other quantities can be converted into electrical quantities and vice versa;

They are accurately converted into a digital code and allow you to achieve high accuracy, sensitivity and speed of measurement instruments.

Based on their operating principle, sensors can be divided into two classes: generator and parametric. A separate group consists of radioactive sensors. Radioactive sensors are sensors that use phenomena such as changes in parameters under the influence of g and b rays; ionization and luminescence of certain substances under the influence of radioactive irradiation. Generator sensors directly convert the input value into an electrical signal. Parametric sensors convert the input value into a change in any electrical parameter (R, L or C) of the sensor.

Based on the principle of operation, sensors can also be divided into ohmic, rheostatic, photoelectric (optoelectronic), inductive, capacitive, etc.

There are three classes of sensors:

Analog sensors, i.e. sensors that produce an analog signal proportional to the change in the input value;

Digital sensors that generate a pulse train or binary word;

Binary (binary) sensors that produce a signal of only two levels: “on/off” (0 or 1).


Figure 1 – Classification of sensors for mining machine automation systems


Requirements for sensors:


Unambiguous dependence of the output value on the input value;

Stability of characteristics over time;

High sensitivity;

Small size and weight;

Absence of reverse impact on the controlled process and on the controlled parameter;

Work under various operating conditions;

Various options installation.

Parametric sensors

Parametric sensors are sensors that convert input signals into a change in some parameter. electrical circuit(R, L or C). In accordance with this, active resistance, inductive, and capacitive sensors are distinguished.

A characteristic feature of these sensors is that they are used only with an external power source.

In modern automation equipment, various parametric active resistance sensors are widely used - contact, rheostatic, potentiometric sensors.

Contact sensors. The most reliable with contact sensors Magnetically controlled sealed contacts (reed switches) are considered.



Figure 1 – Schematic diagram of a reed switch sensor

The sensor's sensing element, the reed switch, is an ampoule 1, inside of which contact springs (electrodes) 2, made of ferromagnetic material, are sealed. The glass ampoule is filled with a protective gas (argon, nitrogen, etc.). The tightness of the ampoule excludes bad influence(impact) of the environment on the contacts, increasing the reliability of their operation. The contacts of the reed switch located at the controlled point in space close under the action magnetic field, which is created by a permanent magnet (electromagnet) installed on a moving object. When the reed switch contacts are open, its active resistance is equal to infinity, and when closed, it is almost zero.

The output signal of the sensor (U out on load R1) is equal to the voltage U p of the power source in the presence of a magnet (object) at the control point and zero in its absence.

Reed switches are available with both make and break contacts, as well as switching and polarized contacts. Some types of reed switches - KEM, MKS, MKA.

The advantages of reed switch sensors are high reliability and mean time between failures (about 10 7 operations). The disadvantage of reed sensors is a significant change in sensitivity with a slight displacement of the magnet in the direction perpendicular to the movement of the object.

Reed sensors are used, as a rule, in the automation of lifting, drainage, ventilation and conveyor installations.

Potentiometric sensors. Potentiometric sensors are a variable resistor (potentiometer) consisting of a flat (strip), cylindrical or ring frame on which a thin wire of constantan or nichrome with high resistivity is wound. A slider moves along the frame - a sliding contact connected mechanically to the object (see Figure 2).

By moving the slider using the appropriate drive, you can change the resistance of the resistor from zero to maximum. Moreover, the resistance of the sensor can change both according to a linear law and according to other, often logarithmic, laws. Such sensors are used in cases where it is necessary to change the voltage or current in the load circuit.


Figure 2 - Potentiometric sensor

For a linear potentiometer (see Figure 2) length l the output voltage is determined by the expression:

,

where x is the movement of the brush; k=U p / l- transfer coefficient; U p – supply voltage.

Potentiometric sensors are used to measure various process parameters - pressure, level, etc., previously converted by a sensing element in motion.

The advantages of potentiometric sensors are their design simplicity, small size, and the ability to be powered by both direct and alternating current.

The disadvantage of potentiometric sensors is the presence of a sliding electrical contact, which reduces the reliability of operation.

Inductive sensors. The principle of operation of the inductive sensor is based on a change in the inductance L of the coil 1, placed on the ferromagnetic core 2, when moving x anchors 3 (see Figure 3).


Figure 3 - Inductive sensor

The sensor circuit is powered from an AC source.

The control element of the sensors is a variable reactance - a choke with a variable air gap.

The sensor works as follows. Under the influence of an object, the armature, approaching the core, causes an increase in flux linkage and, consequently, inductance of the coil. With decreasing gap d to a minimum value, the inductive reactance of the coil x L = wL = 2pfL increases to a maximum, reducing the load current RL, which is usually an electromagnetic relay. The latter, with their contacts, switch control, protection, monitoring circuits, etc.

The advantages of inductive sensors are the simplicity of the device and reliability of operation due to the absence of a mechanical connection between the core and the armature, which is usually attached to a moving object, the position of which is controlled. The functions of an anchor can be performed by an object itself that has ferromagnetic parts, for example a skip when controlling its position in the shaft.

The disadvantages of inductive sensors are the nonlinearity of the characteristics and the significant electromagnetic force of attraction of the armature to the core. To reduce forces and continuously measure displacements, solenoid-type sensors are used, or they are called differential.

Capacitive sensors. Capacitive sensors are structurally variable capacitors of various designs and shapes, but always with two plates, between which there is a dielectric medium. Such sensors are used to convert mechanical linear or angular movements, as well as pressure, humidity or environmental level into a change in capacity. In this case, to control small linear movements, capacitors are used in which the air gap between the plates changes. To control angular movements, capacitors with a constant gap and variable working area of ​​the plates are used. For monitoring tank filling levels bulk materials or liquids with constant gaps and working areas of the plates - capacitors with the dielectric constant of the medium being controlled. The electrical capacity of such a capacitor is calculated by the formula

where: S - Total intersection area of ​​the plates; δ - distance between plates; ε - the dielectric constant environment between the plates; ε 0 is the dielectric constant.

Based on the shape of the plates, flat, cylindrical and other types of variable capacitors are distinguished.

Capacitive sensors only operate at frequencies above 1000Hz. Use at industrial frequency is practically impossible due to the high capacitance (Xc = = ).

Generator sensors

Generator sensors are sensors that directly transform various kinds energy into electrical energy. They do not require external power sources because they themselves produce emf. Generator sensors use well-known physical phenomena: the occurrence of EMF in thermocouples when heated, in photocells with a barrier layer when illuminated, the piezoelectric effect and the phenomenon of electromagnetic induction.

Induction sensors. In induction sensors, the conversion of an input non-electrical quantity into an induced emf. used to measure movement speed, linear or angular movements. E.m.f. in such sensors it is induced in coils or windings made of insulated copper wire and placed on magnetic circuits made of electrical steel.

Small-sized microgenerators that convert the angular velocity of an object into emf, the value of which is directly proportional to the rotation speed of the output shaft of the test object, are called tachogenerators of direct and alternating currents. Circuits of tachogenerators with and without an independent excitation winding are shown in Figure 4.

Figure 4 - Schemes of tachogenerators with and without an independent excitation winding

DC tachogenerators are a collector electric car with armature and field winding or permanent magnet. The latter do not require an additional power source. The principle of operation of such tachogenerators is that an emf is induced in the armature, which rotates in the magnetic flux (F) of a permanent magnet or field winding. (E), the value of which is proportional to the rotation frequency (ω) of the object:

E = cФn = cФω

To maintain the linear dependence of the emf. depending on the speed of rotation of the armature, it is necessary that the load resistance of the tachogenerator always remains unchanged and is many times higher than the resistance of the armature winding. The disadvantage of DC tachogenerators is the presence of a commutator and brushes, which significantly reduces its reliability. The collector provides conversion of alternating emf. armatures in direct current.

More reliable is an alternating current tachogenerator, in which the output intrinsically safe winding is located on the stator, and the rotor is permanent magnet with a corresponding constant magnetic flux. Such a tachogenerator does not require a collector, but its variable emf. converted to direct current using bridge diode circuits. The principle of operation of a synchronous alternating current tachogenerator is that when the rotor is rotated by the control object, a variable emf is induced in its winding, the amplitude and frequency of which are directly proportional to the rotor rotation speed. Due to the fact that the magnetic flux of the rotor rotates at the same frequency as the rotor itself, such a tachogenerator is called synchronous. disadvantage synchronous generator is that it has bearing units, which is not appropriate for mining conditions. The diagram for controlling the speed of a conveyor belt with a synchronous tachogenerator is shown in Figure 5. Figure 5 indicates: 1 - magnetic rotor of the tachogenerator, 2 - drive roller with tread, 3 - conveyor belt, 4 - stator winding of the tachogenerator.

Figure 5 - Scheme for synchronous conveyor belt speed control

tachogenerator

To measure the linear speed of movement of the working bodies of scraper conveyors, magnetic induction sensors are used, which have no moving parts at all. The moving part (armature) in this case is the steel scrapers of the conveyor, moving in the magnetic flux of a permanent magnet sensor with an intrinsically safe coil. When steel scrapers cross a magnetic flux in the coil, a variable emf is induced, directly proportional to the speed of movement and inversely proportional to the gap between the steel core of the coil and the scraper. The magnetic flux, which leads to the emf, in the coil in this case changes under the influence of steel scrapers, which, moving above the sensor, cause fluctuations in the magnetic resistance along the path of closing the magnetic flux formed by the permanent magnet. The diagram for monitoring the speed of movement of the working body of a scraper conveyor using a magnetic induction sensor is shown in Figure 6. Figure 6 indicates: 1 - scraper conveyor, 2 - steel core, 3 - steel washer, 4 - plastic washer, 5 - ring permanent magnet, 6 - sensor coil

Figure 6 - Scheme for controlling the speed of movement of the working body

scraper conveyor with magnetic induction sensor

Magnetoelastic sensors. The principle of operation of magnetoelastic sensors is based on the property of ferromagnetic materials to change the magnetic permeability m when they are deformed. This property is called magnetoelasticity, which is characterized by magnetoelastic sensitivity

Highest value S m = 200 H/m2 is based on permallay (iron-nickel alloy). Some varieties of permallay, when elongated by 0.1%, increase the coefficient of magnetic permeability up to 20%. However, to obtain even such small elongations, a load of the order of 100 - 200 N/mm is required, which is very inconvenient and leads to the need to reduce the cross-section of the ferromagnetic material and requires a power source with a frequency of the order of kilohertz.

Structurally, the magnetoelastic sensor is a coil 1 with a closed magnetic circuit 2 (see Figure 7). The controlled force P, deforming the core, changes its magnetic permeability and, consequently, the inductive reactance of the coil. The load current RL, for example, a relay, is determined by the resistance of the coil.

Magnetoelastic sensors are used to monitor forces (for example, when loading skips and planting cages on fists), rock pressures, etc.

The advantages of magnetoelastic sensors are simplicity and reliability.

The disadvantages of magnetoelastic sensors are that expensive materials for magnetic circuits and their special processing are required.

Figure 7 – Magnetoelastic sensor

Piezoelectric sensors. The piezoelectric effect is inherent in single crystals of some dielectric substances (quartz, tourmaline, Rochelle salt, etc.). The essence of the effect is that under the action of dynamic mechanical forces on the crystal, electric charges arise on its surfaces, the magnitude of which is proportional to the elastic deformation of the crystal. The dimensions and number of crystal plates are selected based on the strength and the required amount of charge. Piezoelectric sensors in most cases are used to measure dynamic processes and shock loads, vibration, etc.

Thermoelectric sensors. To measure temperatures in within wide limits 200-2500 °C thermoelectric sensors are used - thermocouples, which ensure the conversion of thermal energy into electrical emf. The principle of operation of a thermocouple is based on the phenomenon of the thermoelectric effect, which consists in the fact that when the junction and ends of thermoelectrodes are placed in an environment with different temperatures t 1 and t 2 in a circle formed by a thermocouple and a millivoltmeter, a thermo emf appears, proportional to the difference between these temperatures

Figure 8 - Thermocouple diagram

Conductors A and B of thermocouples are made of dissimilar metals and their alloys. The phenomenon of thermoelectric effect is given by a combination of such conductors A and B, copper-constantan (up to 300 ° C), copper - kopel (up to 600 ° C), chromel - kopel (up to 800 ° C), iron - kopel (up to 800 ° C) , chromel - alumel (up to 1300 ° C), platinum - platinum-rhodium (up to 1600 ° C), etc.

Thermal emf value for various types thermocouples range from tenths to tens of millivolts. For example, for a copper-constantan thermocouple it changes from 4.3 to –6.18 mB when the junction temperature changes from + 100 to – 260 o C.

Thermistor sensors. The operating principle of thermistor sensors is based on the property of the sensing element - the thermistor - to change resistance when the temperature changes. Thermistors are made of metals (copper, nickel, atin, etc.) and semiconductors (mixtures of metal oxides - copper, manganese, etc.). A metal thermistor is made of wire, for example copper, with a diameter of approximately 0.1 mm, wound in the form of a spiral on a mica, porcelain or quartz frame. Such a thermistor is enclosed in a protective tube with terminal clamps, which is located at the temperature control point of the object.

Semiconductor thermistors are manufactured in the form of small rods and disks with leads.

With increasing temperature, the resistance of metal thermistors increases, while for most semiconductor ones it decreases.

The advantage of semiconductor thermistors is their high thermal sensitivity (30 times more than metal ones).

The disadvantage of semiconductor thermistors is the large spread of resistance and low stability, which makes them difficult to use for measurements. Therefore, semiconductor thermistors in mine automation systems technological installations mainly used to monitor the temperature values ​​of objects and their thermal protection. In this case, they are usually connected in series with an electromagnetic relay to the power source.

To measure temperature, the thermistor RK is included in a bridge circuit, which converts the resistance measurement into a voltage at the output Uout, used in the automatic control system or measuring system.

The bridge can be balanced or unbalanced.

A balanced bridge is used with the zero measurement method. In this case, the resistance R3 changes (for example, with a special automatic device) following a change in the resistance of the thermistor Rt in such a way as to ensure equality of potential at points A and B. If the scale of the resistor R3 is graduated in degrees, then the temperature can be read based on the position of its slider. The advantage of this method is high accuracy, but the disadvantage is complexity. measuring device, which is an automatic tracking system.

An unbalanced bridge produces a signal Uout, proportional to the overheating of the object. By selecting the resistances of resistors R1, R2, R3, the equilibrium of the bridge is achieved at the initial temperature value, ensuring that the condition is met

Rt / R1= R3 / R2

If the value of the controlled temperature and, accordingly, the resistance Rt changes, the balance of the bridge will be disrupted. If you connect an mV device with a scale graduated in degrees to its output, the device’s needle will show the measured temperature.

Induction flow meter

To control the supply of a drainage pumping unit, it is possible to use induction flow meters, for example, type IR-61M. The operating principle of an induction flow meter is based on Faraday's law (the law of electromagnetic induction).

Structural diagram induction flowmeter is shown in Figure 9. When a conducting liquid flows in a pipeline between the poles of a magnet, an emf occurs in a direction perpendicular to the direction of the liquid and in the direction of the main magnetic flux. U on the electrodes, proportional to the fluid velocity v:

where B is the magnetic induction in the gap between the magnet poles; d – internal diameter of the pipeline.

Figure 9 – Design diagram of an induction flow meter

If we express the speed v in terms of the volumetric flow rate Q, i.e.

Advantages of an induction flow meter:

They have a slight inertia of readings;

There are no parts inside the working pipeline (therefore they have minimal hydraulic losses).

Disadvantages of the flow meter:

The readings depend on the properties of the liquid being measured (viscosity, density) and the nature of the flow (laminar, turbulent);

Ultrasonic flow meters

The operating principle of ultrasonic flow meters is that

the speed of propagation of ultrasound in a moving medium of gas or liquid is equal to the geometric sum of the average speed of movement of the medium v ​​and the natural speed of sound in this medium.

The design diagram of the ultrasonic flow meter is shown in Figure 10.

Figure 10 - Design diagram of an ultrasonic flow meter

The emitter I creates ultrasonic vibrations with a frequency of 20 Hz and higher, which fall on the receiver P, which registers these vibrations (it is located at a distance l). Flow rate F is equal to

where S is the cross-sectional area of ​​the fluid flow; C – speed of sound in the medium (for liquid 1000-1500 m/s);

t1 is the duration of propagation of the sound wave in the direction of flow from the emitter I1 to the receiver P1;

t 2 – duration of propagation of the sound wave against the flow from the emitter I2 to the receiver P2;

l is the distance between the emitter I and the receiver P;

k – coefficient taking into account the distribution of speeds in the flow.

Advantages of an ultrasonic flow meter:

a) high reliability and speed;

b) the ability to measure non-conductive liquids.

Disadvantage: increased requirements for contamination of the controlled water flow.

2. Data transmission devices

Information is transferred from the automation object to the control device via communication lines (channels). Depending on the physical medium through which information is transmitted, communication channels can be divided into the following types:

cable lines– electrical (symmetrical, coaxial, “ twisted pair", etc.), fiber-optic and combined electrical cables with fiber-optic cores;

– power low-voltage and high-voltage electrical networks;

– infrared channels;

– radio channels.

Information transmission over communication channels can be transmitted without information compression, i.e. One information signal (analog or discrete) is transmitted over one channel, and with information compression, many information signals are transmitted over a communication channel. Information compaction is used for remote transmission of information over a considerable distance (for example, from automation equipment located on a roadway to a shearer or from a section of a mine to the surface to a dispatcher) and can be done using various types of signal coding.

Technical systems, which ensure the transmission of information about the state of the object and control commands over a distance via communication channels can be remote control and measurement systems or telemechanical systems. In remote control and measurement systems, each signal uses its own line - a communication channel. As many signals as there are, so many communication channels are required. Therefore, with remote control and measurement, the number of controlled objects, especially over long distances, is usually limited. In telemechanical systems, only one line, or one communication channel, is used to transmit many messages to a large number of objects. Information is transmitted in encoded form, and each object “knows” its code, so the number of controlled or managed objects is practically unlimited, only the code will be more complex. Telemechanics systems are divided into discrete and analog. Discrete telecontrol systems are called telealarm systems(TS), they provide the transmission of a finite number of object states (for example, “on”, “off”). Analog television monitoring systems are called telemetering systems(TI), they provide the transmission of continuous changes in any parameters characterizing the state of the object (for example, changes in voltage, current, speed, etc.).

The elements that make up discrete signals have various qualitative characteristics: pulse amplitude, pulse polarity and duration, frequency or phase of alternating current, code in sending a series of pulses. Telemechanical systems are discussed in more detail in.

To exchange information between microprocessor controllers of various automation system devices, including control computers, they are used special means, methods and rules of interaction – interfaces. Depending on the method of data transfer, a distinction is made between parallel and serial interfaces. IN parallel interface q bits of data are transmitted over q communication lines. IN serial interface Data transmission is usually carried out over two lines: one continuously transmits clock (synchronizing) pulses from the timer, and the second carries information.

In mining machine automation systems, serial interfaces of the RS232 and RS485 standards are most often used.

The RS232 interface provides communication between two computers, a control computer and a microcontroller, or communication between two microcontrollers at speeds up to 19600 bps over a distance of up to 15m.

The RS-485 interface provides data exchange between several devices over one two-wire communication line in half-duplex mode. The RS-485 interface provides data transfer at speeds up to 10 Mbit/s. The maximum transmission range depends on the speed: at a speed of 10 Mbit/s maximum length line - 120 m, at a speed of 100 kbit/s - 1200 m. The number of devices connected to one interface line depends on the type of transceivers used in the device. One transmitter is designed to control 32 standard receivers. Receivers are available with input impedances of 1/2, 1/4, 1/8 of the standard. When using such receivers, the total number of devices can be increased accordingly: 64, 128 or 256. Data transfer between controllers is carried out according to rules called protocols. Exchange protocols in most systems operate on a master-slave principle. One device on the highway is the master and initiates the exchange by sending requests to slave devices, which differ in logical addresses. One of the popular protocols is the Modbus protocol.

2. Actuators

Execution of the decision, i.e. the implementation of the control action corresponding to the generated control signal is carried out actuators (ED). In general, an actuator is a combination of an actuator (AM) and a regulatory body (RO). The location of the actuators in the block diagram of the local ACS is shown in Figure 11.

Figure 11 - Location of actuators in the block diagram of a local automatic control system

An actuator (AM) is a device designed to convert control signals generated by the control unit (PLC) into signals convenient for influencing the final link of the ACS - the regulatory body (RO).

The actuator consists of the following basic elements:

executive motor (electric motor, piston, membrane);

clutch element (coupling, hinge);

transmission-converting element (gearbox with output lever or rod);

power amplifier (electric, pneumatic, hydraulic, combined)

In a specific MI model, a number of elements (except for the actuator motor) may be missing.

The main requirement for the IM: movement of the RO with the least possible distortion of the control laws of the generated PLC, i.e. The MI must have sufficient speed and accuracy.

Main characteristics:

a) nominal and maximum torque value

on the output shaft (rotary) or forces on the output rod;

b) the rotation time of the output shaft of the IM or the stroke of its rod;

c) the maximum value of the output shaft rotation angle or stroke

d) dead zone.

Actuators are classified according to the following signs:

1) movement of the regulatory body (rotary and linear);

2) design (electric, hydraulic, pneumatic);

Electric – with drives electric motor and an electromagnet;

Hydraulic – with drives: piston, plunger, from a hydraulic motor;

Pneumatic – with drives: piston, plunger, membrane, diaphragm, from an air motor.

In practice, electrical MI is most widely used. Electrical MI are classified as:

electromagnetic;

electric motor

Electromagnetic MI are divided into:

IM with drives from electromagnetic couplings designed to transmit rotational motion (friction and sliding clutches;

IMs with a solenoid drive are 2-position devices (i.e., designed for 2-position control) that carry out translational movement of the drive elements according to the discrete principle: “on - off.”

Electric motor MI are divided into:

single-turn - the angle of rotation of the output shaft does not exceed 360 0. Example: MEO (electric single-turn mechanism). They use single-phase and three-phase (MEOK, MEOB) asynchronous motors.

multi-turn – for remote and local control of pipeline fittings (valves).

In automation systems of mining machines, electric hydraulic distributors, for example the GSD and 1RP2 types, are widely used as actuators. The 1RP2 electric hydraulic distributor is designed to control the feed speed and cutting elements of the combine as part of the URAN.1M automatic load controllers and the SAUK02.2M automation system. The 1RP2 electrohydraulic distributor is a hydraulic spool valve with a pull-type electromagnetic drive.

Regulatory body (RO) is the final element of the ACS that exercises direct control influence on the OS. RO changes the flow of material, energy, mutual arrangement parts of apparatus, machines or mechanisms in the direction of the normal flow of the technological process.

The main characteristic of the RO is its static characteristic, i.e. the relationship between the output parameter Y (flow, pressure, voltage) and the stroke value of the regulator in percent.

RO provide:

a) two-position regulation - the RO gate quickly moves from one extreme position to another.

b) continuous - in this case it is necessary that the throughput characteristic of the RO be strictly defined (gate, tap, butterfly valve).

The means of generating and primary processing of information include keyboard devices for applying data to cards, tapes or other information carriers by mechanical (punching) or magnetic methods; the accumulated information is transferred for subsequent processing or reproduction. Keyboard devices, punching or magnetic blocks and transmitters are used to make up production recorders for local and system purposes, which generate primary information in workshops, warehouses and other places of production.

Sensors (primary transducers) are used to automatically extract information. They are very diverse devices in terms of operating principles that sense changes in the controlled parameters of technological processes. Modern measuring technology can directly evaluate more than 300 different physical, chemical and other quantities, but this requires automation in a number of new areas human activity sometimes it's not enough. An economically feasible expansion of the range of sensors in the GPS is achieved by unifying the sensitive elements. Sensitive elements that respond to pressure, force, weight, speed, acceleration, sound, light, thermal and radioactive radiation are used in sensors to control the loading of equipment and its operating modes, the quality of processing, accounting for the release of products, monitoring their movements on conveyors, stocks and consumption of materials, workpieces, tools, etc. The output signals of all these sensors are converted into standard electrical or pneumatic signals, which are transmitted by other devices.

Devices for transmitting information include signal converters into forms of energy convenient for broadcasting, telemechanics equipment for transmitting signals via communication channels over long distances, switches for distributing signals to places where information is processed or presented. These devices connect all peripheral sources of information (keyboard devices, sensors) with the central part of the control system. Their purpose is efficient use communication channels, eliminating signal distortion and the influence of possible interference during transmission over wired and wireless lines.

Devices for logical and mathematical information processing include functional converters that change the nature, shape or combination of information signals, as well as devices for processing information according to given algorithms (including computers) in order to implement laws and control (regulation) modes.

Computers for communication with other parts of the control system are equipped with information input and output devices, as well as storage devices for temporary storage of source data, intermediate and final results calculations, etc. (see Data input. Data output, Storage device).

Devices for presenting information show the human operator the state of production processes and record it the most important parameters. Such devices are signal boards, mnemonic diagrams with visual symbols on boards or control panels, secondary pointer and digital indicating and recording instruments, cathode ray tubes, alphabetic and digital typewriters.

Devices for generating control actions convert weak information signals into more powerful energy pulses of the required shape, necessary to activate protection, regulation or control actuators.

Security High Quality products is associated with automation of control at all main stages of production. Subjective human assessments are replaced by objective indicators from automatic measuring stations linked to central points where the source of defects is determined and from where commands are sent to prevent deviations outside of tolerances. Automatic control using computers in the production of radio-technical and radio-electronic products is of particular importance due to their mass production and a significant number of controlled parameters. No less important are final tests of finished products for reliability (see Reliability technical devices). Automated stands for functional, strength, climatic, energy and specialized tests allow you to quickly and identically check technical and economic characteristics products (products).

Actuating devices consist of starting equipment, actuating hydraulic, pneumatic or electrical mechanisms (servomotors) and regulatory bodies that act directly on the automated process. It is important that their operation does not cause unnecessary energy losses and reduce the efficiency of the process. For example, throttling, which is usually used to regulate the flow of steam and liquids, based on an increase hydraulic resistance in pipelines, they are replaced by influencing flow-forming machines or other, more advanced methods of changing the flow speed without loss of pressure. Of great importance is the economical and reliable control of an alternating current electric drive, the use of gearless electric actuators, and contactless ballasts for controlling electric motors.

The idea of ​​constructing instruments for monitoring, regulation and control in the form of units consisting of independent blocks that perform certain functions, implemented in GSP, made it possible, through various combinations of these blocks, to obtain a wide range of devices for solving diverse problems using the same means. Unification of input and output signals ensures the combination of blocks with different functions and their interchangeability.

The GSP includes pneumatic, hydraulic and electrical devices and devices. Electrical devices designed to receive, transmit and reproduce information are the most versatile.

The use of a universal system of industrial pneumatic automation elements (USEPPA) made it possible to reduce the development of pneumatic devices mainly to assembling them from standard units and parts with a small number of connections. Pneumatic devices are widely used for control and regulation in many fire and explosion hazardous industries.

GSP hydraulic devices are also assembled from blocks. Hydraulic instruments and devices control equipment that requires high speeds to move control elements with significant effort and high precision, which is especially important in machine tools and automatic lines.

In order to most rationally systematize GSP facilities and to increase the efficiency of their production, as well as to simplify the design and configuration of automated control systems, GSP devices are combined into aggregate complexes during development. Aggregate complexes, thanks to the standardization of input-output parameters and block design of devices, most conveniently, reliably and economically combine various technical means into automated systems controls and allow you to assemble a variety of specialized installations from multi-purpose automation units.

Targeted aggregation of analytical equipment, testing machines, mass-dosing mechanisms with unified measuring, computing and office equipment facilitates and accelerates the creation of basic designs of this equipment and the specialization of factories for their production.

The classification of technical automation equipment is not something too complicated and loaded. However, in general, technological automation tools have a fairly ramified classification structure. Let's try to deal with it.

Modern means automation are divided into two groups: switched and non-commutated (programmed) technical means of automation:

1) Switched automation equipment

Regulators

Relay circuits

2) Programmed automation tools

ADSP processors

ADSP processors are an automation tool that is used for complex mathematical analysis of processes in the system. These processors have high-speed input/output modules that can transmit data at high frequencies to the central processor, which uses complex mathematics to analyze the operation of the system. An example is vibration diagnostic systems that use Fourier series for analysis, spectral analysis and a pulse counter. As a rule, such processors are implemented in the form of a separate PCI card, which is mounted in the appropriate slot of the computer and uses the CPU for mathematical processing.

PLC (Programmable Logic Controller)

PLCs are the most common automation tools. They have their own power supply, central processor, RAM, network card, input/output modules. The advantage is high reliability of the system, adaptation to industrial conditions. In addition, programs are used that run cyclically and have a so-called Watch Dog, which is used to prevent the program from freezing. Also, the program runs sequentially and does not have parallel connections and processing steps that could lead to negative consequences.

PKK (Programmable Computer Controllers)

PKK is a computer with input/output cards, network cards that are used for input/output of information.

PACK

PAK ( programmed automated controllers) – PLC+PKK. They have a distributed network structure for data processing (several PLCs and PCs).

· Specialized controllers

Specialized controllers are not freely programmable automation tools, but use standard programs in which only some coefficients can be changed (PID controller parameters, actuator running time, delays, etc.). Such controllers are focused on a previously known control system (ventilation, heating, hot water supply). At the beginning of the new millennium, these technical means of automation became widespread.

A feature of ADSP and PKK is the use of standard programming languages: C, C++, Assembler, Pascal, since they are created on a PC. This feature of automation tools is both an advantage and a disadvantage.

The advantage is that a more complex and flexible algorithm can be written using standard programming languages. The disadvantage is that to work with them you need to create drivers and use a programming language, which is more complex. The advantage of PLCs and PACs is the use of engineering programming languages ​​that are standardized by IEC 61131-3. These languages ​​are not designed for a programmer, but for an electrical engineer.

Principle of information transformation

Management principles are based on the principle of information transformation.

Converters are devices used to convert quantities of one physical nature into another and vice versa.

Sensors are devices that produce a discrete signal depending on the code of the technological process or the impact of information on them.

Information and methods for converting it

The information must have the following properties:

1. Information must be understandable in accordance with the adopted coding system or its presentation.

2. Information transmission channels must be noise-proof and prevent the penetration of false information.

3. Information must be convenient for processing.

4. Information should be convenient for storing it.

To transmit information, communication channels are used, which can be artificial, natural, or mixed.

Rice. 3. Communication channels

We will talk in more detail about communication channels a little later.